Daikin FXSQ125PVE4 [306/370] Centralized address duplication

Daikin FXHQ32MAVS [306/370] Centralized address duplication
Troubleshooting by Indication on the Remote Controller SiBE311209
297 Service Diagnosis
4.54 Centralized Address Duplication
Remote
Controller
Display
UC
Applicable
Models
All indoor unit models
Method of Error
Detection
The principal indoor unit detects the same address as that of its own on any other indoor unit.
Error Decision
Conditions
The error decision is made as soon as the abnormality aforementioned is detected.
Supposed
Causes
Address duplication of centralized controller
Defective indoor unit PCB
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
The centralized address is
duplicated.
Make setting change so that
the centralized address will not
be duplicated.