Daikin FXSQ100P7VEB Сервис мануал онлайн [148/370] 544695

Daikin FXSQ100P7VEB Сервис мануал онлайн [148/370] 544695
Test Operation SiBE311209
139 Test Operation
It is possible to find out how many indoor units are active and connected by operating the BS
button on the PCB (A1P) of the working outdoor unit.
Make sure that all the indoor units connected to the outdoor unit are active.
Follow the 5-step procedure as explained below.
The LEDs on the A1P shows the operating status of the outdoor unit and the number of
indoor units that are active.
The number of units that are active can be read from the LED display in the "Monitor Mode"
procedure below.
Example: in the following procedure there are 22 units active:
Note: Wherever during this procedure, press the BS1 MODE button if something becomes unclear.
You will return to setting mode 1 (H1P =
h
"OFF").
Press the BS1 MODE button to switch from setting mode 1 to monitor mode.
To check the number of indoor units, press the BS2 SET button 5 times.
Pressing the BS3 RETURN button causes the LED display to show the data on the number
of indoor units that are connected.
Calculate the number of connected indoor units by adding the values of all (H2P~H7P) blinking
(
l
) LEDs together.
In this example: 16 + 4 + 2 = 22 units
Press the BS1 MODE button to return to step 1, setting mode 1 (H1P =
h
"OFF").
(a) The state of the H8P (multi) LED in a multi-system shows which unit is the master
unit (
k
), slave 1 unit (
l
).
Only the master unit is connected to the indoor units with transmission wiring.
1. How to check how many units are connected
h: OFF k: ON l: Blinking
1 Setting mode 1 (default system status)
H1P H2P H3P H4P H5P H6P H7P
Default status (normal)
hhkhhhh
2 Monitor mode
H1P H2P H3P H4P H5P H6P H7P
Default status display
lhhhhhh
3 Monitor mode
H1P H2P H3P H4P H5P H6P H7P
Selection status of how many
connected indoor units to
display.
lhhhkhk
4 Monitor mode
H1P H2P H3P H4P H5P H6P H7P
Displaying the number of
connected indoor units
lhlhllh
32 16 8 4 2 1
2. Normal system display
LED display
(Default status
before delivery)
Micro-
computer
operation
monitor
Mode
Ready/
Error
Cooling/Heating
changeover
Low
noise
Demand
Multi
Individual
Bulk
(master)
Bulk
(slave)
HAP
H1P H2P H3P H4P H5P H6P H7P H8P
Single outdoor unit
system
l hhkhhhhh
Multiple
outdoor
unit
system
Master
unit
(a)
l hhkhhhhk
Slave
unit 1
(a)
l hhhhhhhloo
or
h

Содержание

Скачать