Daikin FXSQ100P7VEB [274/370] Overcurrent of inverter compressor

Daikin FXSQ25PVE [274/370] Overcurrent of inverter compressor
Troubleshooting by Indication on the Remote Controller SiBE311209
265 Service Diagnosis
4.38 Overcurrent of Inverter Compressor
Remote
Controller
Display
L8
Applicable
Models
Outdoor Unit: RTSQ8~16PAY1
Method of Error
Detection
Error is detected by current flowing in the power transistor.
Error Decision
Conditions
When overload in the compressor is detected (Inverter secondary current 16.1A)
(1) 19.0A and over continues for 5 seconds
(2) 16.1A and over continues for 260 seconds
Supposed
Causes
Compressor overload
Compressor coil disconnected
Disconnection of compressor
Defective inverter PCB