SiBE311209 Rotation Control
Function 86
4. Rotation Control
4.1 Rotation of Outdoor Units
In order to make operating time equal for each compressor of multi connection outdoor units,
outdoor units are used in rotation.
[Rotation of outdoor units]
[System with two outdoor units]
[Timing of outdoor rotation]
In start of startup control
4.2 Operating Priority and Rotation of Compressors
[System with one outdoor unit]
[System with two outdoor units]
Used in 2 patterns of “Rotation Operation” as shown in the following.
Outdoor Unit 1 Outdoor Unit 2
Previous time Priority 1 Priority 2
This time Priority 2 Priority 1
Next time Priority 1 Priority 2
Each compressor operates in the following order of priority. INV.: Inverter compressor
STD1: Standard compressor 1
STD2: Standard compressor 2
RTSYQ10PA
RTSYQ14PA
RTSYQ16PA
No.1 No.2
INV. STD1
No.1 No.2
INV. STD1
No.3
STD2
RTSYQ20PA
No.1 No.2 No.3
No.2 No.1 No.3
INV. INV. STD1