Daikin FXSQ100P7VEB [213/370] Malfunction code indication by outdoor unit pcb

Daikin FXZQ50MVE [213/370] Malfunction code indication by outdoor unit pcb
SiBE311209 Troubleshooting by Remote Controller
Service Diagnosis 204
Malfunction code indication by outdoor unit
PCB
<Monitor mode>
To enter the monitor mode, press the
MODE (BS1) button when in “Setting
mode 1”.
<Selection of setting item>
Refer to P.172 for Monitor mode.
Refer to P.172 for Monitor mode.
Press the SET (BS2) button and set
the LED display to a setting item.
<Confirmation of error 1>
Press the RETURN (BS3) button
once to display "First digit" of error
code.
<Confirmation of error 2>
Press the SET (BS2) button once to
display "Second digit" of error code.
<Confirmation of error 3>
Press the SET (BS2) button once to
display "error location".
<Confirmation of error 4>
Press the SET (BS2) button once to
display "master or slave 1 or slave 2"
and "error location".
Detail
description
on next
page.
Press the RETURN (BS3) button and
switches to the initial status of
“Monitor mode”.
Press the MODE (BS1) button and
returns to “Setting mode 1”.
Errors Error code
Description of malfunction Description of malfunction (PGF) Remote
controller
PCB malfunction PCB malfunction E1
Faulty PCB
Abnormal discharge pressure High pressure switch activated E3
Abnormal suction pressure Pe malfunction E4
Compressor lock INV compressor lock detected E5
OC activation STD1 compressor lock detected E6
STD2 compressor lock detected
Overload, overcurrent and abnormal
lock of outdoor unit fan motor
Instantaneous overcurrent of 1DC fan motor
E7
1DC fan motor lock detected
Fan 1 IPM faulty protection detected
Instantaneous overcurrent of 2DC fan motor
2DC fan motor lock detected
Fan 2 IPM faulty protection detected
Electronic expansion valve
malfunction
EVM (main) E9
EVJ (refrigerant charging)
EVT (subcooling heat exchanger)
Abnormal discharge pipe temperature Td malfunction F3
Abnormal heat exchanger temperature
Refrigerant overcharged F6
Positioning signal malfunction of
outdoor unit fan motor
1DC fan motor positioning signal
malfunction
H7
2DC fan motor positioning signal
malfunction
Abnormal outdoor air temperature Ta sensor malfunction (short-circuited
or open)
H9
Current sensor malfunction CT1 sensor malfunction (STD
compressor 1)
J2
CT2 sensor malfunction (STD
compressor 2)
CT sensor malfunction (system)
Discharge pipe temperature sensor
malfunction
Tdi sensor malfunction J3
Tds1 sensor malfunction (short-
circuited)
Tds2 sensor malfunction (short-
circuited)
Heat exchanger gas temperature
sensor malfunction
Tg sensor malfunction (R2T) J4
Suction pipe temperature sensor
malfunction
TsA sensor malfunction (short-
circuited) (R8T)
J5
Heat exchanger temperature sensor
malfunction
Tb sensor malfunction (R4T) J6
Liquid pipe temperature sensor
malfunction
Tsc sensor malfunction (R6T) J7
TL sensor malfunction (R9T)
Heat exchanger liquid pipe
temperature sensor malfunction
Tf sensor malfunction (R7T) J8
Subcooling heat exchanger
temperature sensor malfunction
Tsh sensor malfunction (R5T) J9
Discharge pressure sensor malfunction
Pc sensor malfunction (S1NPH) JA
Suction pressure sensor malfunction Pe sensor malfunction (S1NPL) JC
INV PCB malfunction Faulty IPM
Current sensor failure confirmation 1
Current sensor failure confirmation 2
IGBT malfunction
L1
Rise in INV radiation fin temperature
Overheat of INV radiation fin temperature
L4
DC output overcurrent INV. compressor (outdoor unit) L5
INV. compressor (function unit)
Electronic thermal Electronic thermal 1 L8
Electronic thermal 2
Loss of synchronization
Speed degradation after startup
Thunder detected
Stall prevention (time limit) Stall prevention (increased current) L9
Stall prevention (startup failure)
Abnormal starting waveform
Loss of synchronization
INV transmission malfunction INV. transmission data malfunction LC
INV. transmission malfunction
k
: ON
l
: Blink
h
: OFF