Daikin FXSQ100P7VEB [259/370] Discharge pipe thermistor r31t r32t r33t abnormality

Daikin FXSQ100P7VEB [259/370] Discharge pipe thermistor r31t r32t r33t abnormality
SiBE311209 Troubleshooting by Indication on the Remote Controller
Service Diagnosis 250
4.26 Discharge Pipe Thermistor (R31T, R32T, R33T)
Abnormality
Remote
Controller
Display
J3
Applicable
Models
Outdoor Unit: RTSQ8~16PAY1
Function Unit: BTSQ20PY1
Method of Error
Detection
Error is detected from the temperature detected by discharge pipe thermistor.
Error Decision
Conditions
When a short circuit or an open circuit in the discharge pipe thermistor is detected
Supposed
Causes
Defective connection of thermistor
Defective outdoor unit discharge pipe thermistor (R31T, R32T, R33T)
Defective outdoor unit PCB (A1P)
Troubleshooting
The alarm indicator is displayed when the fan is being used also.
Refer to P.314.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Connector is
connected to X29A
of outdoor unit PCB
(A1P).
NO
Connect the connector and turn ON
again.
Confirm which discharge
thermistor is abnormal using
outdoor unit "monitor mode".
Resistance is normal when
measured after
disconnecting the thermistor
R31, 32T or R33T from the
outdoor unit PCB.
CHECK 11
YES
NO
YES
Replace the thermistor (R31, 32T
or R33T)
Replace the outdoor unit PCB
(A1P).
CHECK 11