Daikin RXQ46MAY1 Сервис мануал онлайн [179/344] 545802

Daikin RXQ26MAY1 Сервис мануал онлайн [179/344] 545648
Troubleshooting by Remote Controller Si39-501
168 Troubleshooting
8: ON 7: OFF 9: Blink
Malfunction
code
Operation
lamp
Inspection
display
Unit No. Malfunction contents Page
Referred
Indoor
Unit
A0 999Error of external protection device 172
A1 999PC board defect, E
2
PROM defect 173
A3 999Malfunction of drain level control system (S1L) 174
A6 999Fan motor (M1F) lock, overload 176
A7 879Malfunction of swing flap motor (MA) 177
A9 999Malfunction of moving part of electronic expansion
valve (20E)
179
AF 879Drain level about limit 181
AH 879Malfunction of air filter maintenance
AJ 999Malfunction of capacity setting 182
C4 999Malfunction of thermistor (R2T) for heat exchange
(loose connection, disconnection, short circuit, failure)
183
C5 999Malfunction of thermistor (R3T) for gas pipes (loose
connection, disconnection, short circuit, failure)
184
C9 999Malfunction of thermistor (R1T) for air inlet (loose
connection, disconnection, short circuit, failure)
185
CJ 888Malfunction of thermostat sensor in remote controller 186
Outdoor
Unit
E1 999PC board defect 187
E3 999Actuation of high pressure switch 188
E4 999Actuation of low pressure sensor 189
E5 999Compressor motor lock 190
E6 999Standard compressor lock or over current 191
E7 999Malfunction of outdoor unit fan motor 192
E9 999Malfunction of moving part of electronic expansion
valve (Y1E~3E)
194
F3 999Abnormal discharge pipe temperature 196
F6 999Refrigerant overcharged 197
H3 879Malfunction of High pressure switch
H4 999Malfunction of Low pressure switch
H7 999Abnormal outdoor fan motor signal 198
H9 999Malfunction of thermistor (R1T) for outdoor air (loose
connection, disconnection, short circuit, failure)
199
J2 999Current sensor malfunction 200
J3 999Malfunction of discharge pipe thermistor (R31~33T)
(loose connection, disconnection, short circuit,
failure)
201
J5 999Malfunction of thermistor (R2T) for suction pipe
(loose connection, disconnection, short circuit,
failure)
202
Outdoor
Unit
J6 999Malfunction of thermistor (R4T) for heat exchanger
(loose connection, disconnection, short circuit,
failure)
203
J7 999Malfunction of receiver outlet liquid pipe thermistor (R6T) 204
J9 999Malfunction of subcooling heat exchanger gas pipe
thermistor (R5T)
205
JA 999Malfunction of discharge pipe pressure sensor 206
JC 999Malfunction of suction pipe pressure sensor 207
L0 999Inverter system error
L4 999Malfunction of inverter radiating fin temperature rise 208
L5 999Inverter compressor motor grounding, short circuit 209
L6 999Compressor motor coil grounding on short circuit
L8 999Inverter current abnormal 210
L9 999Inverter start up error 211