Daikin RXYQ14MY1B [118/242] Branch with refnet header

Daikin RXYQ28MY1B [118/242] Branch with refnet header
Appendix Si39-303
112 General Information
7.3.3 Branch with refnet header
(Connection of 8 indoor units Heat pump system)
One outdoor
unit installed
(RXYQ5 ~16)
Branch with refnet header
When multiple
outdoor units
installed
(RXYQ18 ~ )
a
H1
H2
Outdoor unit
Refnet header
Indoor units (1-8)
cde
f
g
h
b
1234567
8
H2
8
H1
H3
a
Outdoor unit
Refnet header
Indoor units (1-8)
cde
f
g
h
b
1234567
Maximum
allowable
length
Between outdoor
and indoor units
Actual pipe length
Pipe length between outdoor and indoor units
150m
Example unit 6: a + i
150m
Equivalent length
Equivalent pipe length between outdoor and indoor units
175m
(assume equivalent pipe length of refnet joint to be 0.5m, that of refnet header to be 1m,
calculation purposes)
Total extension length
Total piping length from outdoor unit* to all indoor units
300m
Between outdoor branch and indoor unit
(Only for RXYQ18 or more)
Actual pipe length
Piping length from outdoor branch to outdoor unit
10m
(Approximately length: max 13m)
Allowable
height
length
Between outdoor and indoor units
Difference in height
Difference in height between outdoor and indoor units (H1)
50m
(Max 40m if the outdoor unit is below)
Between indoor and indoor units
Difference in height
Difference in height between adjacent indoor units (H2)
15m
Between outdoor and outdoor units
Difference in height
Difference in height between outdoor unit (main) and outdoor unit (sub) (H3)
5m
Allowable
length after
the branch
Actual pipe length
Pipe length from first refrigerant branch kit (either refnet joint or refnet header) to indoor unit
40m
Example unit 8: i
40m
*If the system capacity is RXYQ18 or more, re-read to
the first outdoor branch as seen from the indoor unit.
r
t
s
Outdoor unit
r 10m
s 10m
t 10m