Method of Troubleshooting SiE30-408
94 Troubleshooting
3.9.2 Cautions in Transmitting Waveform Measurement
Make sure the probe is securely connected to respective terminals (F1 and F2)
Playing on either of the terminals may deform the waveform, thus resulting in incorrect
diagnosis.
In order to acquire proper diagnosis, be sure to connect a temporary distributing cable to the
probe and fix it to the F1 and F2 with screws.
There are several types of waveforms (for sending and receiving). Therefore, the
acquirement of only one waveform remains many things unknown.
Commit yourself to data reduction. Record waveforms as soon as acquired so as to
recognize at which points the waveforms have been acquired.
It is useful for measurements to provide a temporary distributing cable.
3.9.3 Measurement Range
Basically, time axis (lateral axis): 50 µs to 100 µs
voltage axis (longitudinal axis): 2 V to 5 V
For oscilloscope, acquire waveforms with the "trigger" set to NORMAL mode for easy
reading. (By setting the trigger to AUTO mode, waveforms displayed may immediately
disappear.)
For MEMORY HiCORDER, set all the "filters" to OFF. (Setting the filter to ON may recognize
waveforms as noise, thus resulting in no display.)
In common with the oscilloscope and MEMORY HiCORDER, pay attention to the
"POSITION". (Neglecting the position may conceal waveforms to the point of invisibility in
upper or lower portion of the screen.)
It is useful for measurement to provide AC mode for sampling mode. (Waveforms will be
displayed in the center of the screen.)