Daikin RX48MTL [190/255] Data on occurrence of malfunction while in all unit heating operation

Daikin RX36MYLE [190/255] Data on occurrence of malfunction while in all unit heating operation
Points of Analysis SiE30-408
186 Service Checker Type3 Application Edition
Data on occurrence of malfunction while in all-unit heating operation
Graph of indoor unit (1)
Indoor unit (1)
OUT2 - R2T: Suction pipe temp.
OUT2 - Compressor 2 (STD1)
OUT2 - High pressure gas side (MPa)
OUT2 - R31T: Discharge pipe temp. (INV)
OUT2 - Compressor 3 (STD2)
OUT2 - Low pressure gas side (MPa)
OUT2 - Compressor 2 (STD1)
OUT2 - INV discharge pipe stepping down
control
Suction pipe temperature risesup to approximately 70°C.
Temp. [°C]
Time
Pressure [MPa]
Low pressure reaches
approximately 1.5 MPa.
High pressure does not become stable.
Discharge pipe stepping down control isactivated.
3.5
3
2.5
2
1.5
1
0.5
0
IN1 - Remote controller set temp.
IN1 - Indoor gas pipe temp.
IN1 - Suction temp. IN1 - Indoor liquid pipe temp.
IN1 - Indoor EV opening degree
Even though electronic
expansion valve isset to 0 pls,
the gas pipe temperature rises.
Temp. [°C]
Time
Expansion valve opening degree [pls]