SiE30-408 Field Setting on Outdoor Unit
Field Settings from Remote Controller 59
No.
Used Example
LED Display
Setting condition display
*Factory setting
Page
H1P
Under
prepa-
ration,
Malfun
ction
H2P
Cooling/Heating
selection
Low
noise
H6P
Dema
nd
H7P
Indivi-
dual
H3P
Batch
master
H4P
Batch
slave
H5P
0
For emergency
measures by inverter in
individual installation
machine.
The unit will stop when
this setting made with
multi system unit.
8777777
Normal operation
Emergency operation
(INV compressor is
inhibited to operate.)
8777778*
8777787
1
8777778
Address 0
Binary number 1
(6 digits)
31
8777777*
8777778
~
8788888
2
Setting for mounting of
external control adapter
8777787
Address 0
Binary number 1
(6 digits)
31
8777777*
8777778
~
8788888
5
Used for deciding the
system either indoor or
outdoor.
8777878
Normal operation
Indoor forcedly fan H
8777778*
8777787
6
Forcedly puts the indoor
unit into the test
operation mode.
[UNDER
CENTRALIZED
CONTROL] is displayed
in indoor remote
controller.
8777887
Normal operation
Indoor forcedly operation
8777778*
8777787
8
Correction of the
pressure loss in piping
Select according to the
piping length and scale
of the pressure loss.
8778777
High
Normal
Low
8777877
8777787*
8777778
9
Correction of the
pressure loss in piping
Select according to the
piping length and scale
of the pressure loss.
8778778
High
Normal
Low
8777877
8777787*
8777778
10
Changing of the time for
entering in defrost.
8778787
Quick
Normal
Slow
8777877
8777787*
8777778
11
8778788
Equipped
Not equipped
8777778*
8777787
12
Setting when mounting
of external control
adapter.
Can be used together
with No. 30.
8778877
External low noise ·
Demand: No
External low noise ·
Demand: YES
8777778*
8777787
13
Convenient to check the
checker type 3 system
8778878
Address 0
Binary number 1
(6 digits)
63
8777777*
8777778
~
8788888
18
8787787
High static pressure
setting OFF
High static pressure
setting ON
8777778*
8777787
19
For emergency
measures of individual
installation unit when the
defect of STD.
8787788
OFF
STD 1, 2 operation:
Inhibited
STD 2 operation:
Inhibited
8777777*
8777778
8777787
20
Setting for refrigerant
charging
8787877
Refrigerant charging:
OFF
Refrigerant charging: ON
8777778*
8777787
21
Fully opens motorized
valve forcedly in indoor
or outdoor unit
8787878
Refrigerant recovery:
OFF
Refrigerant recovery: ON
8777778*
8777787