4. Fetch of display signals
Normal operation output terminals (W1 and W2) and malfunction output terminals (W3 and
W4) are used for no-voltage normal contact output.
(Allowable current is 10mA to 3A per contact.)
Caution In order to use power supply of 220 ~ 240 VAC, keep the power supply cable away from input
wirings.
The following table shows the display of output.
Adaptor
KRP4A51 • 52 • 53
Ry1
Operation display
Error display
Power
source
Ry2
Error output (Ry2)
ON when the indoor unit stopsbecause
of malfunction or when a transmission
error occursbetween the adaptor and
the indoor unit.
Normal operation output (Ry1)
ON when the indoor unit is
operating normally.
Output
Both Ry1 & Ry2 are
turned OFF.
RY1 is only
turned ON.
Ry2 is only turned ON.
Display Stop Normal operation
This system stops due to malfunction or
transmission error between the adapter PC
board and indoor unit.