Daikin RXQ34PY1 [105/355] Contents of control modes

Daikin RXQ18PY1 [105/355] Contents of control modes
SiEN34-705 Test Operation
General Information 99
4.4.1.9 Setting of Operation Control Mode from Remote Control (Local Setting)
The operation control mode is compatible with a variety of controls and operations by limiting
the functions of the operation remote control. Furthermore, operations such as remote control
ON/OFF can be limited in accordance with the combination conditions. (Refer to information in
the table below.)
Central remote control is normally available for operations. (Except when centralized monitor is
connected)
4.4.1.10 Contents of Control Modes
Twenty modes consisting of combinations of the following five operation modes with
temperature and operation mode setting by remote control can be set and displayed by
operation modes 0 through 19.
$ ON/OFF control impossible by remote control
Used when you want to turn on/off by central remote control only.
(Cannot be turned on/off by remote control.)
$ OFF control only possible by remote control
Used when you want to turn on by central remote control only, and off by remote control
only.
$ Centralized
Used when you want to turn on by central remote control only, and turn on/off freely by
remote control during set time.
$ Individual
Used when you want to turn on/off by both central remote control and remote control.
$ Timer operation possible by remote control
Used when you want to turn on/off by remote control during set time and you do not want to
start operation by central remote control when time of system start is programmed.