Daikin RXQ34PY1 [199/355] Rx y q20p 22p 24p 26p 28p 30p 32p 34p 36py1 rxyq20p 22p 24p 26p 28p 30p 32p 34p 36pyl

Daikin RXQ18PY1 [199/355] Rx y q20p 22p 24p 26p 28p 30p 32p 34p 36py1 rxyq20p 22p 24p 26p 28p 30p 32p 34p 36pyl
SiEN34-705 Appendix
General Information 193
RX(Y)Q20P, 22P, 24P, 26P, 28P, 30P, 32P, 34P, 36PY1
RXYQ20P, 22P, 24P, 26P, 28P, 30P, 32P, 34P, 36PYL
3D052261B
2 Wires Cable
(Transmisson line)
2 Wires Cable
(Transmisson line)
2 Wires Cable
(Transmisson line)
[UNIT 2][UNIT 1]
2 Wires Cable
(Transmisson line)
2 Wires Cable
(Transmisson line)
2 Wires Cable
(Power line)
2 Wires Cable
(Power line)
2 Wires Cable
(Power line)
2 Wires Cable
(Power line)
2 Wires Cable
(Power line)
Switch
Switch
Switch
Switch
Fuse
Fuse
Switch
Fuse
Fuse
Fuse
Main
Switch
Main
Switch
Power supply
OUTDOOR UNITS
When the source is connected in series
between the units.
INDOOR UNITS
Power supply
Notes
1) All wiring, components and materials to be procured on the site must
comply with the applicable local and national codes.
2) Use copper conductors only
3) As for details, see wiring diagram.
4) Install circuit breaker for safety.
5) All field wiring and components must be provided by licensed
electrician.
6) Unit shall be grounded in compliance with the applicable local and national codes.
7) Wiring shown are general points-of-connection guides only are not intended for or to include all details for or to specific
installation.
8) Be sure to install the switch and the fuse to the power line of each equipment.
9) Install the main switch that can interrupt all the power sources in an integrated manner because this system consists of
the equipment utilizing the multiple power sources.
10) The capacity of UNIT 1 must be larger than UNIT 2 when the power source is connected in series between the units.
11) If there exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off while the
product is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
2 Wires Cable
(Transmisson line)
2 Wires Cable
(Transmisson line)
2 Wires Cable
(Transmisson line)
[UNIT 2]
[UNIT 1]
2 Wires Cable
(Transmisson line)
2 Wires Cable
(Transmisson line)
2 Wires Cable
(Power line)
2 Wires Cable
(Power line)
2 Wires Cable
(Power line)
2 Wires Cable
(Power line)
2 Wires Cable
(Power line)
Switch
Switch
Switch
Switch
Fuse
Switch
Fuse
Fuse
Switch
Fuse
Fuse
Fuse
Main
Switch
Main
Switch
Power supply
OUTDOOR UNITS
When the power source is supplied to each
outdoor unit individually.
INDOOR UNITS
Power supply

Содержание

Скачать