202 General Information
7.14.9 Example 9: “88” cannot be Cleared from the Central Remote Control.
Situation The display on the central remote control does not change from its initial state after turning
power ON.
Initial display of the central remote control
Cause 1. None of the indoor units connected to the central remote control have been given a group
No.
2. The connector for setting the master controller inside the central remote control is
disconnected.
Remedial Action ! Set a centralized control group No. for each indoor unit with the respective remote controls.
! Connect the connector for setting the master controller in one of the central remote control.
Main Points ! If the setting for master controller has been changed, reset the power to the unit at the ON/
OFF switch or the forced reset switch of the controller.
! Activate power to the central remote control, unified ON/OFF controller and indoor unit
before setting the centralized control group No.
! For details on how to set the centralized control group number, refer to the installation
manual.