Daikin RXYQ48PAYL [30/36] Refers to bringing outdoor air to near indoor temperature and delivering to a room

Daikin RXYQ48PAYL [30/36] Refers to bringing outdoor air to near indoor temperature and delivering to a room
5857
System Configuration
Building Management System
•Up to 64 groups of indoor units(128 units) can be connected, and ON/OFF, temperature setting and
monitoring can be accomplished individually or simultaneously. Connectable up to 2 controllers in one
system.
Note 2
DCS302CA61
Central remote controller2
•Up to 16 groups of indoor units (128 units) can be easily controlled using the large LCD panel. ON/OFF,
temperature settings and scheduling can be controlled individually for indoor units.
Note 3
DCS303A51
Residential central remote controller1
•Up to 16 groups of indoor units(128 units) can be turned, ON/OFF individually or simultaneously, and
operation and malfunction can be displayed. Can be used in combination with up to 8 controllers.
Note 2
DCS301BA61
Unified ON/OFF controller3
KJB212AAElectrical box with earth terminal (2 blocks)3-1
KEK26-1ANoise filter (for electromagnetic interface use only)3-2
KJB311AAElectrical box with earth terminal (3 blocks)2-1
DTA102A52
Interface adaptor for SkyAir-series5
DTA107A55
6
DTA103A51
Wiring adaptor for other air-conditioner7
No. Item Model No. Function
•Up to 1024 units can be centrally controlled in 64 different groups.
•Wiring restrictions (max. length: 1,000 m, total wiring length: 2,000 m, max. number of branches: 16)
apply to each adaptor.
DTA109A51
D -NET
Expander Adaptor
8
•Fixing plate for DTA109A51KRP4A92
Mounting plate8-1
•Adaptors required to connect products other than those of the VRV System to the high-speed DIII-NET
communication system adopted for the VRV System.
* To use any of the above optional controllers, an appropriate adaptor must be installed on the product unit to be
controlled.
For UAT
(
Y
)
-K
(
A
)
,FD-K
For SkyAir, FD
(
Y
)
M-FA, FDY-KA
FDYB-KA, FVY(P)J-A, FXUQ-MA
Central control adaptor kit
Notes: 1. Installation box for adaptor must be obtained locally.
2. For FXUQ-MAV1, an interface adaptor (DTA102A52) for the SkyAir series is necessary.
3. For residential use only. Cannot be used with other centralised control equipment.
Notes: *1.
BACnet
®
is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).
*2. LonWorks
®
is a trademark of Echelon Corporation registered in the United States and other countries.
*3. Installation box for adaptor must be obtained locally.
ComponentsComponents
of Indoor Air Qualityof Indoor Air Quality
Components
of Indoor Air Quality
A recent trend rapidly gaining popularity is for air treatment to be required as well as air conditioning. Daikin’s
Outdoor-Air Processing Unit can combine fresh air treatment and air conditioning, supplied from a single system.
It adjusts the temperature of air from outdoors using a fixed discharge temperature control. Along with Outdoor-Air
Processing Units, we also offer Heat Reclaim Ventilator systems. The Heat Reclaim Ventilator VAM-GJ series units
in particular have been praised for their compactness, energy conservation and extensive operation range of
outdoor temperatures. This series provides higher enthalpy efficiency , due to the greatly enhanced performance
of the thin film element. Furthermore, improved external static pressure offers more flexibility for installation. The
Heat Reclaim Ventilator VKM-GAM series units, equipped with a DX-coil and a humidifier, provide further
advanced features, such as temperature adjustment to suit conditions indoors and to prevent cold air from blowing
on people directly during heating operation. The series also realises significant energy savings by exercising heat
recovery.
DaikinDaikins air treatment systemss air treatment systems
creating a highercreating a higher
air quality enair quality environmentvironment
Daikin’s air treatment systems
creating a higher
air quality environment
Ventilation
Humidification
Air Processing*
Ventilation
Ventilation
Humidification
Air Processing*
Humidification
Ventilation
Humidification
Air Processing*
Air Processing*
Outdoor-Air
Processing Unit
VKM-GAM Type VKM-GA Type VAM-GJ Type
Refrigerant Piping
Connectable Not connectable
Wiring
Connectable Connectable
After-cool &
After-heat Control
Available Not available
——
Energy savings obtained
Fitted
Option Option
Air supply only Air supply & air exhaust
220-240 V, 50 Hz 220-240 V/220 V, 50 Hz/60 Hz
Heat Reclaim Ventilator
Connections
with VRVIII
Connectable
Connectable
Available
Heat Exchange Element
Energy savings obtained
Humidifier
High Efficiency Filter
Option
Ventilation System
Air supply & air exhaust
Power Supply
220-240 V, 50 Hz
Airflow Rate
150 m
3
/h
250 m
3
/h
350 m
3
/h
500 m
3
/h
650 m
3
/h
800 m
3
/h
1080 m
3
/h
1000 m
3
/h
500 m
3
/h
800 m
3
/h
1000 m
3
/h
1680 m
3
/h
1500 m
3
/h
2100 m
3
/h
2000 m
3
/h
*Refers to bringing outdoor air to near indoor
temperature and delivering to a room.
1
2
For models: VAM150/250/350/650/800/1000/2000GJVE
For models: VAM150/350/500GJVE
2
1
*Refers to bringing outdoor air to near indoor temperature and delivering to a room.
Control Systems—Option List
Air Treatment Equipment Lineup
Operation Control System Optional Accessories
No.
FXFQ-P FXCQ-M FXKQ-MA
FXDQ-PB
FXDQ-NB
FXAQ-P
FXLQ-MA
FXNQ-MA
Remote controller
Type
Item
BRC7F635F
BRC7C67 BRC4C63
BRC7EA619
BRC4C64BRC4C66
FXMQ-P
BRC4C66
FXUQ-MA
BRC7CA529W
FXHQ-MA
BRC7EA66
FXMQ-MA
BRC4C64
BRC7F634F
BRC7C62
FXZQ-M
BRC7E531W
BRC7E530W
BRC4C61
BRC7EA618
BRC4C62BRC4C65 BRC4C65
BRC7CA528W
BRC7EA63W
BRC4C62
1
BRC1C62
•Programmed time weekly schedule can be controlled by unified control for up to 64 groups of indoor units
(128 units). Can turn units ON/OFF twice per day.
Note 2
DST301BA61
Schedule timer
4
Wired remote controller with weekly schedule timer BRC1D61
3
Navigation remote controller (Wired remote controller) BRC1E61
2
Notes: 1. Installation box is necessary for each adaptor marked .
2. Up to 2 adaptors can be fixed for each installation box.
4
5
Simplified remote controller (Exposed type)
6 Adaptor for wiring
7-1 Wiring adaptor for electrical appendices (1)
7-2 Wiring adaptor for electrical appendices (2)
Remote controller for hotel use (Concealed type)
10 External control adaptor for outdoor unit
BRC3A61
BRC2C51
9 Installation box for adaptor PCB
BRC2C51
BRC3A61
5. Installation box is necessary for second adaptor.
6. Installation box is necessary for each adaptor.
3. Only one installation box can be installed for each indoor unit.
4. Up to 2 installation boxes can be installed for each indoor unit.
KRP1B61
DTA104A61
KRP1C63
KRP2A61 KRP2A62
KRP4AA51 KRP4AA53
KRP2A61
KRP1B61
DTA104A62
Notes 2, 3
KRP1B96
DTA104A62
Notes 4, 6
KRP1BA101
Note 3
KRP1CA93
Notes 2, 3
KRP4AA93
Notes 2, 3
KRP1H98
KRP1C64
KRP2A61
KRP2A61
KRP4AA51
KRP4AA51
KRP2A62
KRP2A61
KRP4AA52 KRP4AA51
KRP4AA51
Notes 2, 3
KRP4A96
Notes 4, 6
KRP1BA101
DTA104A61
KRP1BA97
KRP4AA53
DTA104A53
DTA104A61
DTA104A61 DTA104A62 DTA104A61
DTA104A61
KRP1BA57
KRP2A62
KRP4AA53
KRP1BA54
KRP1B61
KRP1B56
KRP2A53
KRP4A54
KRP1B61
KRP2A61
KRP4AA51
11 Adaptor for multi tenant
DTA114A61
DTA114A61
DTA114A61
C/O
Wireless
Wired
H/P
8 Remote sensor (for indoor temperature)
KRCS01-1B KRCS01-1B
KRCS01-4B
KRCS01-4B
•Interface unit to allow communications between VRV and BMS. Operation and monitoring of air-
conditioning systems through
LONWORKS
®
communication.
DMS504B51
4
3
•Expansion kit, installed on DMS502B51, to provide 2 more DIII-NET communication ports. Not usable
independently.
DAM411B513-1
No. Item Model No. Function
*2 Interface for use in LONWORKS
®
•Interface unit to allow communications between VRV and BMS. Operation and monitoring of air-
conditioning systems through BACnet
®
communication.
DMS502B51
•Additional 64 groups (10 outdoor units) is possible.
Max. 7 iTM plus adaptors can be connected to intelligent Touch Manager.
DCM601A52
*1 Interface for use in BACnet
®
Optional DIII board
KJB411A
•Expansion kit, installed on DMS502B51, to provide 16 more wattmeter pulse input points. Not usable
independently.
DAM412B51Optional Di board
•8 pairs based on a pair of On/Off input and abnormality input.DEC101A51Di unit2-5
3-2
1-2
1
Electrical box with earth terminal (4 blocks)
DCS601A52
1-1
•Additional 64 groups (10 outdoor units) is possible.
•Wall embedded switch box.
DCS601C51 •Air-Conditioning management system that can be controlled by a compact all-in-one unit.
intelligent Touch
Controller
DIII-NET plus adaptor
intelligent Touch Controller
Hardware
Hardware
Basic
DCM601A51 •Air-conditioning management system that can be controlled by touch screen.
intelligent Touch Manager
DCM601A53 •Max. 5 intelligent Touch Managers can be integrated.
iTM integrator
Hardware
Basic
Option
iTM plus adaptor
•Building energy consumption is visualised.
Wasted air-conditioning energy can be found out.
DCM008A51iTM energy navigator
•Power consumption of indoor units are calculated based on operation status of the indoor unit and
outdoor unit power consumption measured by kWh metre.
DCM002A51
iTM power proportional
distribution
2
2-2
2-1
2-4
2-3
Hardware
Software
Option
•4 pairs based on a pair of On/Off input and abnormality input.DEC102A51Dio unit2-6
•Interface between the central monitoring board and central control units.
DCS302A525
Unification adaptor for
computerised control
Communication
line
Contact/analogue
signal
intelligent Touch
Manager
 