Daikin REYQ240PYDN [8/20] Remote controller and cool heat selector name and function of each switch and display refer to figure 2 and 3
![Daikin REYQ240PYDN [8/20] Remote controller and cool heat selector name and function of each switch and display refer to figure 2 and 3](/views2/1717999/page8/bg8.png)
5 English
*1: Refrigerant charge at factory shipment
3. WHAT TO DO BEFORE OPERATION
This operation manual is for the following system
with standard control. Before initiating operation,
contact your Daikin dealer for the operation that cor-
responds to your system type and mark.
If your installation has a customized control system,
ask your Daikin dealer for the operation that corre-
sponds to your system.
Outside units (Refer to figure 1)
• Names and functions of parts (Refer to figure 1)
1. Outside unit
2. Indoor unit
3. Remote controller
4. Inlet air
5. Outlet air
6. BS unit
7. Cool/Heat selector
8. Refrigerant piping
(figure 1 shows system with Cool/Heat selector)
4. REMOTE CONTROLLER AND
COOL/HEAT SELECTOR : NAME
AND FUNCTION OF EACH
SWITCH AND DISPLAY
(Refer to figure 2 and 3)
1.
On/off button
Press the button and the system will start. Press
the button again and the system will stop.
2.
Operation lamp (red)
The lamp lights up during operation.
Model name
REYQ144PYDN REYQ168PYDN REYQ192PYDN
Power supply
Phase
—3~ 3~ 3~
Frequency
(Hz) 60 60 60
Voltage
(V) 460 460 460
Nominal cooling capacity
(MBh) 144 168 192
Nominal heating capacity
(MBh) 162 189 216
(66-1/8×36-5/
8×30-1/8)+
(66-1/8×36-5/
8×30-1/8)+
(66-1/8×36-5/
8×30-1/8)+
Dimensions H×W×D
(inch)
(66-1/8×36-5/
8×30-1/8)
(66-1/8×36-5/
8×30-1/8)
(66-1/8×36-5/
8×30-1/8)
Mass
(Ib) 463+463 463+573 463+573
Refrigerant
type
— R410A R410A R410A
charge (*1)
(Ib) 18.1+18.1 18.1+19.8 19.8+19.8
Design pressure
High side
(psig) 478 478 478
Low side
(psig) 320 320 320
Model name
REYQ216PYDN REYQ240PYDN
Power supply
Phase
—3~ 3~
Frequency
(Hz) 60 60
Voltage
(V) 460 460
Nominal cooling capacity
(MBh) 216 240
Nominal heating capacity
(MBh) 243 270
(66-1/8×36-5/
8×30-1/8)+
(66-1/8×36-5/
8×30-1/8)+
Dimensions H×W×D
(inch)
(66-1/8×36-5/
8×30-1/8)
(66-1/8×36-5/
8×30-1/8)
Mass
(Ib) 573+573 573+573
Refrigerant
type
— R410A R410A
charge (*1)
(Ib) 18.1+20.1 20.1+20.1
Design pressure
High side
(psig) 478 478
Low side
(psig) 320 320
Model name
REYQ72PTJU REYQ96PTJU REYQ120PTJU
Power supply
Phase
—3~ 3~ 3~
Frequency
(Hz) 60 60 60
Voltage
(V) 208-230 208-230 208-230
Nominal cooling capacity
(MBh) 72 96 120
Nominal heating capacity
(MBh) 81 108 135
Dimensions H×W×D
(inch)
66-1/8×
51-3/16×
30-1/8
66-1/8×
51-3/16×
30-1/8
66-1/8×
51-3/16×
30-1/8
Mass
(Ib) 730 730 730
Refrigerant
type
— R410A R410A R410A
charge (*1)
(Ib) 22.7 23.4 23.8
Design pressure
High side
(psig) 478 478 478
Low side
(psig) 320 320 320
Model name
REYQ144PTJU REYQ168PTJU REYQ192PTJU
Power supply
Phase
—3~ 3~ 3~
Frequency
(Hz) 60 60 60
Voltage
(V) 208-230 208-230 208-230
Nominal cooling capacity
(MBh) 144 168 192
Nominal heating capacity
(MBh) 162 189 216
Dimensions H×W×D
(inch)
66-1/8×
51-3/16×
30-1/8
(66-1/8×36-5/8×
30-1/8)+
(66-1/8×36-5/8×
30-1/8)
(66-1/8×36-5/8×
30-1/8)+
(66-1/8×36-5/8×
30-1/8)
Mass
(Ib) 747 450+560 450+560
Refrigerant
type
— R410A R410A R410A
charge (*1)
(Ib) 24.5 18.1+19.8 18.1+20.1
Design pressure
High side
(psig) 478 478 478
Low side
(psig) 320 320 320
Model name
REYQ216PTJU REYQ240PTJU
Power supply
Phase
—3~ 3~
Frequency
(Hz) 60 60
Voltage
(V) 208-230 208-230
Nominal cooling capacity
(MBh) 216 240
Nominal heating capacity
(MBh) 243 270
Dimensions H×W×D
(inch)
(66-1/8×36-5/8×
30-1/8)+
(66-1/8×36-5/8×
30-1/8)
(66-1/8×36-5/8×
30-1/8)+
(66-1/8×36-5/8×
30-1/8)
Mass
(Ib) 560+560 560+560
Refrigerant
type
— R410A R410A
charge (*1)
(Ib) 19.8+20.1 20.1+20.1
Design pressure
High side
(psig) 478 478
Low side
(psig) 320 320
COOL/HEAT selector Operation modes
Inverter series
heat pumps
RXYQ
series ❏ yes ❏ no
Heat recovery series
heat pumps
REYQ
series ❏ yes ❏ no
01_EN_3P215731-1D.fm Page 5 Tuesday, February 5, 2008 6:35 PM
Содержание
- Operation manual 1
- System air conditioner 1
- 1 13 2 3
- _cv_3p215731 1d fm page 3 wednesday february 6 2008 11 34 am 3
- Contents 4
- Safety considerations 4
- Electrical work 6
- Pay attention to operating sound 6
- Place of installation 6
- Design pressure 7
- Dimensions h w d 7
- Drainage through drainpipe 7
- English 4 7
- Make sure that the drainpipe is installed prop erly to drain water if no water is discharged from the drainpipe while the air conditioner is cooling operation the drain pipe may be clogged with dust or dirt and water leakage from the indoor units may result stop operating the air conditioner and consult your dealer 7
- Model name 7
- Nominal cooling capacit 7
- Nominal heating capacit 7
- Power supply 7
- Refrigerant 7
- Specifications 7
- English 8
- If your installation has a customized control system ask your daikin dealer for the operation that corre sponds to your system outside units refer to figure 1 8
- Names and functions of parts refer to figure 1 1 outside unit 2 indoor unit 3 remote controller 4 inlet air 5 outlet air 6 bs unit 7 cool heat selector 8 refrigerant piping figure 1 shows system with cool heat selector 8
- On off button press the button and the system will start press the button again and the system will stop 8
- Operation lamp red the lamp lights up during operation 8
- Remote controller and cool heat selector name and function of each switch and display 8
- Remote controller and cool heat selector name and function of each switch and display refer to figure 2 and 3 8
- This operation manual is for the following system with standard control before initiating operation contact your daikin dealer for the operation that cor responds to your system type and mark 8
- What to do before operation 8
- 1 cooling heating automatic and fan only operation 10
- Operation procedure 10
- Operation range 10
- 2 program dry operation 11
- 3 adjusting the air flow direc tion refer to figure 6 only for dou ble flow multi flow corner ceiling suspended and wall mounted 12
- 4 programming start and stop of the system with timer refer to figure 9 13
- 5 setting the master remote con troller 13
- 6 precautions for group con trol system or two remote controller control system 14
- Optimum operation 14
- 1 at the beginning of the season 15
- 1 the system does not operate 15
- 2 at the end of the season 15
- 2 it stops sometimes 15
- 3 cool heat cannot be changed over 15
- Following symptoms are not air conditioner troubles 15
- Seasonal maintenance 15
- 10 the units can give off odours 16
- 11 the outside unit fan does not rotate 16
- 5 the fan strength does not cor respond to the setting 16
- 6 the fan direction does not cor respond to the setting 16
- 7 white mist comes out of the unit 16
- 8 noise of air conditioners 16
- 9 dust comes out of the unit 16
- Cooling and heating do not work 16
- Fan operation is possible but 16
- 12 the display shows 17
- 13 the compressor or fan in the outside unit does not stop 17
- 14 the inside of outside unit is warm even when the unit has stopped 17
- 15 hot air is emitted even though the unit is stopped 17
- 16 does not cool very well 17
- Trouble shooting 17
- After sales service and warranty 18
- P215731 1d em07a037a 20
Похожие устройства
- Daikin REYQ240PYDN Сервис мануал
- Daikin REYQ72PATJ Спецификация
- Daikin REYQ72PATJ Руководство по вводу в эксплуатацию
- Daikin REYQ96PATJ Спецификация
- Daikin REYQ96PATJ Руководство по вводу в эксплуатацию
- Daikin REYQ96PATJ Инструкция по монтажу
- Daikin REYQ72PATJ Инструкция по монтажу
- Daikin REYQ120PATJ Спецификация
- Daikin REYQ120PATJ Руководство по вводу в эксплуатацию
- Daikin REYQ120PATJ Инструкция по монтажу
- Daikin REYQ120PATJ Инструкция по монтажу
- Daikin REYQ192PATJ Спецификация
- Daikin REYQ168PATJ Спецификация
- Daikin REYQ168PATJ Руководство по вводу в эксплуатацию
- Daikin REYQ192PATJ Руководство по вводу в эксплуатацию
- Daikin REYQ192PATJ Инструкция по монтажу
- Daikin REYQ168PATJ Инструкция по монтажу
- Daikin REYQ144PATJ Спецификация
- Daikin REYQ144PATJ Руководство по вводу в эксплуатацию
- Daikin REYQ144PATJ Инструкция по монтажу