APC Back-UPS BE700G-FR AR Инструкция по эксплуатации онлайн

APC Back-UPS BE700G-FR AR Инструкция по эксплуатации онлайн
Operation Manual
Back-UPS
ES 550/700
Connect the Battery
The Back-UPS is shipped with one battery cable disconnected. Remove the “Stop! Connect the Battery” label that covers the
outlets. Prior to connecting any equipment to the unit, connect the battery cable to the unused battery terminal. It is normal for
small sparks to be seen when the battery cable is connected to the battery terminal.
Wall Mount Installation
The UPS can be installed vertically or horizontally to a wall. Use the template to assist with installation and a fastener (not
included) that can support at least 6.8 kg.
1. Hold the template against the wall surface and use a nail or pin to mark the center of each hole.
2. Install a fastener into the wall at the marked locations. Allow 8 mm of the fastener to protrude from the wall.
3. Install the unit on the wall, using the fasteners.
Inventory Safety and General Information
Inspect the package contents upon receipt. Notify
the carrier and dealer if there is any damage.
Read the Safety Guide supplied with this unit before
installing the UPS.
This UPS is intended for indoor use only.
Do not operate this UPS in direct sunlight, in contact with fluids, or where there is
excessive dust or humidity.
Be sure the air vents on the UPS are not blocked. Allow adequate space for proper
ventilation.
The battery typically lasts for two to three years. Environmental factors impact battery life.
Elevated ambient temperatures, poor quality AC power, and frequent short duration
discharges will shorten battery life.
Connect the UPS power cable directly to a wall outlet. Do not use surge protectors or
extension cords.
Charge the battery for at
least 16 hours before
use.
bu075c
B
a
c
k
-
U
P
S
Us er D oc ume nta tion
bu034a
bu0 35 a
b
u036a
165 mm
(6.50 in.)
Wall-mounting Template
Скачать