APC Back-UPS BE700G-FR AR [5/6] Specifications

APC Back-UPS BE700G-FR AR [5/6] Specifications
Back-UPS ES 550 & 700 5
Specifications
Replace Battery
Deliver the used battery to a recycling facility.
Replace the used battery with an APC by Schneider Electric approved battery. Replacement batteries can be
ordered through the APC by Schneider Electric Web site, www.apc.com. Battery replacement parts are RBC110
for Back-UPS BE550, and RBC17 for Back-UPS BE700.
The Power On indicator flashes once
per second and the Back-UPS beeps
once per second at the same time.
Battery capacity is low (about 2
minutes of use remaining).
The Back-UPS is about to shut off due to a low battery charge
condition! When the unit beeps once every second, the battery has
about 2 minutes of power remaining. Immediately power down your
computer and turn the unit OFF. When normal power returns, the
unit will recharge the battery.
Inadequate runtime. The battery is not fully charged. Allow the unit to charge by leaving it plugged into the wall for at
least 16 hours.
Battery is near the end of useful life. As a battery ages, the amount of runtime available will decrease.
You can replace the battery by ordering one at www.apc.com.
Batteries also age prematurely if the Back-UPS is placed near
excessive heat.
The device connected to the Master
outlet goes into Sleep or Standby mode,
but the equipment connected to the
Controlled outlets do not turn off.
The “green” function is turned off or
the threshold setting is incorrect.
Re-configure the Master and Controlled outlets. See Connect the
Equipment on page 2.
The threshold setting of the device
connected to the Master outlet is not
configured properly.
Re-configure the threshold settings of the device connected to the
Master outlet.
Power is not supplied to some outlets. The Controlled Outlets may be turned
OFF.
Disable the Master/Controlled outlets.
The Controlled Outlets are not
supplying power, even though the
Master device is not in sleep mode.
The Master Outlet threshold may be
incorrectly set.
Re-configure the Master Outlet, ensure the device connected to the
Master Outlet is in sleep or standby mode, or is OFF, when the
threshold is set.
Input
Voltage 230 Vrms Nominal
Frequency 50/60 Hz (auto sensing)
Brownout Transfer 180 Vrms, typical
Over-voltage Transfer 266 Vrms, typical
Output
Voltage On Battery 230 Vac rms +/- 8%
Total Amperage (8 outlets) 10 Amps (including UPS output)
UPS Capacity (4 outlets) 550VA/330W 700VA/405W
Frequency - On Battery 50/60 Hz +/-1 Hz
Transfer Time 6 ms typical, 10 ms maximum
Protection
and Filter
AC Surge Protection Full time, 451 joules
Phone/fax/DSL Surge Protection Single line (2-wire)
Network Surge Protection 10/100Base-T Ethernet
EMI/RFI Filter Full time
AC Input Resettable circuit breaker
Battery
Type Sealed, maintenance-free lead acid
Average Life 3 - 5 years depending on the number of discharge cycles and environmental temperature
Physical
Net Weight 6.4kg 6.8kg
Dimensions (H x W x D) 285 x 230 x 86 mm (11.2 x 9.1 x 3.4 in)
Operating Temperature
0
o
C to 40
o
C (32
o
F to 104
o
F)
Storage Temperature
-15
o
C to 45
o
C (5
o
F to 113
o
F)
Operating Relative Humidity 0 to 95% non-condensing
Operating Elevation 0 to 3000 m (0 to 10,000 ft)
Problem Probable Cause Solution