Daikin FTKE35BVMT [83/169] Check no 3 refer to p 63

Daikin FTKE25BVM [83/169] Check no 3 refer to p 63
Troubleshooting Si10-417
82 Service Diagnosis
Trouble
shooting
Check No.13
Refer to
P.163
Replace the outdoor
unit PCB, outdoor unit
fan.
Replace the outdoor
unit PCB.
Reconnect as
specified.
Inverter checker
Part No.: 1225477
Correct the power
supply or replace the
outdoor unit PCB.
Replace the
compressor.
(R2847)
Normal
NO
NO
YES
YES
NO
YES
YES
Any LED off?
NO
DC380±30V?
Electricals
or compressor harnesses
connected as
specified?
Check the electrolytic
capacitor voltage.
Check with the inverter
checker ().
Turn off the power. Disconnect
the harnesses U, V and W.
Check No. 13
Check for short-circuit.
Caution
Be sure to turn off power switch before connect or
disconnect connector, or parts damage may be occurred.