11 English
Test Run and Final Check
1.
Trial operation and testing.
1-1Measurethe supply voltage andmakesurethat it falls in the specified range.
1-2Trialoperationshould be carried out in eithercoolingorheating mode.
For heat pump
In cooling mode, select the lowest programmabletemperature; in heatingmode, select the highest programmable temper-
ature.
1) Trial operation may be disabled in either mode depending on the room temperature.
2) After trialoperation is complete, setthe temperature to anormal level(26°Cto28°Cincooling mode,20°Cto24°Cin
heatingmode).
3) For protection, the system disables restart operationfor 3minutes afteritisturnedoff.
Forcooling only
Select thelowest programmable temperature.
1) Trial operation in coolingmodemay be disabled depending on the room temperature.
2) After trialoperation is complete, setthe temperature to anormal level(26°Cto28°C).
3) Forprotection, theunitdisablesrestart operation for 3minutes afteritisturnedoff.
1-3Carry outthe test operationinaccordance with theoperation manual to ensurethat all functions andparts,
such as louvermovement, areworkingproperly.
Theair conditioner requiresasmall amount of power in its standby mode. If the system is not to be used forsome
time after installation, shutoff thecircuit breaker to eliminate unnecessarypower consumption.
If the circuitbreaker trips to shut offthe powertothe air conditioner,the system will restore the original operation
mode when the circuitbreaker is openedagain.
2.
Test items.
Test items
Symptom
(diagnosticdisplay on RC)
Check
Indoor and outdoor units are installed properlyonsolid bases. Fall, vibration,noise
No refrigeran tgas leaks.Incomplete cooling/heating function
Refrigerant gasand liquid pipesand indoo rdrain hose extension arethermally insulated. Waterleakage
Draining line is properly installed. Waterleakage
Systemisproperlyearthed. Electrical leakage
The specified wires are used forinterconnecting wire connections. Inoperativeorburndamage
Indoor or outdoor unitsair intakeorexhaust has clearpath of air.
Stop valves are opened.
Incomplete cooling/heating function
Indoor unit properly receives remote controller commands.Inoperative