Daikin RXLG50K3V1B [4/16] Accessories
![Daikin RXLG50K3V1B [4/16] Accessories](/views2/1772599/page4/bg4.png)
2 nEnglish
Accessories
Accessories supplied with the outdoor unit:
Precautions for Selecting the Location
1) Choose a place solid enough to bear the weight and vibration of the unit, where the operation noise will not be amplified.
2) Choose a location where the hot air discharged from the unit or the operation noise will not cause a nuisance to the neighbors of
the user.
3) Avoid places near a bedroom and the like, so that the operation noise will cause no trouble.
4) There must be sufficient spaces for carrying the unit into and out of the site.
5) There must be sufficient space for air passage and no obstructions around the air inlet and the air outlet.
6) The site must be free from the possibility of flammable gas leakage in a nearby place.
7) Install units, power cords and inter-unit cables at least 3 meter away from television and radio sets. This is to prevent interference
to images and sounds. (Noises may be heard even if they are more than 3 meter away depending on radio wave conditions.)
8) In coastal areas or other places with salty atmosphere of sulfate gas, corrosion may shorten the life of the air conditioner.
9) Since drain flows out of the outdoor unit, do not place under the unit anything which must be kept away from moisture.
NOTE
Cannot be installed hanging from ceiling or stacked.
CAUTION
When operating the air conditioner in a low outdoor ambient tempera-
ture, be sure to follow the instructions described below.
1) To prevent exposure to wind, install the outdoor unit with its suction
side facing the wall.
2) Never install the outdoor unit at a site where the suction side may
be exposed directly to wind.
3) To prevent exposure to wind, it is recommended to install a baffle
plate on the air discharge side of the outdoor unit.
4) In heavy snowfall areas, select an installation site where the snow will not affect the unit.
• Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small
animals.
Small animals making contact with electrical parts can cause malfunctions, smoke or fire. Please instruct the customer to keep the area around the unit clean.
• This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial
and household use by lay persons.
• Sound pressure level is less than 70 dB(A).
(A) Installation Manual
1
(B) Refrigerant charge label
1
(C)
Multilingual fluorinated greenhouse gases label
1
Construct a large canopy.
Construct a pedestal.
Install the unit high enough off the
ground to prevent burying in snow.
Содержание
- Installation manual 1
- Daikin industries czech republic s r o 2
- En60335 2 4 2
- Low voltage 2006 95 ec machinery 2006 42 ec electromagnetic compatibility 2004 108 ec 2
- P291651 7d_offset book page 1 sunday july 8 2012 3 14 pm 2
- P327445 6a 2
- Rxl50j3v1b rxlg50k3v1b 2
- Takayuki fujii managing director 1st of 012 2
- Caution 3
- N english 1 3
- Safety precautions 3
- Warning 3
- Accessories 4
- Accessories supplied with the outdoor unit 4
- Caution 4
- N english 4
- Precautions for selecting the location 4
- Caution 5
- English 5
- N english 3 5
- Outdoor unit installation drawings 5
- Installation guidelines 6
- Installing outdoor unit 6
- N english 6
- Outdoor unit installation 6
- Precautions on installation 6
- Caution 7
- Flaring the pipe end 7
- Outdoor unit installation 7
- Refrigerant piping 7
- Warning 7
- N english 8
- Purging air and checking gas leakage 8
- Warning 8
- Important information regarding the refrigerant used 9
- Outdoor unit installation 9
- Refilling the refrigerant 9
- Refrigerant piping work 9
- Forced cooling operation 10
- In order to protect the environment be sure to pump down when relocating or disposing of the unit 10
- N english 10
- Pump down operation 10
- Warning 10
- Wiring 10
- Caution 11
- English 11
- N english 9 11
- C7 c8 capacitor 12
- Db1 db3 diode bridge 12
- E1h heater 12
- Fu1 fu2 fu3 12
- Fu4 fu5 fuse 12
- Fu6 field fuse 12
- Ipm intelligent power module 12
- L live 12
- L803 l804 reactor 12
- M1c compressor motor 12
- M1f fan motor 12
- Mrcw mrm10 mrm20 mr30 mr30_a mr30_b magnetic relay 12
- N english 12
- N neutral 12
- Pcb1 pcb2 printed circuit board 12
- Protective earth 12
- Q1di earth leak detector 12
- Q1l overload protector 12
- R1t r2t r3t thermistor 12
- S10 s11 s12 s20 s40 s50 s70 s80 s90 hl3 hn3 x11a x12a connector 12
- S1t thermostat 12
- Sa1 surge absorber 12
- V1 v2 v3 varistor 12
- Wiring diagram 12
- Wiring diagram parts table 12
- X1m terminal strip 12
- Y1e electronic expansion valve coil 12
- Y1s reversing solenoid valve coil 12
- Z1c z2c z3c 12
- Z4c noise filter ferrite core 12
- N english 11 13
- Test items 13
- Trial operation and testing 13
Похожие устройства
- Daikin RXL42J3V1B Руководство по монтажу
- Daikin RXS60F2V1B Руководство по монтажу
- Daikin RXS60F3V1B Руководство по монтажу
- Daikin RXS60F4V1B Руководство по монтажу
- Daikin RXS71FAV1B Руководство по монтажу
- Daikin RXS71FV1B Руководство по монтажу
- Daikin RXS71FAV1B9 Руководство по монтажу
- Daikin RXS71FAV1B8 Руководство по монтажу
- Daikin RKS71FAV1B Руководство по монтажу
- Daikin RKS71FV1B Руководство по монтажу
- Daikin RXM42R2V1B Руководство по монтажу
- Daikin RXM50R2V1B Руководство по монтажу
- Daikin RXM60R2V1B Руководство по монтажу
- Daikin RXM71R2V1B Руководство по монтажу
- Daikin RXS50J2V1B Руководство по монтажу
- Daikin RKS50J2V1B Руководство по монтажу
- Daikin RKS60F3V1B Руководство по монтажу
- Daikin RXS50G2V1B Руководство по монтажу
- Daikin RKS50G2V1B Руководство по монтажу
- Daikin RKS60F2V1B Руководство по монтажу