Outdoor Units • R-410A • RKH-CAVMB
1
3
Split Sky Air • Outdoor Units5
3 Electrical data
RKH35CVMB
Indoor unit Outdoor unit
Power supply Compressor OFM IFM
Hz-Volts
Voltage range
MCA MFA RHz RLA W FLA W FLA
FTKS35CVMB RKH35CVMB 50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
13.015 704.41250.35180.20
3D044325
SYMBOLS
MCA : Min. Circuit Amps (A)
MFA : Max. Fuse Amps (A)
RHz : Rated operating frequency(Hz)
RLA : Rated Load Amps (A)
OFM : Outdoor Fan Motor
IFM : Indoor Fan Motor
FLA : Full Load Amps
W : Rated motor output (W)
NOTES
1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWB
Outdoor temp. : 35°CDB
2. Maximum allowable voltage unbalance between phases is 2%
3. Select wire size based on the larger value of MCA.
4. Instead of fuse, use circuit breaker.
5. For more details concerning conditional connections, see
http://eu.extranet.daikineurope.com, select ’’E-Data Books’’.
Finally, click on the document title of your choice.