Daikin FTXS25EVMA [12/79] Holding functions no functions
![Daikin RKS25EBVMA [12/79] Holding functions no functions](/views2/1776932/page12/bgc.png)
ED04-805 Functions
Room Air Conditioners E-Series 11
3. Functions
Category Functions
FTKS25/35EVMA
RKS25/35EBVMA
FTXS25/35EVMA
RXS25/35EBVMA
Category Functions
FTKS25/35EVMA
RKS25/35EBVMA
FTXS25/35EVMA
RXS25/35EBVMA
Basic
Function
Inverter (with Inverter Power Control)
{{
Health &
Clean
Air Purifying Filter — —
Operation Limit for Cooling (°CDB)
10
~46
10
~46
Photocatalytic Deodorizing Filter — —
Operation Limit for Heating (°CWB) —
–10
~20
Air Purifying Filter with Photocatalytic
Deodorizing Function
——
PAM Control
{{
Titanium Apatite Photocatalytic
Air-Purifying Filter
{{
Compressor Oval Scroll Compressor — —
Swing Compressor
{{
Mold Proof Air Filter
{{
Rotary Compressor — — Wipe-clean Flat Panel
{{
Reluctance DC Motor
{{
Washable Grille — —
Comfortable
Airflow
Power-Airflow Flap — — Mold Proof Operation
{{
Power-Airflow Dual Flaps
{{
Heating Dry Operation — —
Power-Airflow Diffuser — — Good-Sleep Cooling Operation — —
Wide-Angle Louvers
{{
Timer 24-Hour On/Off Timer
{{
Vertical Auto-Swing (Up and Down)
{{
Night Set Mode
{{
Horizontal Auto-Swing (Right and Left) — — Worry Free
“Reliability &
Durability”
Auto-Restart (after Power Failure)
{{
3-D Airflow — — Self-Diagnosis (Digital, LED) Display
{{
Comfort Airflow Mode — — Wiring Error Check — —
3-Step Airflow (H/P Only) — —
Anticorrosion Treatment of Outdoor
Heat Exchanger
{{
Comfort
Control
Auto Fan Speed
{{
Indoor Unit Quiet Operation
{{
Flexibility
Multi-Split / Split Type Compatible
Indoor Unit
{{
Night Quiet Mode (Automatic) — —
Outdoor Unit Quiet Operation (Manual)
{{
Flexible Voltage Correspondence
{{
INTELLIGENT EYE
{{
High Ceiling Application — —
Quick Warming Function —
{
Chargeless 10m 10m
Hot-Start Function —
{
Either Side Drain (Right or Left)
{{
Automatic Defrosting —
{
Power Selection — —
Operation Automatic Operation —
{
Remote
Control
5-Rooms Centralized Controller
(Option)
{{
Programme Dry Function
{{
Fan Only
{{
Remote Control Adaptor
(Normal Open-Pulse Contact) (Option)
{{
Lifestyle
Convenience
New POWERFUL Operation
(Non-Inverter)
——
Remote Control Adaptor
(Normal Open Contact) (Option)
{{
Inverter POWERFUL Operation
{{
DIII-NET Compatible (Adaptor) (Option)
{{
Priority-Room Setting — — Remote
Controller
Wireless
{{
Cooling / Heating Mode Lock — — Wired — —
HOME LEAVE Operation — —
ECONO Mode
{{
Indoor Unit On/Off Switch
{{
Signal Reception Indicator
{{
Temperature Display — —
Another Room Operation — —
Note:
{
: Holding Functions
— : No Functions
Содержание
- Capacity tables 9 2
- Cooling only ftks25evma ftks35evma rks25ebvma rks35ebvma 2
- Dimensions 4 2
- Electric characteristics 7 12 installation manual 8 2
- Features 2 power supply 0 3 functions 1 4 specifications 2 2
- Heat pump ftxs25evma ftxs35evma rxs25ebvma rxs35ebvma 2
- Operation limit 3 2
- Operation manual 4 2
- Piping diagrams 7 2
- Sound level 4 2
- Split system room air conditioners e series 2
- Table of contents 2
- Wiring diagrams 6 2
- Option list 0 14 installation manual 1 3
- Optional accessories 0 3
- Comfortable functions 4
- Easy maintenance 4
- Features 4
- Higher energy saving 4
- Installation example 4
- Pair multi compatible indoor unit 4
- Quiet sound levels 4
- Stylish flat design 4
- A dc fan motor is introduced in this small class the motor features fine rotation control and improved energy consumption 5
- Dc fan motor 5
- Decrease the operating current 5
- Econo mode 5
- Features ed04 805 5
- High durability 5
- Large energy savings 5
- Low vibrations and low noise 5
- Rag19a 11 5
- Rag19a 12 5
- Rag19a 17 5
- Reluctance dc motor 5
- Room air conditioners e series 5
- Swing compressor 5
- Intelligent eye 6
- 2 c shift up minimum frequency 34hz 7
- Air flow setting on the r c 7
- Automatic shift up when sensing no human intelligently saving energy 7
- Back to normal operation when presence detected 7
- Decrease sound level 7
- H m l sl ml mh 7
- Intelligent eye 7
- Min absence 7
- Normal operation energy saving operation activated 7
- Rag19a 21 7
- Rag19a 22 7
- Rag19a 23 7
- Saving 20 7
- Saving 30 7
- Selectable 6 steps air flow rate 5 steps and quiet make fine on demand comfort 7
- Steps air flow rate 7
- Db down db down 8
- Ed04 805 features 8
- Indoor unit quiet operation 8
- Mold proof function 8
- Outdoor unit quiet operation 8
- Room air conditioners e series 7 8
- The mold proof operation reduces the spread of mold and decreases nasty odors that is caused by the mold 8
- When quiet button is selected the outdoor unit s operation sound reduces by 3db in night time operation the unit can be operated with less nuisance to the neighborhood 8
- Features ed04 805 9
- Healthy and clean 9
- Mold proof function 9
- Room air conditioners e series 9
- This function is not designed to remove existing dust or mold this function is not available when the unit is turned off using the off timer during this function is operated the flaps open a little and the air is blown upward slightly 9
- Titanium apatite photocatalytic air purifying filter 9
- Ed04 805 features 10
- Room air conditioners e series 9 10
- Wipe clean flat panel 10
- Note power supply intake outdoor unit 11
- Power supply 11
- Power supply ed04 805 11
- Room air conditioners e series 11
- Ed04 805 functions 12
- Functions 12
- Holding functions no functions 12
- Room air conditioners e series 11 12
- Cooling only 13
- Hz 220 230 240v 60hz 220 230v 13
- Room air conditioners e series 13
- Specifications 13
- Specifications ed04 805 13
- Ed04 805 specifications 14
- Heat pump 14
- Hz 220 230 240v 60hz 220 230v 14
- Room air conditioners e series 13 14
- Dimensions 15
- Dimensions ed04 805 15
- Ftks25 35evma 15
- Ftxs25 35evma 15
- Indoor units 15
- Room air conditioners e series 15
- D059795 16
- Ed04 805 dimensions 16
- Outdoor units 16
- Rk x s25 35ebvma 16
- Room air conditioners e series 15 16
- Field wiring 17
- Ftk x s25 35evma 17
- Indoor units 17
- Intelligent eye sensor 17
- Outdoor units 17
- Rk x s25 35ebvma 17
- Room air conditioners e series 17
- Transmission circuit 17
- Wiring diagrams 17
- Wiring diagrams ed04 805 17
- Ed04 805 piping diagrams 18
- Ftks25 35evma ftxs25 35evma 18
- Indoor units 18
- Piping diagrams 18
- Room air conditioners e series 17 18
- Cooling only 19
- Heat pump 19
- Outdoor units 19
- Piping diagrams ed04 805 19
- Rks25 35ebvma 19
- Room air conditioners e series 19
- Rxs25 35ebvma 19
- Afr air flow rate m³ min 1 capacities are based on the following conditions corresponding refrigerant piping length 7 m level difference 0m 2 shows nominal rated capacities and power input bf bypass factor 20
- Bf 0 4 20
- Capacity tables 20
- Cooling only 20
- Ed04 805 capacity tables 20
- Edb entering dry bulb temp c 20
- Ewb entering wet bulb temp c 20
- Ftks25evma rks25ebvma 50hz 220 230 240v 60hz 220 230v 20
- Ftks35evma rks35ebvma 50hz 220 230 240v 60hz 220 230v 20
- Pi power input kw 20
- Room air conditioners e series 19 20
- Shc sensible heat capacity kw 20
- Symbols note 20
- Tc total capacity kw 20
- Afr air flow rate m³ min 1 capacities are based on the following conditions corresponding refrigerant piping length 7 m level difference 0m 2 shows nominal rated capacities and power input bf bypass factor 21
- Bf 0 4 21
- Capacity tables ed04 805 21
- Cooling 21
- Edb entering dry bulb temp c 21
- Ewb entering wet bulb temp c 21
- Ftxs25evma rxs25ebvma 50hz 220 230 240v 60hz 220 230v 21
- Heat pump 21
- Heating 21
- Pi power input kw 21
- Room air conditioners e series 21
- Shc sensible heat capacity kw 21
- Symbols note 21
- Tc total capacity kw 21
- Afr air flow rate m³ min 1 capacities are based on the following conditions corresponding refrigerant piping length 7 m level difference 0m 2 shows nominal rated capacities and power input bf bypass factor 22
- Bf 0 4 22
- Cooling 22
- Ed04 805 capacity tables 22
- Edb entering dry bulb temp c 22
- Ewb entering wet bulb temp c 22
- Ftxs35evma rxs35ebvma 50hz 220 230 240v 60hz 220 230v 22
- Heating 22
- Pi power input kw 22
- Room air conditioners e series 21 22
- Shc sensible heat capacity kw 22
- Symbols note 22
- Tc total capacity kw 22
- Capacity correction factor by the length of refrigerant piping reference 23
- Capacity tables ed04 805 23
- Note the graph shows the factor when additional refrigerant of the proper quantity is charged 23
- Room air conditioners e series 23
- The cooling and the heating capacity of the unit has to be corrected in accordance with the length of refrigerant piping the distance between the indoor unit and the outdoor unit 23
- Cooling only 24
- Ed04 805 operation limit 24
- Heat pump 24
- Operation limit 24
- Rks25 35ebvma 24
- Room air conditioners e series 23 24
- Rxs25 35ebvma 24
- Measuring location 25
- Note 1 operation sound is measured in an anechoic chamber 2 the data are based on the conditions shown in the table below 25
- Room air conditioners e series 25
- Sound level 25
- Sound level ed04 805 25
- Cooling 26
- Ed04 805 sound level 26
- Ftks25evma ftks35evma 26
- Ftxs25evma 26
- Ftxs35evma 26
- Heating 26
- Indoor units 26
- Octave band level 26
- Room air conditioners e series 25 26
- Cooling heating 27
- D047728g 27
- Outdoor units 27
- Rks25ebvma rks35ebvma 27
- Room air conditioners e series 27
- Rxs25ebvma 27
- Rxs35ebvma 27
- Sound level ed04 805 27
- Ed04 805 electric characteristics 28
- Electric characteristics 28
- Room air conditioners e series 27 28
- Caution 29
- Indoor units 29
- Installation manual 29
- Safety precautions 29
- Warning 29
- Accessories 30
- Caution 30
- Choosing an installation site 30
- Indoor unit 30
- Installation tips 30
- Titanium apatite photocatalytic air purifying filter 30
- Wireless remote controller 30
- Caution 31
- Do not hit or violently push the intelligent eye sensor this can lead to damage and malfunction 2 do not place large objects near the sensor also keep heating units or humidifiers outside the sensor s detection area 31
- Indoor unit installation drawings 31
- Installation manual ed04 805 31
- Intelligent eye sensor 31
- Room air conditioners e series 31
- Boring a wall hole and installing wall embedded pipe 32
- For walls containing metal frame or metal board be sure to use a wall embedded pipe and wall cover in the feed through hole to prevent possible heat electrical shock or fire be sure to caulk the gaps around the pipes with caulking material to prevent water leakage 1 bore a feed through hole of 65mm in the wall so it has a down slope toward the outside 2 insert a wall pipe into the hole 3 insert a wall cover into wall pipe 4 after completing refrigerant piping wiring and drain piping caulk pipe hole gap with putty 32
- Indoor unit installation 1 32
- Installing the mounting plate 32
- Recommended mounting plate retention spots and dimensions 32
- The mounting plate should be installed on a wall which can support the weight of the indoor unit 1 temporarily secure the mounting plate to the wall make sure that the panel is completely level and mark the boring points on the wall 2 secure the mounting plate to the wall with screws 32
- 1 right side right back or right bottom piping 1 attach the drain hose to the underside of the refrigerant pipes with an adhesive vinyl tape 2 wrap the refrigerant pipes and drain hose together with an insulation tape 33
- 2 left side left back or left bottom piping 1 attach the drain hose to the underside of the refrigerant pipes with adhesive vinyl tape 33
- 3 wall embedded piping follow the instructions given under 33
- Be sure to connect the drain hose to the drain port in place of a drain plug 33
- Caulk this hole with putty or caulking material bind with plastic tape 33
- Drain hose 33
- Indoor unit installation 2 33
- Insert the drain hose to this depth so it wo 33
- Installing indoor unit 33
- Mounting plate 33
- Open the front panel then open the service lid refer to installation tips 5 pass the interconnecting wires from the outdoor unit through the feed through wall hole and then through the back of the indoor unit pull them through the front side bend the ends of tie wires upward for easier work in advance if the interconnecting wire ends are to be stripped first bundle wire ends with adhesive tape 6 press the bottom frame of the indoor unit with both hands to set it on the mounting plate hooks make sure that the wires do not catch on the edge of the indoor unit 33
- Pass the drain hose and refrigerant pipes through the wall hole then set the indoor unit on the mounting plate hooks by using the markings at the top of the indoor unit as a guide 33
- Shape the refrigerant pipe along the pipe path marking on the mounting plate 4 pass drain hose and refrigerant pipes through the wall hole then set the indoor unit on mounting plate hooks using the markings at the top of indoor unit as a guide 5 pull in the interconnecting wires 6 connect the inter unit piping 7 wrap the refrigerant pipes and drain hose together with insulation tape as right figure in case of setting the drain hose through the back of the indoor unit 8 33
- T be pulled out of the drain pipe 33
- Wrap insulating tape around the bent portion of refrigerant pipe overlap at least half the width of the tape with each turn 33
- Drain piping 34
- Indoor unit installation 3 34
- Warning 34
- When connecting to an ha system 34
- Wiring 34
- 1 caution on piping handling 1 protect the open end of the pipe against dust and moisture 2 all pipe bends should be as gentle as possible use a pipe bender for bending bending radius should be 30 to 40mm or larger 2 2 selection of copper and heat insulation materials 35
- 144 175kgf cm 35
- 17 n m 35
- 330 407kgf cm 35
- 35 class 25 35 class 35
- 39 n m 35
- 4 inch 35
- 8 inch 35
- Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand then tighten them fully with the torque wrenches 35
- Apply oil 35
- Caution 35
- Cut the pipe end with a pipe cutter 2 remove burrs with the cut surface facing downward so that the chips do not enter the pipe 3 put the flare nut on the pipe 4 flare the pipe 5 check that the flaring is properly made 35
- Do never install a drier to this r410a unit in order to guarantee its lifetime 5 the drying material may dissolve and damage the system 6 incomplete flaring may cause refrigerant gas leakage 35
- Do not use mineral oil on flared part 2 prevent mineral oil from getting into the system as this would reduce the lifetime of the units 3 35
- Flare nut tightening torque 35
- Flaring 35
- Flaring the pipe end 35
- Gas pipe thermal insulation 35
- Gas side 35
- Insulation material polyethylene foam heat transfer rate 0 41 to 0 52w mk 0 35 to 0 45kcal mh c refrigerant gas pipe s surface temperature reaches 110 c max choose heat insulation materials that will withstand this temperature 2 be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below 35
- Liquid side 35
- Liquid side liquid pipe thermal insulation 35
- O d 6 mm i d 8 10mm 35
- O d 9 mm i d 12 15mm 35
- Refrigerant piping 35
- Refrigerant piping work 35
- Thickness 0 mm thickness 10mm min 35
- Tighten 35
- Use separate thermal insulation pipes for gas and liquid refrigerant pipes 35
- Use the flare nut fixed to the main unit to prevent cracking of the flare nut by aged deterioration 2 35
- Warning 35
- Test items 36
- Trial operation and testing 36
- Trial operation from remote controller 36
- After completing installation test the unit to check for installation errors give the user adequate instructions concerning the use and cleaning of the unit according to the operation manual 37
- Caution 37
- Outdoor units 37
- Read these safety precautions carefully to ensure correct installation this manual classifies the precautions into warning and caution be sure to follow all the precautions below they are all important for ensuring safety 37
- Safety precautions 37
- The following safety symbols are used throughout this manual 37
- Warning 37
- Accessories 38
- Caution 38
- Precautions for selecting the location 38
- Precautions on installation 38
- Installation guidelines 39
- Installation manual ed04 805 39
- Outdoor unit installation drawings 39
- Room air conditioners e series 39
- Wall facing one side 39
- Walls facing three sides 39
- Walls facing two sides 39
- Where a wall or other obstacle is in the path of outdoor unit s intake or exhaust airflow follow the installation guidelines below for any of the below installation patterns the wall height on the exhaust side should be 1200mm or less 39
- Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand then tighten them fully with the torque wrenches 40
- Caution 40
- Cut the pipe end with a pipe cutter 2 remove burrs with the cut surface facing downward so that the chips do not enter the pipe 3 put the flare nut on the pipe 4 flare the pipe 5 check that the flaring is properly made 40
- Do never install a drier to this r410a unit in order to guarantee its lifetime 5 the drying material may dissolve and damage the system 6 incomplete flaring may cause refrigerant gas leakage 40
- Do not use mineral oil on flared part 2 prevent mineral oil from getting into the system as this would reduce the lifetime of the units 3 40
- Drain work heat pump models 40
- Flaring the pipe end 40
- Installing outdoor unit 40
- Outdoor unit installation 1 40
- Refrigerant piping 40
- Use drain plug for drainage 2 if the drain port is covered by a mounting base or floor surface place additional foot bases of at least 30mm in height under the outdoor unit s feet 3 in cold areas do not use a drain hose with the outdoor unit otherwise drain water may freeze impairing heating performance 40
- Use the flare nut fixed to the main unit to prevent cracking of the flare nut by aged deterioration 2 to prevent gas leakage apply refrigeration oil only to the inner surface of the flare use refrigeration oil for r410a 3 40
- Warning 40
- When installing the outdoor unit refer to precautions for selecting the location and the outdoor unit installation drawings 2 if drain work is necessary follow the procedures below 40
- Outdoor unit installation 2 41
- Purging air and checking gas leakage 41
- Warning 41
- 1 cautions on pipe handling 1 42
- Caution 42
- How to force cooling operation mode 42
- Outdoor unit installation 3 42
- Pump down operation 42
- Refilling the refrigerant 42
- Refrigerant piping work 42
- Selection of copper and heat insulation materials 42
- W mk 0 35 to 0 45kcal mh 42
- Caution 43
- Do not turn on the safety breaker until all work is completed 1 43
- Do not use tapped wires stranded wires extensioncords or starburst connections as they may cause overheating electrical shock or fire 2 do not use locally purchased electrical parts inside the product do not branch the power for the drain pump etc from the terminal block doing so may cause electric shock or fire 3 be sure to install an earth leakage breaker one that can handle higher harmonics this unit uses an inverter which means that it must be used an earth leakage breaker capable handling harmonics in order to prevent malfunctioning of the earth leakage breaker itself 4 use an all pole disconnection type breaker with at least 3mm between the contact point gaps 43
- Good wrong 43
- Observe the notes mentioned below when wiring to the power supply terminal board precautions to be taken for power supply wiring use a round crimp style terminal for connection to the power supply terminal board in case it cannot be used due to unavoidable reasons be sure to observe the following instruction 43
- Problems with the work may cause heat and fires 43
- Round crimp style terminal 43
- Stranded wire 43
- Warning 43
- Wiring 43
- Test items 44
- Test run and final check 44
- Trial operation and testing 44
- Caution 45
- Operation manual 45
- Safety precautions 45
- Warning 45
- Consider nuisance to your neighbours from noises 46
- Electrical work 46
- Installation site 46
- System relocation 46
- Indoor unit 47
- Names of parts 47
- Outdoor unit 48
- On off 49
- Remote controller 49
- Attention 50
- Preparation before operation 50
- Set the front cover as before 50
- Set two dry batteries aaa 50
- Slide the front cover to take it off 50
- To set the batteries 50
- Attention 51
- Choose a place from where the sig nals reach the unit 51
- Fix the holder to a wall a pillar etc with the screws supplied with the holder 51
- Place the remote controller in the remote controller holder 51
- Preparation before operation 51
- To fix the remote controller holder on the wall 51
- To operate the remote controller 51
- Be careful not to cool heat the room too much keeping the temperature setting at a moderate level helps save energy 52
- Blocking sunlight and air from outdoors increases the cooling heating effect 52
- Cancel 52
- Clogged air filters cause inefficient operation and waste energy clean them once in about every two weeks 52
- Condensation may occur on the indoor unit and drip 52
- Cover windows with a blind or a curtain 52
- If you are not going to use the air conditioner for a long period for example in spring or autumn turn the breaker off 52
- Mode fan 52
- Operation outside this humidity or temperature range may cause a safety device to disable the system 52
- Outdoor temperature 10 to 20 c indoor temperature 10 to 30 c 52
- Outdoor temperature 10 to 46 c indoor temperature 18 to 32 c indoor humidity 80 max 52
- Please note 52
- Press clock button 52
- Press timer setting button to set the clock to the present time 52
- Recommended temperature setting 52
- Sensor 52
- The air conditioner always consumes 15 35 watts of electricity even while it is not operating 52
- Tips for saving energy 52
- To set the clock 52
- Turn the breaker on 52
- Use the air conditioner in the following conditions 52
- Auto dry cool heat fan operation 53
- Press mode selector button and select a operation mode 53
- Press on off button 53
- Press on off button again 53
- Press temperature adjustment button 53
- To change the temperature setting 53
- To start operation 53
- To stop operation 53
- Press fan setting button 54
- To change the air flow rate setting 54
- Adjusting the air flow direction 55
- To adjust the horizontal blades flaps 55
- Notes on flaps and louvres angles 56
- To adjust the vertical blades louvres 56
- Powerful operation 57
- To cancel powerful operation 57
- To start powerful operation 57
- Outdoor unit quiet operation 58
- To cancel outdoor unit quiet operation 58
- To start outdoor unit quiet operation 58
- Econo operation 59
- To cancel econo opera tion 59
- To start econo operation 59
- Mold proof operation 60
- To cancel mold proof operation 60
- To set mold proof operation 60
- Intelligent eye operation 61
- Press sensor button 61
- Press sensor button again 61
- To cancel the intelligent eye operation 61
- To start intelligent eye operation 61
- Caution 62
- Intelligent eye is useful for energy saving 62
- Notes on intelligent eye 62
- Timer operation 63
- To cancel the off timer operation 63
- To use off timer opera tion 63
- Attention 64
- Press cancel button 64
- Press on timer button 64
- Press on timer button again 64
- Press timer setting button until the time setting reaches the point you like 64
- To cancel on timer operation 64
- To combine on timer and off timer 64
- To use on timer operation 64
- Attach the front panel 65
- Before cleaning be sure to stop the operation and turn the breaker off 65
- Care and cleaning 65
- Caution 65
- Clean the front panel 65
- Front panel 65
- Indoor unit outdoor unit and remote controller 65
- Open the front panel 65
- Remove the front panel 65
- Wipe them with dry soft cloth 65
- Air filter 66
- Filters 66
- Maintenance 66
- Replacement 66
- Titanium apatite photocatalytic air purifying filter 66
- After operation stops turn off the breaker for the room air conditioner 67
- Before a long idle period 67
- Clean the air filters and set them again 67
- Operate the fan only for several hours on a fine day to dry out the inside 67
- Take out batteries from the remote controller 67
- Case explanation 68
- These cases are not troubles 68
- Trouble shooting 68
- Case check 69
- Check again 69
- A switch or a button often fails to work properly there is a burning smell water leaks from the indoor unit 70
- Call the service shop immediately 70
- The power cord is abnormally hot or damaged an abnormal sound is heard during operation 70
- Turn the breaker off and call the service shop 70
- Warning 70
- We recommend periodical maintenance 70
- Option list 71
- Optional accessories 71
- Optional accessories ed04 805 71
- Room air conditioners e series 71
- Time clock and other devices obtained locally 71
- Wiring adaptor is also required for each indoor unit 71
- Ed04 805 optional accessories 72
- Field wiring 72
- Functions and features 72
- Installation manual 72
- Krp413a1s 72
- Room air conditioners e series 71 72
- Safety precautions 72
- Installation 73
- Krp413a1 73
- Krp413a1s krp413aa1s 73
- Optional accessories ed04 805 73
- Room air conditioners e series 73
- Automatic reset after power failure 74
- Connection with remote controller 74
- Ed04 805 optional accessories 74
- Room air conditioners e series 73 74
- Wiring 74
- Diagnostic check 75
- Is the air conditioner working properly are the connectors of the wiring properly connected are the remote controller and field wiring properly connected are all switch settings correct if there is nothing apparently wrong conduct a diagnostic check using the following procedure 75
- Optional accessories ed04 805 75
- Room air conditioners e series 75
- Switch settings and connection terminals 75
- Test operation and confirmation 75
- When the system is not working 75
- Binding band 76
- Component parts and separately sold parts which are required 76
- Ed04 805 optional accessories 76
- Fan operation cannot be selected from the central controller or wired remote controller 76
- Group control i e control of multiple indoor units with a single remote controller is not available 76
- Installation manual 76
- Krp928b2s 76
- Mounting screws 76
- Names of parts and electric wiring 76
- Overview features and compatible models 76
- Room air conditioners e series 75 76
- Safety precautions 76
- Combining equipment 77
- Optional accessories ed04 805 77
- P157704 2b 77
- Read operating error display signal 77
- Room air conditioners e series 77
- Switch settings 5 control codes 77
- Before installation 78
- Caution 78
- Installation of louver 78
- Installation procedure 78
- Kpw937a4 78
- Selection of installation location 78
Похожие устройства
- Daikin FTXS35EVMA Инструкция по монтажу
- Daikin FTXS35EVMA Инструкция по эксплуатации
- Daikin FTXS35EVMA Сервис мануал
- Daikin FTXS35EVMA Технические данные
- Daikin FTKS25EVMA Инструкция по эксплуатации
- Daikin FTKS25EVMA Технические данные
- Daikin FTKS25EVMA Сервис мануал
- Daikin FTKS35EVMA Инструкция по эксплуатации
- Daikin FTKS35EVMA Технические данные
- Daikin FTKS35EVMA Сервис мануал
- Iek ВД1-63 2Р 50А 100мА Руководство по эксплуатации
- Iek ВД1-63 2Р 50А 30мА тип А Руководство по эксплуатации
- Iek ВД1-63 2Р 63А 300мА Руководство по эксплуатации
- Iek ВД1-63 2Р 80А 100мА Руководство по эксплуатации
- Iek ВД1-63 2Р100А 100мА Руководство по эксплуатации
- Iek ВД1-63 4Р 16А 10мА Руководство по эксплуатации
- Iek ВД1-63 4Р 16А 30мА Руководство по эксплуатации
- Iek ВД1-63 4Р 25А 10мА Руководство по эксплуатации
- Iek ВД1-63 2Р 32А 30мА тип А Руководство по эксплуатации
- Iek ВД1-63 2Р 40А 30мА Руководство по эксплуатации
Скачать
Случайные обсуждения