Daikin FTKS60FVM [59/244] 3 minute standby

Daikin FTKS71FVM [59/244] 3 minute standby
Control Specification Si04-703A
48 Function and Control
3.3.4 3-Minute Standby
Prohibit to turn ON the compressor for 3 minutes after turning it off.
(Except when defrosting. (Only for Heat Pump Model).)
3.3.5 Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of frequency must be set as
follows. (The function must not be used when defrosting (only for heat pump model).)
3.4 Discharge Pipe Temperature Control
Outline The discharge pipe temperature is used as the compressor's internal temperature. If the
discharge pipe temperature rises above a certain level, the operating frequency upper limit is
set to keep this temperature from going up further.
Detail Divide the Zone
Management within the Zones
FCG 3
FCG 2
FCG 1
85
70
55
80
65
55
50/60class,
71FVM(T)
71-90FVMA
Zone Control contents
Stop zone When the temperature reaches the stop zone, stop the compressor and
correct abnormality.
Drooping zone Start the timer, and the frequency will be drooping.
Keep zone Keep the upper limit of frequency.
Reset zone Cancel the upper limit of frequency.
A˚C
B˚C
C˚C
D˚C
E˚C
(R5205)
A
B
C
D
E
50/60 class
110
103
101.5
100
95
71/80/90 class
120
111
109
107
107
Keep zone
Stop zone
Reset zone
Discharge pipe
temperature
Drooping
zone

Содержание

Скачать