Capacity Tables ED04-702
26 Room Air Conditioners F-Series
FTXS60FVMA + RXS60FVMA (50Hz 220-240V / 60Hz 220-230V)
3D055263
Cooling
AFR 16.2
BF 0.28
INDOOR OUTDOOR TEMPERATURE(°CDB)
EWB EDB 20 25 30 32 35 40
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20 5.684.001.495.684.001.665.593.951.815.483.891.875.313.801.965.033.662.10
16.0 22 6.424.181.536.144.031.675.863.891.825.753.841.885.593.751.975.313.622.11
18.0 25 6.704.321.546.424.191.686.144.061.836.034.001.895.863.931.985.583.802.12
19.0 27 6.84 4.51 1.54 6.56 4.38 1.69 6.28 4.25 1.83 6.17 4.20 1.89
6.00 4.12 1.98 5.72 4.00 2.13
22.0 30 7.254.331.556.974.211.706.694.101.856.584.061.916.413.991.996.143.882.14
24.0 32 7.534.201.567.254.091.716.973.991.866.863.951.916.693.892.006.413.792.15
Heating
AFR 17.4
INDOOR OUTDOOR TEMPERATURE(°CWB)
EDB –10 –5 0 6 10
°C TC PI TC PI TC PI TC PI TC PI
15.0 4.71 1.73 5.50 1.81 6.29 1.89 7.24 1.99 7.87 2.06
20.0 4.471.775.261.866.051.94
7.00 2.04 7.63 2.11
22.0 4.37 1.79 5.16 1.87 5.95 1.96 6.90 2.06 7.54 2.13
24.0 4.28 1.81 5.07 1.89 5.86 1.98 6.81 2.08 7.44 2.14
25.0 4.23 1.82 5.02 1.90 5.81 1.99 6.76 2.09 7.39 2.15
27.0 4.13 1.84 4.92 1.92 5.71 2.00 6.66 2.10 7.29 2.17
Symbols NOTE:
AFR : Air flow rate (m³/min.) 1. Capacities are based on the following conditions.
(1) Corresponding refrigerant piping length : 7.5m
(2) Level difference : 0m
2. shows nominal (rated) capacities and power input.
BF : Bypass factor
EWB : Entering wet bulb temp. C)
EDB : Entering dry bulb temp. (°C)
TC : Total capacity (kW)
SHC : Sensible heat capacity (kW)
PI : Power input (kW)