Daikin RKS71FVM [43/125] 505 615kgf cm 630 770kgf cm 144 175kgf cm
![Daikin RKS50FVM [43/125] 505 615kgf cm 630 770kgf cm 144 175kgf cm](/views2/1778485/page43/bg2b.png)
Installation Manual ED04-702
42 Room Air Conditioners F-Series
Refrigerant Piping Work
2. Refrigerant piping.
1)
Align the centres of both flares and tighten the flare nuts 3 or 4
turns by hand. Then tighten them fully with the torque wrenches.
•
Use torque wrenches when tightening the flare nuts to
prevent damage to the flare nuts and escaping gas.
2-1. Caution on piping handling.
1) Protect the open end of the pipe against dust and moisture.
2) All pipe bends should be as gentle as possible. Use a
pipe bender for bending.
(Bending radius should be 30 to 40mm or larger.)
2-2. Selection of copper and heat insulation materials.
•
When using commercial copper pipes and fittings, observe the following:
1) Insulation material: Polyethylene foam
Heat transfer rate: 0.041 to 0.052W/mK (0.035 to 0.045kcal/(mh •ºC))
Refrigerant gas pipe’s surface temperature reaches 110ºC max.
Choose heat insulation materials that will withstand this temperature.
2) Be sure to insulate both the gas and liquid piping and to provide
insulation dimensions as below.
1. Flaring the pipe end.
1) Cut the pipe end with a pipe cutter.
2)
Remove burrs with the cut surface facing
downward so that the chips do not enter the
pipe.
3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.
1) Do not use mineral oil on flared part.
2) Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
3) Never use piping which has been used for previous installations. Only use parts which are delivered
with the unit.
4) Do never install a drier to this R410A unit in order to guarantee it’s lifetime.
5) The drying material may dissolve and damage the system.
6) Incomplete flaring may cause refrigerant gas leakage.
WARNING
2) To prevent gas leakage, apply refrigeration oil on both inner and outer surfaces of the flare.
(Use refrigeration oil for R410A.)
3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.
Thickness 10mm Min.
71 class
O.D. 15.9mm
Thickness 1.0mm
50/60 class
O.D. 12.7mm
Thickness 0.8mm
71 class
I.D. 16-20mm
50/60 class
I.D. 14-16mm
Gas side Gas pipe thermal insulation
50/60/71 classs
O.D. 6.4mm
Thickness 0.8mm
50/60/71 class
I.D. 8-10mm
Liquid side Liquid pipe thermal insulation
Flare nut tightening torque
Gas side Liquid side
1/2 inch 5/8 inch 1/4 inch
49.5-60.3N
m 61.8-75.4N m 14.2-17.2N m
(505-615kgf
cm) (630-770kgf cm) (144-175kgf cm)
,
install as described in the installation manual supplied with the Multi outdoor unit.
With a Multi indoor unit
Coat here with refrigeration oil
Torque wrench
Piping union
Flare nut
Spanner
Wall
If no flare cap is
available, cover
the flare mouth
with tape to keep
dirt or water out.
Be sure to
place a cap.
Rain
Gas pipe
Liquid pipe
Gas pipe
insulation
Liquid pipe
insulation
Finishing tape
Drain hose
Inter-unit wiring
(Cut exactly at
right angles.) Remove burrs
Set exactly at the position shown below.
A
Flaring
Die
A 0-0.5mm
Clutch-type
Flare tool for R410A
1.0-1.5mm
Clutch-type (Rigid-type)
1.5-2.0mm
Wing-nut type (Imperial-type)
Conventional flare tool
Check
Flare’s inner
surface must
be flaw-free.
The pipe end must
be evenly flared in
a perfect circle.
Make sure that the
flare nut is fitted.
Содержание
- Capacity tables 3 2
- Cooling only ftks50fvm ftks60fvm ftks71fvm 2
- Dimensions 3 2
- Electric characteristics 5 12 installation manual 6 2
- Features 2 power supply 3 functions 4 specifications 0 2
- Heat pump ftxs50fvma ftxs60fvma ftxs71fvma 2
- Operation limit 9 10 sound level 0 2
- Piping diagrams 0 2
- Rks50fvm rks60fvm rks71fvm 2
- Rxs50fvma rxs60fvma rxs71fvma 2
- Split system room air conditioners f series 2
- Table of contents 2
- Wiring diagrams 7 2
- Operation manual 6 3
- Optional accessories 16 3
- A dc fan motor is introduced for the first time in this small class the motor features fine rotation control and improved energy consumption 4
- Comfortable functions 4
- Dc fan motor 4
- Ed04 702 features 4
- Energy saving 4
- Features 4
- High durability 4
- Home leave operation indoor unit quiet operation outdoor unit quiet operation 4
- Large energy savings 4
- Low vibrations and low noise 4
- Reluctance dc motor 4
- Room air conditioners f series 3 4
- Swing compressor 4
- Swing compressor reluctance dc motor pam control intelligent eye 4
- Wipe clean flat panel healthy clean functions 4
- Features ed04 702 5
- Intelligent eye 5
- Room air conditioners f series 5
- Saving 20 5
- Ed04 702 features 6
- H m l sl ml mh 6
- Heating 6
- Indoor unit quiet operation 6
- Intelligent eye 6
- Room air conditioners f series 5 6
- Saving 30 6
- Steps air flow rate 6
- Temperature 6
- Db down db down 7
- Features ed04 702 7
- Home leave operation 7
- In night time operation the unit can be operated with less nuisance to the neighborhood 7
- Outdoor unit quiet operation 7
- Room air conditioners f series 7
- When quiet button is selected the outdoor unit s operation sound reduces by 3db 7
- Ed04 702 features 8
- Room air conditioners f series 7 8
- Titanium apatite photocatalytic air purifying filter 8
- Wipe clean 8
- Note power supply intake outdoor unit 9
- Power supply 9
- Power supply ed04 702 9
- Room air conditioners f series 9
- Ed04 702 functions 10
- Functions 10
- Holding functions no functions 10
- Room air conditioners f series 9 10
- Cooling only 11
- Hz 220 230 240v 60hz 220 230v 11
- Room air conditioners f series 11
- Specifications 11
- Specifications ed04 702 11
- Ed04 702 specifications 12
- Heat pump 12
- Hz 220 230 240v 60hz 220 230v 12
- Room air conditioners f series 11 12
- Hz 220 230 240v 60hz 220 230v 13
- Room air conditioners f series 13
- Specifications ed04 702 13
- Dimensions 14
- Ed04 702 dimensions 14
- Ftks50fvm ftks60fvm 14
- Ftks71fvm 14
- Indoor units 14
- Room air conditioners f series 13 14
- Blade angles 15
- Controller 15
- D054935a 15
- D054936a 15
- Dimensions ed04 702 15
- Ftxs50fvma ftxs60fvma 15
- Ftxs71fvma 15
- Required space 15
- Room air conditioners f series 15
- Standard locations of wall holes 15
- Wireless remote 15
- D051657d 16
- D051658c 16
- Ed04 702 dimensions 16
- Outdoor units 16
- Rks50fvm rks60fvm rxs50fvma rxs60fvma 16
- Rks71fvm 16
- Room air conditioners f series 15 16
- D054589a 17
- Dimensions ed04 702 17
- Room air conditioners f series 17
- Rxs71fvma 17
- Ed04 702 wiring diagrams 18
- Ftks50fvm ftks60fvm ftks71fvm ftxs50fvma ftxs60fvma ftxs71fvma 18
- Indoor units 18
- Room air conditioners f series 17 18
- Wiring diagrams 18
- D050981f 19
- D052297c 19
- Outdoor units 19
- Rks50fvm rks60fvm 19
- Rks71fvm 19
- Room air conditioners f series 19
- Wiring diagrams ed04 702 19
- D050706f 20
- D053931b 20
- Ed04 702 wiring diagrams 20
- Indoor 20
- Outdoor 20
- Room air conditioners f series 19 20
- Rxs50fvma rxs60fvma 20
- Rxs71fvma 20
- Ftks50fvm ftks60fvm ftks71fvm 21
- Ftxs50fvma ftxs60fvma ftxs71fvma 21
- Indoor units 21
- Piping diagrams 21
- Piping diagrams ed04 702 21
- Room air conditioners f series 21
- Cooling only 22
- Ed04 702 piping diagrams 22
- Outdoor units 22
- Rks50fvm rks60fvm 22
- Rks71fvm 22
- Room air conditioners f series 21 22
- Heat pump 23
- Piping diagrams ed04 702 23
- Room air conditioners f series 23
- Rxs50fvma rxs60fvma 23
- Rxs71fvma 23
- Afr air flow rate m³ min 1 capacities are based on the following conditions 1 corresponding refrigerant piping length 7 m 2 level difference 0m 2 shows nominal rated capacities and power input bf bypass factor 24
- Capacity tables 24
- Cooling only 24
- Ed04 702 capacity tables 24
- Edb entering dry bulb temp c 24
- Ewb entering wet bulb temp c 24
- Ftks50fvm rks50fvm 50hz 220 240v 60hz 220 230v 24
- Ftks60fvm rks60fvm 50hz 220 240v 60hz 220 230v 24
- Pi power input kw 24
- Room air conditioners f series 23 24
- Shc sensible heat capacity kw 24
- Symbols note 24
- Tc total capacity kw 24
- Afr air flow rate m³ min 1 capacities are based on the following conditions 1 corresponding refrigerant piping length 7 m 2 level difference 0m 2 shows nominal rated capacities and power input bf bypass factor 25
- Capacity tables ed04 702 25
- Edb entering dry bulb temp c 25
- Ewb entering wet bulb temp c 25
- Ftks71fvm rks71fvm 50hz 220 240v 60hz 220 230v 25
- Pi power input kw 25
- Room air conditioners f series 25
- Shc sensible heat capacity kw 25
- Symbols note 25
- Tc total capacity kw 25
- Afr air flow rate m³ min 1 capacities are based on the following conditions 1 corresponding refrigerant piping length 7 m 2 level difference 0m 2 shows nominal rated capacities and power input bf bypass factor 26
- Cooling 26
- Ed04 702 capacity tables 26
- Edb entering dry bulb temp c 26
- Ewb entering wet bulb temp c 26
- Ftxs50fvma rxs50fvma 50hz 220 240v 60hz 220 230v 26
- Heat pump 26
- Heating 26
- Pi power input kw 26
- Room air conditioners f series 25 26
- Shc sensible heat capacity kw 26
- Symbols note 26
- Tc total capacity kw 26
- Afr air flow rate m³ min 1 capacities are based on the following conditions 1 corresponding refrigerant piping length 7 m 2 level difference 0m 2 shows nominal rated capacities and power input bf bypass factor 27
- Capacity tables ed04 702 27
- Cooling 27
- Edb entering dry bulb temp c 27
- Ewb entering wet bulb temp c 27
- Ftxs60fvma rxs60fvma 50hz 220 240v 60hz 220 230v 27
- Heating 27
- Pi power input kw 27
- Room air conditioners f series 27
- Shc sensible heat capacity kw 27
- Symbols note 27
- Tc total capacity kw 27
- Afr air flow rate m³ min 1 capacities are based on the following conditions 1 corresponding refrigerant piping length 7 m 2 level difference 0m 2 shows nominal rated capacities and power input bf bypass factor 28
- Cooling 28
- Ed04 702 capacity tables 28
- Edb entering dry bulb temp c 28
- Ewb entering wet bulb temp c 28
- Ftxs71fvma rxs71fvma 50hz 220 240v 60hz 220 230v 28
- Heating 28
- Pi power input kw 28
- Room air conditioners f series 27 28
- Shc sensible heat capacity kw 28
- Symbols note 28
- Tc total capacity kw 28
- 50 class 29
- 60 71 class 29
- Capacity correction factor by the length of refrigerant piping reference 29
- Capacity tables ed04 702 29
- Note 1 the graphs show the factor when additional refrigerant of the proper quantity is charged 29
- Room air conditioners f series 29
- The cooling and the heating capacity of the unit has to be corrected in accordance with the length of refrigerant piping the distance between the indoor unit and the outdoor unit 29
- Ed04 702 operation limit 30
- Operation limit 30
- Rks50fvm rks60fvm rks71fvm 30
- Room air conditioners f series 29 30
- Rxs50fvma rxs60fvma rxs71fvma 30
- Measuring location 31
- Note 1 operation sound is measured in an anechoic chamber 2 the data are based on the conditions shown in the table below 31
- Room air conditioners f series 31
- Sound level 31
- Sound level ed04 702 31
- D040305g 32
- Ed04 702 sound level 32
- Ftks50fvm ftks60fvm 32
- Ftks71fvm 32
- Indoor units cooling only 32
- Octave band level 32
- Room air conditioners f series 31 32
- Cooling 33
- Cooling heating 33
- Ftxs50fvma 33
- Ftxs60fvma 33
- Ftxs71fvma 33
- Heating 33
- Indoor units heat pump 33
- Room air conditioners f series 33
- Sound level ed04 702 33
- D056049 34
- D056050 34
- D056051 34
- Ed04 702 sound level 34
- Outdoor units cooling only 34
- Rks50fvm rks60fvm 34
- Rks71fvm 34
- Room air conditioners f series 33 34
- Cooling 35
- Cooling heating 35
- Heating 35
- Outdoor units heat pump 35
- Room air conditioners f series 35
- Rxs50fvma 35
- Rxs60fvma 35
- Rxs71fvma 35
- Sound level ed04 702 35
- Ed04 702 electric characteristics 36
- Electric characteristics 36
- Fla full load amps a 36
- Ifm indoor fan motor 36
- Mca min circuit amps a 1 rla is based on the following conditions indoor temp 27 cdb 19 cwb outdoor temp 35 cdb 2 maximum allowable voltage variation between phases is 2 3 select wire size based on the larger value of mca 4 instead of fuse use circuit breaker 5 be sure to install an earth leak detector one that can handle higher harmonics this unit uses an inverter which means that it must be used an earth leak detector capable handling high harmonics in order to prevent malfunctioning of the earth leak detector itself 36
- Mfa max fuse amps a 36
- Ofm outdoor fan motor 36
- Rhz rated operating frequency hz 36
- Rla rated load amps a 36
- Room air conditioners f series 35 36
- Symbols note 36
- W fan motor rated output w 36
- Indoor units 37
- Installation manual 37
- Safety precautions 37
- Accessories 38
- Caution 38
- Choosing an installation site 38
- Ftks 50 60 71 f 38
- Indoor unit 38
- Installation tips 38
- Wireless remote controller 38
- Caution 39
- Do not hit or violently push the intelligent eye sensor this can lead to damage and malfunction 2 do not place large objects near the sensor also keep heating units or humidifiers outside the sensor s detection area 39
- Indoor unit installation drawings 39
- Installation manual ed04 702 39
- Intelligent eye sensor 39
- Room air conditioners f series 39
- Boring a wall hole and installing wall embedded pipe 40
- For walls containing metal frame or metal board be sure to use a wall embedded pipe and wall cover in the feed through hole to prevent possible heat electrical shock or fire be sure to caulk the gaps around the pipes with caulking material to prevent water leakage 1 bore a feed through hole of 80mm in the wall so it has a down slope toward the outside 2 insert a wall pipe into the hole 3 insert a wall cover into wall pipe 4 after completing refrigerant piping wiring and drain piping caulk pipe hole gap with putty 40
- Indoor unit installation 1 40
- Installing the mounting plate 40
- Recommended mounting plate retention spots and dimensions 40
- The mounting plate should be installed on a wall which can support the weight of the indoor unit 1 temporarily secure the mounting plate to the wall make sure that the panel is completely level and mark the boring points on the wall 2 secure the mounting plate to the wall with screws 40
- 1 right side right back or right bottom piping 1 attach the drain hose to the underside of the refrigerant pipes with an adhesive vinyl tape 2 wrap the refrigerant pipes and drain hose together with an insulation tape 41
- 2 left side left back or left bottom piping 1 attach the drain hose to the underside of the refrigerant pipes with adhesive vinyl tape 41
- 3 wall embedded piping follow the instructions given under 41
- Be sure to connect the drain hose to the drain port in place of a drain plug 41
- Indoor unit installation 2 41
- Insert the drain hose to this depth so it won t be pulled out of the drain pipe 41
- Installing indoor unit 41
- Open the front panel then open the service lid refer to installation tips 5 pass the inter unit wiring from the outdoor unit through the feed through wall hole and then through the back of the indoor unit pull them through the front side bend the ends of tie wires upward for easier work in advance if the inter unit wiring ends are to be stripped first bundle wire ends with adhesive tape 6 press the bottom frame of the indoor unit with both hands to set it on the mounting plate hooks make sure that the wires do not catch on the edge of the indoor unit 41
- Pass the drain hose and refrigerant pipes through the wall hole then set the indoor unit on the mounting plate hooks by using the markings at the top of the indoor unit as a guide 41
- Shape the refrigerant pipe along the pipe path marking on the mounting plate 4 pass drain hose and refrigerant pipes through the wall hole then set the indoor unit on mounting plate hooks using the markings at the top of indoor unit as a guide 5 pull in the inter unit wiring 6 connect the inter unit piping 7 wrap the refrigerant pipes and drain hose together with insulation tape as right figure in case of setting the drain hose through the back of the indoor unit 8 41
- Drain piping 42
- Indoor unit installation 3 42
- Warning 42
- When connecting to an ha system 42
- Wiring 42
- 1 caution on piping handling 1 protect the open end of the pipe against dust and moisture 2 all pipe bends should be as gentle as possible use a pipe bender for bending bending radius should be 30 to 40mm or larger 43
- 2 inch 1 2 inch 5 8 inch 1 4 inch 43
- 2 selection of copper and heat insulation materials 43
- 505 615kgf cm 630 770kgf cm 144 175kgf cm 43
- 60 71 class 43
- 60 71 classs 43
- 60 class 43
- 60 n m 49 60 n m 61 75 n m 14 17 n m 43
- Cut the pipe end with a pipe cutter 2 43
- Do not use mineral oil on flared part 2 prevent mineral oil from getting into the system as this would reduce the lifetime of the units 3 never use piping which has been used for previous installations only use parts which are delivered with the unit 4 do never install a drier to this r410a unit in order to guarantee it s lifetime 5 the drying material may dissolve and damage the system 6 incomplete flaring may cause refrigerant gas leakage 43
- Flare nut tightening torque 43
- Flaring 43
- Flaring the pipe end 43
- Gas side gas pipe thermal insulation 43
- Gas side gas side liquid side 43
- I d 14 16mm 43
- I d 16 20mm 43
- I d 8 10mm 43
- Insulation material polyethylene foam heat transfer rate 0 41 to 0 52w mk 0 35 to 0 45kcal mh ºc refrigerant gas pipe s surface temperature reaches 110ºc max choose heat insulation materials that will withstand this temperature 2 be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below 43
- Liquid side liquid pipe thermal insulation 43
- O d 12 mm 43
- O d 15 mm 43
- O d 6 mm 43
- Put the flare nut on the pipe 4 flare the pipe 5 check that the flaring is properly made 43
- Refrigerant piping 43
- Refrigerant piping work 43
- Thickness 0 mm 43
- Thickness 1 mm 43
- Thickness 10mm min 43
- To prevent gas leakage apply refrigeration oil on both inner and outer surfaces of the flare use refrigeration oil for r410a 43
- Use separate thermal insulation pipes for gas and liquid refrigerant pipes 43
- Warning 43
- Test items 44
- Trial operation and testing 44
- Trial operation from remote controller 44
- Accessories 45
- Caution 45
- Choosing an installation site 45
- Ftxs 50 60 71 f 45
- Indoor unit 45
- Installation tips 45
- Wireless remote controller 45
- Caution 46
- Do not hit or violently push the intelligent eye sensor this can lead to damage and malfunction 2 do not place large objects near the sensor also keep heating units or humidifiers outside the sensor s detection area 46
- Ed04 702 installation manual 46
- Indoor unit installation drawings 46
- Intelligent eye sensor ftxs ftks only 46
- Room air conditioners f series 45 46
- Boring a wall hole and installing wall embedded pipe 47
- For walls containing metal frame or metal board be sure to use a wall embedded pipe and wall cover in the feed through hole to prevent possible heat electrical shock or fire be sure to caulk the gaps around the pipes with caulking material to prevent water leakage 1 bore a feed through hole of 80mm in the wall so it has a down slope toward the outside 2 insert a wall pipe into the hole 3 insert a wall cover into wall pipe 4 after completing refrigerant piping wiring and drain piping caulk pipe hole gap with putty 47
- Indoor unit installation 1 47
- Installing the mounting plate 47
- Recommended mounting plate retention spots and dimensions 47
- The mounting plate should be installed on a wall which can support the weight of the indoor unit 1 temporarily secure the mounting plate to the wall make sure that the panel is completely level and mark the boring points on the wall 2 secure the mounting plate to the wall with screws 47
- 1 right side right back or right bottom piping 1 attach the drain hose to the underside of the refrigerant pipes with an adhesive vinyl tape 2 wrap the refrigerant pipes and drain hose together with an insulation tape 48
- 2 left side left back or left bottom piping 1 attach the drain hose to the underside of the refrigerant pipes with adhesive vinyl tape 48
- 3 wall embedded piping follow the instructions given under 48
- Be sure to connect the drain hose to the drain port in place of a drain plug 48
- Indoor unit installation 2 48
- Insert the drain hose to this depth so it won t be pulled out of the drain pipe 48
- Installing indoor unit 48
- No gap 48
- Open the front panel then open the service lid refer to installation tips 5 pass the inter unit wiring from the outdoor unit through the feed through wall hole and then through the back of the indoor unit pull them through the front side bend the ends of tie wires upward for easier work in advance if the inter unit wiring ends are to be stripped first bundle wire ends with adhesive tape 6 press the bottom frame of the indoor unit with both hands to set it on the mounting plate hooks make sure that the wires do not catch on the edge of the indoor unit 48
- Pass the drain hose and refrigerant pipes through the wall hole then set the indoor unit on the mounting plate hooks by using the markings at the top of the indoor unit as a guide 48
- Shape the refrigerant pipe along the pipe path marking on the mounting plate 4 pass drain hose and refrigerant pipes through the wall hole then set the indoor unit on mounting plate hooks using the markings at the top of indoor unit as a guide 5 pull in the inter unit wiring 6 connect the inter unit piping 7 wrap the refrigerant pipes and drain hose together with insulation tape as right figure in case of setting the drain hose through the back of the indoor unit 8 48
- Drain piping 49
- Indoor unit installation 3 49
- Warning 49
- When connecting to an ha system 49
- Wiring 49
- 1 caution on piping handling 1 protect the open end of the pipe against dust and moisture 2 all pipe bends should be as gentle as possible use a pipe bender for bending bending radius should be 30 to 40mm or larger 2 2 selection of copper and heat insulation materials 50
- 2 inch 1 2 inch 5 8 inch 1 4 inch 50
- 505 615kgf cm 630 770kgf cm 144 175kgf cm 50
- 60 71 80 90 class 50
- 60 71 80 90 classs 50
- 60 class 50
- 60 n m 49 60 n m 61 75 n m 14 17 n m 50
- 80 90 class 50
- Cut the pipe end with a pipe cutter 2 50
- Do not use mineral oil on flared part 2 prevent mineral oil from getting into the system as this would reduce the lifetime of the units 3 never use piping which has been used for previous installations only use parts which are delivered with the unit 4 do never install a drier to this r410a unit in order to guarantee it s lifetime 5 the drying material may dissolve and damage the system 6 incomplete flaring may cause refrigerant gas leakage 50
- Flare nut tightening torque 50
- Flaring 50
- Flaring the pipe end 50
- Gas side gas pipe thermal insulation 50
- Gas side gas side liquid side 50
- I d 14 16mm 50
- I d 16 20mm 50
- I d 8 10mm 50
- Insulation material polyethylene foam heat transfer rate 0 41 to 0 52w mk 0 35 to 0 45kcal mh c refrigerant gas pipe s surface temperature reaches 110 c max choose heat insulation materials that will withstand this temperature 2 be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below 50
- Liquid side liquid pipe thermal insulation 50
- O d 12 mm 50
- O d 15 mm 50
- O d 6 mm 50
- Put the flare nut on the pipe 4 flare the pipe 5 check that the flaring is properly made 50
- Refrigerant piping 50
- Refrigerant piping work 50
- Thickness 0 mm 50
- Thickness 1 mm 50
- Thickness 10mm min 50
- To prevent gas leakage apply refrigeration oil on both inner and outer surfaces of the flare use refrigeration oil for r410a 50
- Use separate thermal insulation pipes for gas and liquid refrigerant pipes 50
- Warning 50
- Test items 51
- Trial operation and testing 51
- Trial operation from remote controller 51
- Caution 52
- Outdoor units 52
- Safety precautions 52
- Warning 52
- Accessories 53
- Caution 53
- Precautions for selecting the location 53
- Precautions on installation 53
- Rks 50 60 71 f rxs 50 60 f 53
- Caution 54
- Ed04 702 installation manual 54
- Installation guidelines 54
- Outdoor unit installation drawings 54
- Room air conditioners f series 53 54
- Wall facing one side 54
- Walls facing three sides 54
- Walls facing two sides 54
- Where a wall or other obstacle is in the path of outdoor unit s intake or exhaust airflow follow the installation guidelines below for any of the below installation patterns the wall height on the exhaust side should be 1200mm or less 54
- Drain work 55
- Flaring the pipe end 55
- Installing outdoor unit 55
- Outdoor unit installation 1 55
- Refrigerant piping 55
- Warning 55
- Outdoor unit installation 2 56
- Purging air and checking gas leakage 56
- Warning 56
- 1 cautions on pipe handling 57
- Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below 57
- Before filling check whether the cylinder has a siphon attached or not 57
- Filling a cylinder with an attached siphon 57
- Filling other cylinders 57
- Forced operation switch 57
- Gas side liquid side gas pipe thermal insulation liquid pipe thermal insulation 57
- In order to protect the environment be sure to pump down when relocating or disposing of the unit 1 57
- It should have something like liquid filling siphon attached displayed on it 57
- O d 12 mm 57
- O d 6 mm i d 14 16mm i d 8 10mm 57
- Outdoor unit installation 3 57
- Pump down operation 57
- Refilling the refrigerant 57
- Refrigerant piping work 57
- Selection of copper and heat insulation materials 57
- Thickness 0 mm thickness 10mm min 57
- Caution 58
- Warning 58
- Wiring 58
- Test items 59
- Test run and final check 59
- Trial operation and testing 59
- Accessories 60
- Caution 60
- Precautions for selecting the location 60
- Precautions on installation 60
- Rxs 71 f 60
- Also insulate the connection on the outdoor unit 61
- Caution 61
- Clamping material 61
- Installation guidelines 61
- Installation manual ed04 702 61
- Insulation tube 61
- Outdoor unit installation drawings 61
- Room air conditioners f series 61
- Service lid tape 61
- Use tape or insulating material on all connections to prevent air from getting in between the copper piping and the insulation tube be sure to do this if the outdoor unit is installed above 61
- Where a wall or other obstacle is in the path of outdoor unit s intake or exhaust airflow follow the installation guidelines below for any of the below installation patterns the wall height on the exhaust side should be 1200mm or less 61
- Drain work 62
- Flaring the pipe end 62
- Installing outdoor unit 62
- Outdoor unit installation 1 62
- Refrigerant piping 62
- Warning 62
- Outdoor unit installation 2 63
- Purging air and checking gas leakage 63
- Warning 63
- 1 cautions on pipe handling 64
- 2 selection of copper and heat insulation materials 64
- All pipe bends should be as gentle as possible use a pipe bender for bending 64
- Before filling check whether the cylinder has a siphon attached or not 64
- Filling a cylinder with an attached siphon 64
- Filling other cylinders 64
- Gas side liquid side 64
- In order to protect the environment be sure to pump down when relocating or disposing of the unit 64
- It should have something like liquid filling siphon attached displayed on it 64
- O d 15 mm o d 6 mm i d 16 20mm i d 8 10mm 64
- Outdoor unit installation 3 64
- Pump down operation 64
- Refilling the refrigerant 64
- Refrigerant piping work 64
- Thickness 0 mm thickness 1 mm thickness 10mm min 64
- Caution 65
- Warning 65
- Wiring 65
- Test items 66
- Test run and final check 66
- Trial operation and testing 66
- Caution 67
- Operation manual 67
- Safety precautions 67
- Warning 67
- Consider nuisance to your neighbours from noises 68
- Electrical work 68
- Installation site 68
- System relocation 68
- Ftks 50 60 71 f 69
- Indoor unit 69
- Names of parts 69
- Outdoor unit 70
- Arc433b7 71
- Remote controller 71
- Attention 72
- Preparation before operation 72
- To set the batteries 72
- Attention 73
- Choose a place from where the signals reach the unit 73
- Place the remote controller in the remote controller holder 73
- Preparation before operation 73
- To fix the remote controller holder on the wall 73
- To operate the remote controller 73
- Be careful not to cool the room too much keeping the temperature setting at a moderate level helps save energy 74
- Clogged air filters cause inefficient operation and waste energy clean them once in about every two weeks 74
- Cover windows with a blind or a curtain blocking sunlight and air from outdoors increases the cooling effect 74
- If you are not going to use the air conditioner for a long period for example in spring or autumn turn the breaker off 74
- Operation outside this humidity or temperature range may cause a safety device to disable the system 74
- Please note 74
- Press clock button 74
- The air conditioner always consumes 15 35 watts of electricity even while it is not operating 74
- Tips for saving energy 74
- To set the clock 74
- Turn the breaker on 74
- Use the air conditioner in the following conditions 74
- Dry cool fan operation 75
- Press mode selector button and select a operation mode 75
- Press on off button 75
- Press on off button again 75
- Press temperature adjustment button 75
- To change the temperature setting 75
- To start operation 75
- To stop operation 75
- Press fan setting button 76
- To change the air flow rate setting 76
- Adjusting the air flow direction 77
- To adjust the horizontal blade flap 77
- To adjust the vertical blades louvers 77
- Notes on flap angle 78
- Notes on louvers angles 78
- Press either the swing button or the swing button 78
- Press the swing button and the swing button the and display will light up and the flap and louvers will move in turn 78
- To 3 d airflow 78
- To cancel 3 d airflow 78
- Powerful operation 79
- To cancel powerful operation 79
- To start powerful operation 79
- Outdoor unit quiet operation 80
- To cancel outdoor unit quiet operation 80
- To start outdoor unit quiet operation 80
- Before using home leave operation 81
- Home leave operation 81
- To cancel home leave operation 81
- To start home leave operation 81
- Use as a favorite mode 82
- Use as an energy saving mode 82
- Useful in these cases 82
- What s the home leave operation 82
- Intelligent eye operation 83
- Press sensor button 83
- Press sensor button again 83
- To cancel the intelligent eye operation 83
- To start intelligent eye operation 83
- Caution 84
- Intelligent eye is useful for energy saving 84
- Notes on intelligent eye 84
- Timer operation 85
- To cancel the off timer operation 85
- To use off timer operation 85
- Attention 86
- Press cancel button 86
- Press on timer button 86
- Press on timer button again 86
- Press timer setting button until the time setting reaches the point you like 86
- To cancel on timer operation 86
- To combine on timer and off timer 86
- To use on timer operation 86
- Attach the front panel 87
- Before cleaning be sure to stop the operation and turn the breaker off 87
- Care and cleaning 87
- Caution 87
- Clean the front panel 87
- Front panel 87
- Indoor unit outdoor unit and remote controller 87
- Open the front panel 87
- Remove the front panel 87
- Wipe them with dry soft cloth 87
- After washing shake off remaining water and dry in the shade 4 88
- Air filter 88
- Clean or replace each filter 88
- Filters 88
- If it is very dirty soak it for 10 to 15 minutes in water mixed with a neutral cleaning agent 88
- Maintenance 88
- Open the front panel page 24 2 pull out the air filters 88
- Remove dust with a vacuum cleaner and wash lightly with water 2 88
- Remove the tabs on the filter frame and replace with a new filter 88
- Replacement 88
- Set the air filter and the titanium apatite photocatalytic air purifying filter as they were and close the front panel 88
- Take off the titanium apatite photocatalytic air purifying filter 88
- Titanium apatite photocatalytic air purifying filter 88
- Wash the air filters with water or clean them with vacuum cleaner 88
- After operation stops turn off the breaker for the room air conditioner 89
- Before a long idle period 89
- Clean the air filters and set them again 89
- Dispose of old filters as non flammable waste 89
- Operate the fan only for several hours on a fine day to dry out the inside 89
- Press mode button and select fan operation 89
- Press on off button and start operation 89
- Take out batteries from the remote controller 89
- Titanium apatite photocatalytic air purifying filter without frame 1 set 89
- To order titanium apatite photocatalytic air purifying filter contact to the service shop there you bought the air conditioner 89
- Case explanation 90
- These cases are not troubles 90
- Trouble shooting 90
- Case check 91
- Check again 91
- Call the service shop immediately 92
- The power cord is abnormally hot or damaged an abnormal sound is heard during operation the safety breaker a fuse or the earth leakage breaker cuts off the operation frequently a switch or a button often fails to work properly there is a burning smell water leaks from the indoor unit 92
- Turn the breaker off and call the service shop 92
- Warning 92
- We recommend periodical maintenance 92
- Ftxs 50 60 71 f 93
- Indoor unit 93
- Names of parts 93
- 60 class 71 80 90 class 94
- Outdoor unit 94
- Arc433b70 7 95
- Remote controller 95
- Attention 96
- Preparation before operation 96
- To set the batteries 96
- Attention 97
- Choose a place from where the signals reach the unit 97
- Place the remote controller in the remote controller holder 97
- Preparation before operation 97
- To fix the remote controller holder on the wall 97
- To operate the remote controller 97
- Be careful not to cool heat the room too much keeping the temperature setting at a moderate level helps save energy 98
- Clogged air filters cause inefficient operation and waste energy clean them once in about every two weeks 98
- Cover windows with a blind or a curtain blocking sunlight and air from outdoors increases the cooling heating effect 98
- If you are not going to use the air conditioner for a long period for example in spring or autumn turn the breaker off 98
- Operation outside this humidity or temperature range may cause a safety device to disable the system 98
- Please note 98
- Press clock button 98
- The air conditioner always consumes 15 35 watts of electricity even while it is not operating 98
- Tips for saving energy 98
- To set the clock 98
- Turn the breaker on 98
- Use the air conditioner in the following conditions 98
- Auto dry cool heat fan operation 99
- Press mode selector button and select a operation mode 99
- Press on off button 99
- Press on off button again 99
- Press temperature adjustment button 99
- To change the temperature setting 99
- To start operation 99
- To stop operation 99
- Press fan setting button 100
- To change the air flow rate setting 100
- Adjusting the air flow direction 101
- To adjust the horizontal blade flap 101
- To adjust the vertical blades louvers 101
- Notes on flap angle 102
- Notes on louvers angles 102
- Press either the swing button or the swing button 102
- Press the swing button and the swing button the and display will light up and the flap and louvers will move in turn 102
- To 3 d airflow 102
- To cancel 3 d airflow 102
- Powerful operation 103
- To cancel powerful operation 103
- To start powerful operation 103
- Outdoor unit quiet operation 104
- To cancel outdoor unit quiet operation 104
- To start outdoor unit quiet operation 104
- Before using home leave operation 105
- Home leave operation 105
- To cancel home leave operation 105
- To start home leave operation 105
- Use as a favorite mode 106
- Use as an energy saving mode 106
- Useful in these cases 106
- What s the home leave operation 106
- Intelligent eye operation 107
- Press sensor button 107
- Press sensor button again 107
- To cancel the intelligent eye operation 107
- To start intelligent eye operation 107
- Caution 108
- Intelligent eye is useful for energy saving 108
- Notes on intelligent eye 108
- Timer operation 109
- To cancel the off timer operation 109
- To use off timer operation 109
- Attention 110
- Press cancel button 110
- Press on timer button 110
- Press on timer button again 110
- Press timer setting button until the time setting reaches the point you like 110
- To cancel on timer operation 110
- To combine on timer and off timer 110
- To use on timer operation 110
- Attach the front panel 111
- Before cleaning be sure to stop the operation and turn the breaker off 111
- Care and cleaning 111
- Caution 111
- Clean the front panel 111
- Front panel 111
- Indoor unit outdoor unit and remote controller 111
- Open the front panel 111
- Remove the front panel 111
- Wipe them with dry soft cloth 111
- After washing shake off remaining water and dry in the shade 4 since the material is made out of polyester do not wring out the filter when removing water from it 112
- Air filter 112
- Clean or replace each filter 112
- Filters 112
- If it is very dirty soak it for 10 to 15 minutes in water mixed with a neutral cleaning agent 112
- Maintenance 112
- Open the front panel page 24 2 pull out the air filters 112
- Remove dust with a vacuum cleaner and wash lightly with water 2 112
- Remove the tabs on the filter frame and replace with a new filter 112
- Replacement 112
- Set the air filter and the titanium apatite photocatalytic air purifying filter as they were and close the front panel 112
- Take off the titanium apatite photocatalytic air purifying filter 112
- Titanium apatite photocatalytic air purifying filter 112
- Wash the air filters with water or clean them with vacuum cleaner 112
- After operation stops turn off the breaker for the room air conditioner 113
- Before a long idle period 113
- Clean the air filters and set them again 113
- Dispose of old filters as non flammable waste 113
- Operate the fan only for several hours on a fine day to dry out the inside 113
- Press mode button and select fan operation 113
- Press on off button and start operation 113
- Take out batteries from the remote controller 113
- Titanium apatite photocatalytic air purifying filter without frame 1 set 113
- To order titanium apatite photocatalytic air purifying filter contact to the service shop there you bought the air conditioner 113
- Case explanation 114
- These cases are not troubles 114
- Trouble shooting 114
- Case check 115
- Check again 115
- Call the service shop immediately 116
- Disposal requirements 116
- The power cord is abnormally hot or damaged an abnormal sound is heard during operation the safety breaker a fuse or the earth leakage breaker cuts off the operation frequently a switch or a button often fails to work properly there is a burning smell water leaks from the indoor unit 116
- Turn the breaker off and call the service shop 116
- Warning 116
- We recommend periodical maintenance 116
- Option list 117
- Optional accessories 117
- Optional accessories ed04 702 117
- Room air conditioners f series 117
- Time clock and other devices obtained locally 117
- Wiring adaptor is also required for each indoor unit 117
- Ed04 702 optional accessories 118
- Field wiring 118
- Functions and features 118
- Installation manual 118
- Krp413a1s 118
- Room air conditioners f series 117 118
- Safety precautions 118
- Installation 119
- Krp413a1 119
- Krp413a1s krp413aa1s 119
- Optional accessories ed04 702 119
- Room air conditioners f series 119
- Automatic reset after power failure 120
- Connection with remote controller 120
- Ed04 702 optional accessories 120
- Room air conditioners f series 119 120
- Wiring 120
- Diagnostic check 121
- Is the air conditioner working properly are the connectors of the wiring properly connected are the remote controller and field wiring properly connected are all switch settings correct if there is nothing apparently wrong conduct a diagnostic check using the following procedure 121
- Optional accessories ed04 702 121
- Room air conditioners f series 121
- Switch settings and connection terminals 121
- Test operation and confirmation 121
- When the system is not working 121
- Binding band 122
- Component parts and separately sold parts which are required 122
- Ed04 702 optional accessories 122
- Fan operation cannot be selected from the central controller or wired remote controller 122
- Group control i e control of multiple indoor units with a single remote controller is not available 122
- Installation manual 122
- Krp928b2s 122
- Mounting screws 122
- Names of parts and electric wiring 122
- Overview features and compatible models 122
- Room air conditioners f series 121 122
- Safety precautions 122
- Combining equipment 123
- Optional accessories ed04 702 123
- P157704 2a 123
- Read operating error display signal 123
- Room air conditioners f series 123
- Switch settings 5 control codes 123
- Before installation 124
- Caution 124
- Ed04 702 optional accessories 124
- Installation of louvers 124
- Installation procedure 124
- Kpw945a4 124
- Room air conditioners f series 123 124
- Selection of installation location 124
- Space needed for installation 124
Похожие устройства
- Daikin RKS71FVM Сервис мануал
- Daikin RKS71GVMG Сервис мануал
- Daikin RKS50FVMA Сервис мануал
- Daikin RKS60FVMA Сервис мануал
- Daikin RKS71FVMA Сервис мануал
- Daikin RKS50FVLT Сервис мануал
- Daikin RKS60FVLT Сервис мануал
- Daikin RKS71FVLT Сервис мануал
- Daikin RXS50FVMA Технические данные
- Daikin RXS50FVMA Сервис мануал
- Daikin RXS60FVMA Технические данные
- Daikin RXS60FVMA Сервис мануал
- Daikin RXS71FVMA Технические данные
- Daikin RXS71FVMA Сервис мануал
- Daikin RXS80FVMA Сервис мануал
- Daikin RXS90FVMA Сервис мануал
- Daikin RXS50FVLT Сервис мануал
- Daikin RXS60FVLT Сервис мануал
- Daikin RXS71FVLT Сервис мануал
- Daikin CDKD25CVM Руководство по эксплуатации