INSTALLATION OF THE OUTDOOR UNIT
As condensing temperature rises, evaporating temperature rises and cooling capacity drops. In order to achieve maximum
cooling capacity, the location selected for outdoor unit should fulÞ ll the following requirements:
Install the condensing (outdoor) unit in a way such that the hot air distributed by the outdoor condensing unit cannot be
drawn in again (as in the case of short circuit of hot discharge air). Allow sufÞ cient space for maintenance around the
unit.
•
Ensure that there is no obstruction of air ß ow into or out of the unit. Remove obstacles which block air intake or
discharge.
The location must be well ventilated, so that the unit can draw in and distribute plenty of air thus lowering the
condensing temperature.
•
•
A place capable of bearing the weight of the outdoor unit and isolating noise and vibration.
A place protected from the direct sunlight. Otherwise use an awning for protection, if necessary.
•
•
The location must not be susceptible to dust or oil mist.•
! CAUTION
Do not install the unit at altitude over 2000m for both indoor and outdoor•
Содержание
- Installation manual 1
- R22 split series 1
- English 3
- Outline and dimensions 3
- Outline and dimensions 4
- English 5
- Installation manual 6
- Notice 6
- Safety precautions 6
- Warning caution 6
- English 7
- Indoor unit 7
- Installation diagram 7
- Outdoor unit 7
- Installation of the indoor unit 8
- Ceiling concealed drain piping work 9
- English 9
- Caution 10
- Installation of the outdoor unit 10
- All model a b c d 11
- English 11
- Gas pipe size mm in 11
- Installation clearance 11
- Liquid pipe size mm in 11
- Max allowable elevation m 11
- Max allowable length m 11
- Maximum pipe length 11
- Minimum distance mm 300 1000 300 500 11
- Model indoor 11
- Outdoor 11
- Outdoor units must be installed such that there is no short circuit of the hot discharge air or obstruction to smooth air ow select the coolest possible place where intake air should not be hotter than the outside temperature refer to operating range 11
- Refrigerant piping 11
- Remark for fdm60jev1k cooling unit recommended to add 6 kg external accumulator 11
- When the pipe length becomes too long both the capacity and reliability drop as the number of bends increases system piping resistance to the refrigerant ow increases thus lowering the cooling capacity as a result compressor reliability will be affected always choose the shortest path and follow the recommendation as tabulated below 11
- Piping connection to the units 12
- Piping works and flaring technique 12
- Electrical connection 13
- English 13
- English 15
- Charge operation 17
- English 17
- Vacuuming and charging 17
- Vacuuming the piping and the indoor unit 17
- Additional charge 18
- Special precautions when charging unit with scroll compressors 18
- Caution 19
- English 19
- Indicator lights 19
- Operating range 20
- Overall checking 20
- Phase protector optional 20
- Caution 21
- English 21
- Service and maintenance 21
- Troubleshooting 21
Похожие устройства
- Thorvik AIW12717 Инструкция по эксплуатации
- Thorvik AIW12717 Брошюра
- Thorvik AIW12122 Брошюра
- Thorvik AIW12122 Инструкция по эксплуатации
- Thorvik AIW12122 Деталировка
- Thorvik AIW3416M Брошюра
- Thorvik AIW3416M Инструкция по эксплуатации
- Thorvik AIWS125M Брошюра
- Thorvik AIWS125M Инструкция по эксплуатации
- Thorvik AIWS124M Брошюра
- Thorvik AIWS124M Инструкция по эксплуатации
- Thorvik AAG0510 Брошюра
- Thorvik AAG0510 Инструкция по эксплуатации
- Thorvik AOS6105 Брошюра
- Thorvik AOS6105 Инструкция по эксплуатации
- Thorvik ARW1261 Брошюра
- Thorvik ARW1261 Инструкция по эксплуатации
- Thorvik ARW3827 Брошюра
- Thorvik ARW3827 Инструкция по эксплуатации
- Thorvik RAD1018 Брошюра