9 ■English
Pump Down Operation
In order to protect the environment, be sure to pump down when relocating or disposing of the unit.
1) Remove the valve cap from liquid stop valve and gas stop valve.
2) Carry out forced cooling operation.
3) After five to ten minutes, close the liquid stop valve with a hexagonal wrench.
4) After two to three minutes, close the gas stop valve and stop forced cooling operation.
How to forced cooling operation mode
■ Using the indoor unit ON/OFF button
Press the indoor unit ON/OFF button for at least 5 seconds. (Operation will start.)
• Forced cooling operation will stop automatically after around 15 minutes.
To force a trial operation to stop, press the indoor unit ON/OFF button.
■ Using the main unit’s remote controller
1) Press the “ON/OFF” button. (Operation will start.)
2) Press the “TEMP”
button and the “MODE” button at the same time.
3) Press the “MODE” button twice.
(
“”
will be displayed and the unit will enter trial operation.)
4) Press the “MODE” button to return the operation mode to cooling.
• Trial operation will stop automatically after around 30 minutes. To force a trial
operation to stop, press the “ON/OFF” button.
■ Using the outdoor unit forced cooling operation switch (with standby
electricity saving function turned OFF)
1) Push on “ ” with a screwdriver. The unit will start operating.
2) The forced cooling mode is selected, and terminates in approx. 15 minutes.
CAUTION
1) When pressing the switch, do not touch the terminal block. It has a high voltage, so doing so may cause electric shock.
2) After closing the liquid stop valve, close the gas stop valve within three minutes, then stop the forced operation.
Facility Setting
(cooling at low outdoor temperature)
This function is limited only for facilities (the target of air conditioning is equipment (such as computer)). Never use it in
a residence or office (the space where there is a human).
1) Cutting jumper 4 (J4)
on the circuit board will expand the operation range down to –15°C. However it will stop if the outdoor
temperature drops below –20°C and start back up once the temperature rises again.
CAUTION
1) If the outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind, provide a windbreak wall.
2) Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off when using facility settings.
3) Do not place humidifiers or other items which might raise the humidity in rooms where facility settings are being used.
A humidifier might cause dew jumping from the indoor unit outlet vent.
4) Cutting jumper 4 (J4) sets the indoor fan tap to the highest position. Notify the user about this.
Gas
stop valve
Valve cap
Hexagonal
wrench
Close
Liquid
stop valve
1
2
3
The selective connector for standby electricity
saving in use (with standby electricity saving
function turned OFF)
Push here
Screwdriver
Power supply
terminal block
1
2
3
S70
S40
S2
S90
J5
J4
J3
Cut J4 with nippers
or a similar tools.
01_EN_3P203824-7E.fm Page 9 Saturday, October 24, 2009 3:57 PM
Содержание
- Installation manual 1
- Models 1
- R410a split series 1
- Rxg25j2v1b rxg35j2v1b 1
- Umeda center bldg 2 4 12 nakazaki nishi kita ku osaka 530 8323 japan 2
- Caution 3
- English 3
- Safety precautions 3
- Warning 3
- Accessories 4
- Accessories supplied with the outdoor unit 4
- Caution 4
- English 2 4
- Precautions for selecting the location 4
- Caution 5
- English 5
- Outdoor unit installation drawings 5
- Drain work 6
- English 4 6
- Installation guidelines 6
- Installing outdoor unit 6
- Outdoor unit installation 6
- Precautions on installation 6
- Caution 7
- Flaring the pipe end 7
- Outdoor unit installation 7
- Refrigerant piping 7
- Warning 7
- English 6 8
- Purging air and checking gas leakage 8
- Warning 8
- Important information regarding the refrigerant used 9
- Outdoor unit installation 9
- Refilling the refrigerant 9
- Refrigerant piping work 9
- Caution 10
- English 8 10
- Standby electricity saving 10
- The standby electricity saving function turns off power supply to the outdoor unit and sets the indoor unit into standby electricity saving mode thus educing the power consumption of the air conditioner 10
- Caution 11
- English 11
- Facility setting 11
- Facility setting cooling at low outdoor temperature 11
- How to forced cooling operation mode 11
- Pump down operation 11
- Caution 12
- English 10 12
- Good wrong 12
- Warning 12
- Wiring 12
- English 13
- Test items 13
- Test run and final check 13
- Trial operation and testing 13
- P203824 7e m09b216 14
Похожие устройства
- Daikin RXG35J2V1B Инструкция по монтажу
- Daikin RMXS112E8V1B Инструкция по монтажу
- Daikin RMXS140E8V1B Инструкция по монтажу
- Daikin RMXS112E8V1B Сервис мануал
- Daikin RMXS140E8V1B Сервис мануал
- Daikin RMXS160E8V1B Инструкция по монтажу
- Daikin RMXS160E8V1B Сервис мануал
- Daikin RMXS112E7V3B Инструкция по монтажу
- Daikin RMXS112E7V3B Сервис мануал
- Daikin RMXS140E7V3B Инструкция по монтажу
- Daikin RMXS140E7V3B Сервис мануал
- Daikin RMXS160E7V3B Инструкция по монтажу
- Daikin RMXS160E7V3B Сервис мануал
- Daikin RMXS160EV1A Технические данные
- Daikin RMXS112EV1A Технические данные
- Daikin RMXS140EV1A Технические данные
- Daikin FCQ71DV3B Технические данные
- Daikin FCQ71DV3B Инструкция по эксплуатации
- Daikin FCQ71DV3B Инструкция по монтажу
- Daikin FCQ71DV3B Сервис мануал