Outdoor Unit Installation
6.
Refilling the refrigerant.
Check the type of refrigerant to be used on the machine nameplate.
Precautions when adding R410A
Fill from the liquid pipe in liquid form.
It is a mixed refrigerant, so adding it in gas form may cause the refrigerant composition to change, preventing normal operation.
1) Before filling, check whether the cylinder has a siphon attached or not. (It should have something like “liquid filling siphon
attached” displayed on it.)
• Be sure to use the R410A tools to ensure pressure and to prevent foreign objects entering.
NOTE
National implementation of EU regulation on certain fluorinated greenhouse gases may require to provide the appropriate official
national language on the unit. Therefor an additional multilingual fluorinated greenhouse gases label is supplied with the unit.
Sticking instructions are illustrated on the backside of that label.
7.
Refrigerant piping work.
7-1 Cautions on pipe handling.
1) Protect the open end of the pipe against dust and moisture.
2) All pipe bends should be as gentle as possible. Use a pipe bender
for bending.
7-2 Selection of copper and heat insulation materials.
When using commercial copper pipes and fittings, observe the following:
1) Insulation material: Polyethylene foam
Heat transfer rate: 0.041 to 0.052W/mK (0.035 to 0.045kcal/(mh •°C))
Refrigerant gas pipe’s surface temperature reaches 110°C max.
Choose heat insulation materials that will withstand this temperature.
2) Be sure to insulate both the gas and liquid piping and to provide insulation
dimensions as below.
3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.
Gas side Liquid side
Gas pipe
thermal insulation
Liquid pipe
thermal insulation
O.D. 9.5mm O.D. 6.4mm I.D. 12-15mm I.D. 8-10mm
Minimum bend radius Thickness 10mm Min.
30mm or more
Thickness 0.8mm (C1220T-O)
Filling a cylinder with an attached siphon
Stand the cylinder upright when
filling.
There is a siphon pipe inside, so the
cylinder need not be upside-down to
fill with liquid.
Filling other cylinders
Turn the cylinder upside-down
when filling.
3
5
6
2
1
4
Please fill in with indelible ink,
n
1
the factory refrigerant charge of the product,
n
2
the additional refrigerant amount charged in the field and
n
1 + 2
the total refrigerant charge
on the refrigerant charge label supplied with the product.
Important information regarding the refrigerant used
This product contains fluorinated greenhouse gases covered by
the Kyoto Protocol. Do not vent gases into the atmosphere.
Refrigerant type:
R410A
GWP
(1)
value: 1975
(1)
GWP = global warming potential
1 factory refrigerant charge of the
product:
see unit name plate
2 additional refrigerant amount
charged in the field
3 total refrigerant charge
4 Contains fluorinated greenhouse
gases covered by the Kyoto
Protocol
5 outdoor unit
6 refrigerant cylinder and manifold
for charging
The filled out label must be adhered in the
proximity of the product charging port (e.g.
onto the inside of the stop valve cover).
Wall
If no flare cap is
available, cover
the flare mouth
with tape to keep
dirt or water out.
Be sure to
place a cap.
Rain
Gas pipe
Liquid pipe
Gas pipe
insulation
Liquid pipe
insulation
Finishing tape
Drain hose
Inter-unit wiring
01_EN_3P203824-7E.fm Page 7 Saturday, October 24, 2009 3:57 PM
Содержание
- Installation manual 1
- Models 1
- R410a split series 1
- Rxg25j2v1b rxg35j2v1b 1
- Umeda center bldg 2 4 12 nakazaki nishi kita ku osaka 530 8323 japan 2
- Caution 3
- English 3
- Safety precautions 3
- Warning 3
- Accessories 4
- Accessories supplied with the outdoor unit 4
- Caution 4
- English 2 4
- Precautions for selecting the location 4
- Caution 5
- English 5
- Outdoor unit installation drawings 5
- Drain work 6
- English 4 6
- Installation guidelines 6
- Installing outdoor unit 6
- Outdoor unit installation 6
- Precautions on installation 6
- Caution 7
- Flaring the pipe end 7
- Outdoor unit installation 7
- Refrigerant piping 7
- Warning 7
- English 6 8
- Purging air and checking gas leakage 8
- Warning 8
- Important information regarding the refrigerant used 9
- Outdoor unit installation 9
- Refilling the refrigerant 9
- Refrigerant piping work 9
- Caution 10
- English 8 10
- Standby electricity saving 10
- The standby electricity saving function turns off power supply to the outdoor unit and sets the indoor unit into standby electricity saving mode thus educing the power consumption of the air conditioner 10
- Caution 11
- English 11
- Facility setting 11
- Facility setting cooling at low outdoor temperature 11
- How to forced cooling operation mode 11
- Pump down operation 11
- Caution 12
- English 10 12
- Good wrong 12
- Warning 12
- Wiring 12
- English 13
- Test items 13
- Test run and final check 13
- Trial operation and testing 13
- P203824 7e m09b216 14
Похожие устройства
- Daikin RXG35J2V1B Инструкция по монтажу
- Daikin RMXS112E8V1B Инструкция по монтажу
- Daikin RMXS140E8V1B Инструкция по монтажу
- Daikin RMXS112E8V1B Сервис мануал
- Daikin RMXS140E8V1B Сервис мануал
- Daikin RMXS160E8V1B Инструкция по монтажу
- Daikin RMXS160E8V1B Сервис мануал
- Daikin RMXS112E7V3B Инструкция по монтажу
- Daikin RMXS112E7V3B Сервис мануал
- Daikin RMXS140E7V3B Инструкция по монтажу
- Daikin RMXS140E7V3B Сервис мануал
- Daikin RMXS160E7V3B Инструкция по монтажу
- Daikin RMXS160E7V3B Сервис мануал
- Daikin RMXS160EV1A Технические данные
- Daikin RMXS112EV1A Технические данные
- Daikin RMXS140EV1A Технические данные
- Daikin FCQ71DV3B Технические данные
- Daikin FCQ71DV3B Инструкция по эксплуатации
- Daikin FCQ71DV3B Инструкция по монтажу
- Daikin FCQ71DV3B Сервис мануал