4 x Initial start-up
Operating instructions
32
Daikin Control unit
RoCon mb
008.1446899_00 – 07/2019 – EN
If several control units are incorporated in the RoCon system of a
heating installation, additional parameter settings are relevant for
this and can be used to set the individual functions and parame
-
ters using the appropriate authorisations.
For the EHS157034 room station
– [RoCon U1 assign] parameter:
– The setting = "Living Room" can be used to influence the
heating circuit defined by the set heating circuit ID.
– The setting = "Mixing Valve" can be used to carry out all
the settings for the mixer circuit defined by the set heating
circuit ID.
– [Master-RoCon] parameter:
If the heating circuit ID is set for the direct heating circuit of a
Daikin Altherma M ECH
2
O, the setting = "On" can be used to
activate the master RoCon function. In addition to the heating
circuit functions, the hot water functions of the Daikin
Altherma M ECH
2
O can also be operated with this room sta-
tion.
Activation of the master RoCon function can also be used for
heating systems that consist only of a DaikinAltherma M
ECH
2
O (without heating circuit extension) and a room station,
and which are to be operated primarily via the room station
(observe following information).
If the master RoCon function is activated, the oper-
ating mode of the heat generator is set via the room
station, and this is shown on the display.
The settings on the room station are transferred to the heat
generator, but not vice versa. The room station has priority.
If the [Summer] operating mode is set, for example, and sub-
sequently, on the Daikin Altherma M ECH
2
O control panel,
the [Heating] operating mode is set, no heating circuit
requirement is generated, because the direct heating circuit
assigned to the room station via the heating circuit ID is still
in [Summer] operating mode. The change in operating mode
must therefore be carried out at the room station.
On heating systems with heating circuit extensions, we rec-
ommend not activating the master RoCon function (setting =
"Off") and instead using the terminal function.
For all RoCon B1 and EHS157034 control units
– [Terminaladress] parameter:
As soon as a control panel has been assigned with a terminal
ID (all settings except "Off"), the control panel can be used to
activate the terminal function.
After carrying out the [Bus - Scan], all the system components
integrated in the RoCon system can be remotely controlled
using a valid device ID (caretaker authorisation).
If the terminal function is to be used in the heating system, the
terminal ID = 0 must be allocated to a control unit.
4.2 Operating Support during 1st.
Commissioning and during System
Extensions
When a Daikin Altherma M ECH
2
O or a EHS157034 room station
is switched on for the first time, setting the user language is nor-
mally offered first.
Then, on the Daikin Altherma M ECH
2
O you will be asked "Use
Standard Config?". This query can normally be answered with
"Yes".
Only in special applications (e.g. several heat generators in the
RoCon system) should the answer be "No". In this case, the
"Basic Configuration" parameter level will be offered in order to
set the necessary adaptations (see tab. 6-14).
In the case of the EHS157034 room station, after setting the user
language, the "Setup Wizard" installation menu appears.
Setup Wizard
Fig. 4-1 "Setup Wizard" display
The items for defining the function, the authorisation and the IDs
of the room station in the RoCon system are requested and
checked for plausibility.
This prevents duplicate device and terminal IDs being set.
Therefore, it is recommended that you use this installation menu
when extending or making changes to the RoCon system of the
heating installation. To do this, a room station already integrated
in the heating installation must first be reset.
1. Enter the technician code (see chap. 3.6.1).
2. Push the Exit button for at least 5 s.
Menu "Special Level" is displayed.
3. Use the rotary button to select the "RoCon B1/U1 Reset"
program.
4. Execute the program by briefly pressing on the rotary button.
The "Setup Wizard" installation menu starts.
Device ID
Unique numbering of a heat genera-
tor or mixer module in the RoCon sys-
tem.
Up to 16 device numbers can be allo-
cated.
These device numbers are detected
during a [Bus - Scan] and are dis-
played for identification of a remotely
controlled device.
Daikin Altherma M ECH
2
O
(RoCon BM1)
[BUS ID HS]
See tab. 6-14
Identical to heat generator detection.
The value must not be the same as the
heating circuit ID of a mixer module in the
RoCon system.
EHS157068 mixer module [HC Assignment]
See tab. 6-15
Identical to the heating circuit ID.
The value must not be the same as the
heat generator ID of a Daikin Altherma M
ECH
2
O in the RoCon system.
The value must be the same as the setting
of the address switch (fig. 4-2).
Tab. 4-1 Functional IDs in the RoCon system
1) A maximum of 8 heat generators can be connected in the RoCon system via the CAN data bus. Several heat generators integrated in the heating installation must
be regarded as a special application. If necessary contact a Daikin service technician.
ID / Function System components Parameters Comments
Содержание
- Control unit rocon mb ehs157034 ehs157068 1
- Ekhwmx300c ekhwmxb300c ekhwmx500c ekhwmxb500c 1
- Electronic controller for heat pumps 1
- Operating instructions 1
- After first commissioning after successful basic configuration 37 2
- Avoiding danger 5 2
- Basic functions and operating modes 10 2
- Commissioning daikin altherma m ec 2
- Ehs157068 mixer module 51 2
- Emergency operation 56 2
- Errors malfunctions and messages 55 2
- Explanation of the parameter tables 40 2
- For first commissioning or resetting to factory settings 36 2
- Fundamental aspects of the ids and authorisations in the rocon system 31 2
- General 7 2
- Initial start up 31 2
- List of contents 2
- Operating concept 9 2
- Operating support during 1st commissioning and during system extensions 32 2
- Operation 7 2
- Parameter levels for the ehs157068 mixer module 38 2
- Parameter overview 36 2
- Parameter settings 40 2
- Product description 6 2
- Putting optional rocon system components into operation 33 2
- Recognising errors correcting malfunctions 55 2
- Refer to the manual 4 2
- Rotary switch setting configuration 40 2
- Rotary switch setting dhw install 47 2
- Rotary switch setting dhw set temp 48 2
- Rotary switch setting info 49 6 1 exit key special function 50 6 2 basic configuration parameter level 51 6 3 parameter levels of the 2
- Rotary switch setting operating mode 48 2
- Rotary switch setting remote param 49 2
- Rotary switch setting set temp day 48 2
- Rotary switch setting set temp night 48 2
- Rotary switch setting time program 49 2
- Safety 4 2
- Special functions 20 2
- Special system settings 21 2
- Use as intended 5 2
- Warning signs and explanation of symbols 4 2
- Glossary 7 3
- List of contents 3
- List of keywords 3 3
- Notes 8 3
- X safety 4
- X safety 5
- Product description 6
- X product description 6
- Danger 7
- Display 7
- Display and operating elements 7
- General 7
- If electrical components come into contact with water this can cause an electric shock as well as cause potentially fatal burns or injuries 7
- Maximum energy exploitation 7
- Operation 7
- The displays and the keys of the control unit must be protected against the effects of moisture to clean the control unit use a dry cotton cloth using aggressive cleaning agents and other fluids can cause damage to devices or lead to an electric shock 7
- X operation 7
- Caution 8
- Controls 8
- Explanation of symbols 8
- Never operate the operating elements of the control unit with a hard pointed object this can cause damage and can cause the control to malfunction 8
- Rotary switch 8
- X operation 8
- Exit key 9
- Operating concept 9
- Rotary button 9
- X operation 9
- Automatic defrost function 10
- Basic functions and operating modes 10
- Keylock 10
- System information info 10
- X operation 10
- Displaying the operating data overview 11
- X operation 11
- A heating system that is not protected against frost can freeze in the event of frost and thus be damaged 12
- Add glycol to the heating water circuit see installation and maintenance instructions alternatively drain the heating system on the water side if there is a danger of frost if the heating system is not drained the power supply must be ensured and the external main switch must remain switched on if there is a danger of frost 12
- Caution 12
- Displaying the water pressure 12
- Operating mode standby stand by 12
- Setting the operating mode 12
- X operation 12
- Heating cooling 13
- Operating mode automatic 1 time program 13
- Operating mode automatic 2 time program 13
- Operating mode reducing 13
- Operating mode summer 13
- X operation 13
- Setting 14
- Switching time program 14
- Temperature setting of daytime room temperature 14
- Temperature setting of hot water generation 14
- Temperature setting of setback mode 14
- Unscheduled hot water preparation 14
- X operation 14
- Permanent time programs 15
- X operation 15
- Temporary time programs 16
- X operation 16
- Setting the lcd display language date time 17
- System settings 17
- Terminal function 17
- X operation 17
- Activating deactivating terminal operation 18
- Activating deactivating whisper mode 18
- Caution 18
- During active whisper mode the output in room heating and room cooling mode decreases such that it may no longer be possible to achieve pre set target temperature values 18
- Operation with glycol 18
- Whisper mode 18
- With outside temperatures below freezing there is a risk of material damage caused by frost 18
- X operation 18
- Activating deactivating emergency automatic operation 19
- Due to such forced charging the target hot water temperature in the hot water storage tank can exceed 60 c 19
- Ehs emergency operation 19
- Install scald protection in the hot water distri bution line e g vta32 screw set 1 19
- Smart grid sg 19
- There is a danger of scalding at target hot water temperatures over 60 c this is possible as the utility company evu is entitled to control current draw optimised according to supply and demand in the definitions for smart grid 19
- This storage tank charging is carried out even when standby operating mode is set 19
- Warning 19
- X operation 19
- 3 way switching valves reference travel 20
- Manual operation 20
- Special functions 20
- X operation 20
- Access rights technician code 21
- Caution risk of overheating of floor heating 21
- Expert 21
- Heat slope 21
- In the event of malfunction or during manual operation the floor heating the screed or the floor structure could be damaged due to over heating 21
- O is switched to standby or summer operating mode see chap 3 with parameter room thermostat on or parameter interlink fct on the overheating protection switch must be connected so that the room thermostat s switching contact is interrupted if the floor heating is also used for room cooling the connection notes in the above point also apply to the connection of a moisture protection switch in the building 21
- Prior to initial commissioning of the floor heating system set the maximum temper ature limit in the rocon mb controller parameter t vbh1 max and the maximum permissible system temperature parameter max t flow connect an overheating protection switch in the building at the ext plug connection to external operating mode switch over so that the daikin altherma m ec 21
- Special system settings 21
- X operation 21
- Caution risk of condensation 22
- Cooling slope 22
- In the event of malfunction or incorrect parame ter settings the floor heating the screed or the floor structure could be damaged due to con densation 22
- Manually adjusting the heat slope 22
- Prior to initial commissioning and activation of cooling mode set the minimum temper ature limit to the minimum permissible system temperature in the rocon mb controller parameter min t flow cooling 22
- X operation 22
- Frost protection function 23
- Weather dependent t hs control 23
- With connected mixer module 23
- X operation 23
- Additional alternative heat generator 24
- Caution 24
- Interlink function 24
- Limit target feed temperatures to suitable temperature ranges design heat distribution areas with different design temperatures as hydraulically separate heating circuits if necessary design heating circuits with lim ited target feed temperatures as mixer cir cuits and regulate with a mixer module 24
- Unsuitable feed temperatures can cause dam age to the floor heating system or dew formation on cooling surfaces 24
- X operation 24
- Air purge 25
- Heating support 25
- Special function switching contacts 25
- X operation 25
- Anti legionella system 26
- Install scald protection in the hot water distri bution line e g vta32 screw set 1 26
- Option 1 26
- Option 2 26
- Option 3 26
- Resetting to factory settings reset 26
- There is a danger of scalding at target hot water temperatures over 60 c this is possible when using solar energy if the legionella protection or smart grid functions are activated or the target hot water temperature is set higher than 60 c 26
- Warning 26
- X operation 26
- Function heating 27
- Screed curing heating 27
- Screed program 27
- X operation 27
- Setting and starting the screed program 28
- X operation 28
- Defining the switching time program for the circulation pump 29
- Relay test 29
- Settings for optional circulation pump 29
- X operation 29
- Remote control via internet 30
- X operation 30
- Fundamental aspects of the ids and authorisations in the rocon system 31
- Initial start up 31
- X initial start up 31
- For all rocon b1 and ehs157034 control units 32
- For the ehs157034 room station 32
- Operating support during 1st commissioning and during system extensions 32
- X initial start up 32
- Assigning the terminal id on the rocon b1 control panel of the daikin altherma m ec 33
- Commissioning daikin altherma m ec 33
- Mixer module ehs157068 33
- Putting optional rocon system components into operation 33
- X initial start up 33
- A configuration for the living room setting 34
- B configuration for mixing valve setting 34
- Ehs157034 room station 34
- Sequence for initial commissioning see also chap 4 34
- X initial start up 34
- Allocating the ehs157068 mixing module to a heat generator 35
- Caretaker function 35
- Master rocon function 35
- X initial start up 35
- During initial commissioning after resetting to factory settings 36
- For first commissioning or resetting to factory settings 36
- Parameter overview 36
- X parameter overview 36
- After first commissioning after successful basic configuration 37
- Rotary switch setting configuration 37
- X parameter overview 37
- Exit key special function 38
- No function 38
- Parameter levels for the ehs157068 mixer module 38
- Rotary switch setting dhw install 38
- Rotary switch setting dhw set temp 38
- Rotary switch setting info 38
- Rotary switch setting operating mode 38
- Rotary switch setting remote param 38
- Rotary switch setting set temp day 38
- Rotary switch setting set temp night 38
- Rotary switch setting time program 38
- See chap 5 38
- X parameter overview 38
- Rotary switch setting configuration 39
- Rotary switch setting remote param 39
- Rotary switch setting time program 39
- See chap 5 39
- Tab 5 12 parameters in the configuration rotary switch setting 39
- X parameter overview 39
- Explanation of the parameter tables 40
- Parameter settings 40
- Rotary switch setting configuration 40
- Setup level 40
- X parameter settings 40
- X parameter settings 41
- X parameter settings 42
- Tab 6 1 parameters in the configuration rotary switch setting setup level 43
- X parameter settings 43
- System configuration level 44
- X parameter settings 44
- Depending on the version individual information pa rameters are displayed that are not described in tab 6 2 for this see tab 6 12 45
- Hc configuration level 45
- Tab 6 2 parameters in the configuration rotary switch setting system configuration level 45
- X parameter settings 45
- X parameter settings 46
- Dhw configuration level 47
- Rotary switch setting dhw install 47
- X parameter settings 47
- Rotary switch setting dhw set temp 48
- Rotary switch setting operating mode 48
- Rotary switch setting set temp day 48
- Rotary switch setting set temp night 48
- Tab 6 6 parameters in the operating mode rotary switch setting 48
- Tab 6 7 parameters in the set temp day rotary switch setting 48
- Tab 6 8 parameters in the set temp night rotary switch setting 48
- Tab 6 9 parameters in the dhw set temp rotary switch setting 48
- X parameter settings 48
- Rotary switch setting info 49
- Rotary switch setting remote param 49
- Rotary switch setting time program 49
- Tab 6 10 parameters in the time program rotary switch setting 49
- Tab 6 11 parameters in the remote param rotary switch setting 49
- X parameter settings 49
- Exit key special function 50
- Tab 6 12 parameters in the info rotary switch setting 50
- Tab 6 13 parameters at the special level level 50
- To enter press the exit button for at least 5 s 50
- X parameter settings 50
- After the system config parameter has been set to inactive or delete in the configuration rotary switch setting setup level 51
- An unlimited scope of available parameters exists at the indi vidual levels 51
- Basic configuration parameter level 51
- No function 51
- On setting a control panel to mix valve x terminal function the displayed values refer to the components pump mix valve connected to the ehs157068 of the mixer circuit assigned via the device id 51
- On setting a ehs157034 room station assigned to the mixer module via the heating circuit id to living room the parameter t room adj is available the target room temperature can be changed in the range 5 k to 5 k with the rotary button this function is not available if the ehs157034 is used as a remote control in terminal function 51
- Only the corresponding sections are referred to below signif icant differences are explained in more detail 51
- Parameter levels of the ehs157068 mixer module 51
- Rotary switch setting configuration 51
- Rotary switch setting dhw install 51
- Rotary switch setting dhw set temp 51
- Rotary switch setting info 51
- Rotary switch setting operating mode 51
- Rotary switch setting remote param 51
- Rotary switch setting set temp day 51
- Rotary switch setting set temp night 51
- Rotary switch setting time program 51
- See chap 6 51
- See chap 6 0 51
- See chap 6 3 and 6 3 51
- The parameter levels parameter meanings setting ranges and connected functions are basically described in the same way as in the previous sections 51
- This parameter level only appears during initial commissioning if the answer selected for the use standard config prompt was no or 51
- X parameter settings 51
- Rotary switch setting configuration setup level 52
- Tab 6 15 parameters in the configuration rotary switch setting setup level 52
- X parameter settings 52
- Rotary switch setting configuration mixer config level 53
- X parameter settings 53
- Tab 6 16 parameters in the configuration rotary switch setting mixer config level 54
- X parameter settings 54
- Caution 55
- Electrostatic charges can lead to voltage arcing that can destroy the electronic components 55
- Errors malfunctions and messages 55
- Recognising errors correcting malfunctions 55
- Secure potential equalisation before touching electronic parts e g by touching an earthed metallic part 55
- X errors malfunctions and messages 55
- Ehs emergency operation 56
- Emergency operation 56
- Malfunctions and fault codes 56
- X errors malfunctions and messages 56
- Glossary 57
- X glossary 57
- Switching time program 58
- User specific settings 58
- X notes 58
- Circulation time 59
- Enter the parameter changes you have made in the following table and in the daikin altherma m ec 59
- Ids in the rocon can bus system 59
- O operating manual 59
- Parameters 59
- Rocon device id comments 59
- X notes 59
- Other items 60
- X notes 60
- X notes 61
- X notes 62
- List of keywords 63
- X list of keywords 63
Похожие устройства
- Daikin EKHWMXB500CA Инструкция по монтажу
- Daikin RKHWMX300C Инструкция по эксплуатации
- Daikin RKHWMX300C Инструкция по монтажу
- Daikin RKHWMX500C Инструкция по эксплуатации
- Daikin RKHWMX500C Инструкция по монтажу
- Daikin RKHWMXB300C Инструкция по монтажу
- Daikin RKHWMXB300C Инструкция по эксплуатации
- Daikin RKHWMXB500C Инструкция по эксплуатации
- Daikin RKHWMXB500C Инструкция по монтажу
- Daikin RKHW16MX500C Инструкция по эксплуатации
- Daikin RKHW16MX500C Инструкция по монтажу
- Daikin RKHW16MXB500C Инструкция по эксплуатации
- Daikin RKHW16MXB500C Инструкция по монтажу
- Daikin EKHWP300B Схема
- Daikin EKHWP300B Инструкция по эксплуатации
- Daikin EKHWP300B Руководство по эксплуатации
- Daikin EKHWP54419BA Схема
- Daikin EKHWP54419BA Инструкция по эксплуатации
- Daikin EKHWP54419BA Руководство по эксплуатации
- Daikin EKHWP500B Схема