4 x Initial start-up
Operating instructions
32
Daikin Control unit
RoCon mb
008.1446899_00 – 07/2019 – EN
If several control units are incorporated in the RoCon system of a
heating installation, additional parameter settings are relevant for
this and can be used to set the individual functions and parame
-
ters using the appropriate authorisations.
For the EHS157034 room station
[RoCon U1 assign] parameter:
The setting = "Living Room" can be used to influence the
heating circuit defined by the set heating circuit ID.
The setting = "Mixing Valve" can be used to carry out all
the settings for the mixer circuit defined by the set heating
circuit ID.
[Master-RoCon] parameter:
If the heating circuit ID is set for the direct heating circuit of a
Daikin Altherma M ECH
2
O, the setting = "On" can be used to
activate the master RoCon function. In addition to the heating
circuit functions, the hot water functions of the Daikin
Altherma M ECH
2
O can also be operated with this room sta-
tion.
Activation of the master RoCon function can also be used for
heating systems that consist only of a DaikinAltherma M
ECH
2
O (without heating circuit extension) and a room station,
and which are to be operated primarily via the room station
(observe following information).
If the master RoCon function is activated, the oper-
ating mode of the heat generator is set via the room
station, and this is shown on the display.
The settings on the room station are transferred to the heat
generator, but not vice versa. The room station has priority.
If the [Summer] operating mode is set, for example, and sub-
sequently, on the Daikin Altherma M ECH
2
O control panel,
the [Heating] operating mode is set, no heating circuit
requirement is generated, because the direct heating circuit
assigned to the room station via the heating circuit ID is still
in [Summer] operating mode. The change in operating mode
must therefore be carried out at the room station.
On heating systems with heating circuit extensions, we rec-
ommend not activating the master RoCon function (setting =
"Off") and instead using the terminal function.
For all RoCon B1 and EHS157034 control units
[Terminaladress] parameter:
As soon as a control panel has been assigned with a terminal
ID (all settings except "Off"), the control panel can be used to
activate the terminal function.
After carrying out the [Bus - Scan], all the system components
integrated in the RoCon system can be remotely controlled
using a valid device ID (caretaker authorisation).
If the terminal function is to be used in the heating system, the
terminal ID = 0 must be allocated to a control unit.
4.2 Operating Support during 1st.
Commissioning and during System
Extensions
When a Daikin Altherma M ECH
2
O or a EHS157034 room station
is switched on for the first time, setting the user language is nor-
mally offered first.
Then, on the Daikin Altherma M ECH
2
O you will be asked "Use
Standard Config?". This query can normally be answered with
"Yes".
Only in special applications (e.g. several heat generators in the
RoCon system) should the answer be "No". In this case, the
"Basic Configuration" parameter level will be offered in order to
set the necessary adaptations (see tab. 6-14).
In the case of the EHS157034 room station, after setting the user
language, the "Setup Wizard" installation menu appears.
Setup Wizard
Fig. 4-1 "Setup Wizard" display
The items for defining the function, the authorisation and the IDs
of the room station in the RoCon system are requested and
checked for plausibility.
This prevents duplicate device and terminal IDs being set.
Therefore, it is recommended that you use this installation menu
when extending or making changes to the RoCon system of the
heating installation. To do this, a room station already integrated
in the heating installation must first be reset.
1. Enter the technician code (see chap. 3.6.1).
2. Push the Exit button for at least 5 s.
Menu "Special Level" is displayed.
3. Use the rotary button to select the "RoCon B1/U1 Reset"
program.
4. Execute the program by briefly pressing on the rotary button.
The "Setup Wizard" installation menu starts.
Device ID
Unique numbering of a heat genera-
tor or mixer module in the RoCon sys-
tem.
Up to 16 device numbers can be allo-
cated.
These device numbers are detected
during a [Bus - Scan] and are dis-
played for identification of a remotely
controlled device.
Daikin Altherma M ECH
2
O
(RoCon BM1)
[BUS ID HS]
See tab. 6-14
Identical to heat generator detection.
The value must not be the same as the
heating circuit ID of a mixer module in the
RoCon system.
EHS157068 mixer module [HC Assignment]
See tab. 6-15
Identical to the heating circuit ID.
The value must not be the same as the
heat generator ID of a Daikin Altherma M
ECH
2
O in the RoCon system.
The value must be the same as the setting
of the address switch (fig. 4-2).
Tab. 4-1 Functional IDs in the RoCon system
1) A maximum of 8 heat generators can be connected in the RoCon system via the CAN data bus. Several heat generators integrated in the heating installation must
be regarded as a special application. If necessary contact a Daikin service technician.
ID / Function System components Parameters Comments