6 x Parameter settings
Operating instructions
40
Daikin Control unit
RoCon mb
008.1446899_00 – 07/2019 – EN
6 Parameter settings
6.1 Explanation of the parameter tables
The parameter tables listed in Chaps. 6.2 to 6.11 include
compact information on all parameters, which is available in the
respective rotary switch setting on the control unit (1st menu
level, 2nd menu level).
In addition to the parameter designations, the tables contain de-
tails of the setting ranges, factory settings, setting options or
setting step distances and brief function explanations.
In addition, they provide explanation of the access rights for op-
eration of the control unit. The following abbreviations are used
for corresponding labelling:
BE Access right for the operator
HF Access authorisation with technician code
In the event of different information in the BE and HF
columns, login as a heating technician must be carried
out prior to selecting the parameter level in order to
obtain the status entered in the HF column (see
chap. 3.6.1).
Status:
N Not visible
E Visible and configurable
S Visible
Changing some parameters requires a restart of the
device. This takes a few minutes. No further settings
can be made during this time. The restart can be de-
layed by 5 minutes in response to the prompt "Restart
required. Perform now?" by selecting "later".
Parameters that require a restart are marked with (*) in the fol-
lowing tables.
6.2 Rotary switch setting: Configuration
6.2.1 "Setup" level
Sub-
level
Parameters Description Access Setting range
Min / Max
Factory
setting
Incre-
ment
BE HF
LCD Brightness Brightness of the display E E 0 - 100 % 50 % 10 %
LCD Illum Time Lighting duration of the display E E 5 - 120 s 30 s 1 s
Language National language of the display texts on the control unit E E German
English
French
Dutch
Italian
Spanish
Portuguese
German -
Date Current date in day/month/year format. The current day of the week is calculated auto-
matically from the date.
E E
Time Time in hours/minutes format. E E
Keylock Function Release of the key lock function:
Off: Key lock cannot be activated.
On: Key lock can be activated with the rotary button (see chap. 3.3).
E E Off
On
Off -
Access Rights Access code entry. Setting digit-by-digit like a combination lock (see chap. 3.6.1). E E 0 - 9 0000 1
RoCon U1 assign Display only on connected
room station:
Function of the EHS157034 room station in the CAN data bus system:
Living Room: Control unit for the heating circuit allocated in the [HC Assignment] param-
eter.
Mixing Valve: Mixer circuit operating unit (as mixer circuit extension or as a free-standing
mixer circuit control unit)
In addition to the above functions, the room station can basically be used as a remote
control unit for the Daikin Altherma M ECH
2
O and the entire RoCon system (with activat-
ed terminal function) (see chapters 4.1 and 4.4.2).
N E Living Room,
Mixing Valve
Living Room -
Master-RoCon Display only on connected
room station:
Setting of the master RoCon function
Off: Deactivated
On: Function active
For every EHS157034 room station whose heating circuit ID is set on a direct heating
circuit, the master RoCon function can be activated (see chap. 4.4.4). Several room sta-
tions with active master RoCon function in the system are possible, but only one room
station which is assigned to the same heat generator.
All settings on the EHS157034 room station work for activated master RoCon function
as settings on the RoCon B1 control unit of the assigned heat generator. As a result, the
functions for hot water generation can also be remotely operated from the room station.
N E Off
On
Off -
Outdoor type Heat pump outdoor unit type
0: no selection
1: 5 kW
2: 7 kW
N E 0 - 6 0 1