5.7 Air Exchange Setting*
Turn-on air exchange function:
Under on-state of the unit, press Function button into this function setting (Air mark
blinks). AIR 1 displayed at the ambient temperature-displayed location (888) is defaulted
(the last type of AIR will be displayed after adjustment). Press
or button to adjust air
exchange type. Press Enter/Cancel button to turn on/off air exchange function. After
turning on this function, the air mark shows.
There are 10 types of air exchange, but only 1-2 types are for wireless remote control. Refer to the following
details:
1 —— The unit continuously runs for 60min, and fresh air valve opens for 6 min.
2 —— The unit continuously runs for 60min, and fresh air valve opens for 12 min.
3 —— The unit continuously runs for 60min, and fresh air valve opens for 18 min.
4 —— The unit continuously runs for 60min, and fresh air valve opens for 24 min.
5 —— The unit continuously runs for 60min, and fresh air valve opens for 30 min.
6 —— The unit continuously runs for 60min, and fresh air valve opens for 36 min.
7 —— The unit continuously runs for 60min, and fresh air valve opens for 42 min.
8 —— The unit continuously runs for 60min, and fresh air valve opens for 48 min.
9 —— The unit continuously runs for 60min, and fresh air valve opens for 54 min.
10 —— The unit continuously runs for 60min, and fresh air valve a ways opens.
Turn-off air exchange function:
During air exchange function, press Function button into air exchange function.
In this case, air mark is blinking, and then press Enter/Cancel button to turn off this
function. Air mark will subsequently disappear.
Air exchange setting is shown as Fig.5.7:
Press “Function” button
into air exchange function
Press “ ” or “ ” button
to adjust the type of air
exchange
Press “Function” button
into air exchange function
Press “Enter/Cancel” button
to turn on air exchange function
Turn on the unit, without
turning on air exchange
function
Press “Enter/Cancel” button
to turn off air exchange function
5.7 Air exchange device Fig.
In air exchange mode, press “Function” button or there is no any operation within 5s after the last button Note:
operation, the system will quit from air exchange setting, and current setting data won’t be memoried.
l
Содержание
- Ducted air conditioning unit 7 14 kw 1
- Operation and installation instructions manual 1
- User notice 2
- Contents 3
- English 1 3
- I safety precautions 2 3
- Ii displaying part 6 3
- Iii buttons 8 3
- Iv installation of wired controller 9 3
- Ix installation instructions 27 3
- Listed in this manual 3
- Notes the functions with are reserved for other models and are not applicable for the models 3
- V instruction to operation 10 3
- Vi error display 22 3
- Vii setting of indoor room sensor 23 3
- Viii dimensions of indoor unit and outdoor unit 25 3
- X specifications 47 3
- Safety precautions i 4
- Displaying part ii 8
- Lcd display of wired controller 8
- Instruction to lcd display 9
- Buttons iii 10
- Instruction to function of buttons 10
- Silk screen of buttons 10
- Installation of wired controller iv 11
- Instruction to operation v 12
- Mode setting 12
- On off 12
- Fan speed setting 13
- Temperature setting 13
- Swing control function 14
- Timer setting 14
- Air exchange setting 16
- Sleep setting 17
- Save function setting 18
- Turbo function setting 18
- E heater setting 20
- Blow function setting 21
- Field setting 22
- Quiet function setting 22
- Other functions 23
- Error display vi 24
- Air damper 25
- Fresh air control 25
- Indoor side 25
- Outdoor fresh air 25
- Setting of double indoor room sensors 25
- Setting of indoor room sensor 25
- English 26
- It can reach 1 m so that the engineering installation is very convenient and prompt 26
- The head of delivery of the condensate drainage pump 26
- Dimensions of indoor unit 27
- Dimensions of indoor unit and outdoor unit viii 27
- Dimensions of outdoor unit 28
- Installation instructions ix 29
- Precautions on installation of indoor unit 29
- Precautions on installation of outdoor unit 29
- After the indoor unit is installed it is required to check the level of the whole unit the unit must be placed horizontally but the condensate pipe shall be installed obliquely so as to facilitate the drainage of condensat 31
- Air intake pipe 6 main air supply pipe 31
- Canvas air pipe 7 air supply outlet 4 air intake 31
- Caution the air supply pipe the air intake pipe and the fresh air pipe must be covered with a layer of thermal insulation so as to avoid thermal leakage and condensation firstly apply liquid nail on the pipes then attach the thermal insulation cotton with a layer of tinfoil use the liquid nail cover to fi x it lastly use tinfoil adhesive tape to carefully seal the joints other good thermal insulation materials can also be used the air supply pipes and the air intake pipes shall be fi xed to the prefabricated boards of the ceiling by using iron supports the joints of the pipes must be sealed by glue so as to avoid leakage the design and installation of air pipes must be in conformity with the relevant state engineering criteria the edge of the air intake pipe must be at least 150mm away from the wall the air intake must be covered with fi lter silencing and shock absorption shall be considered in the design and installation of the air pipes addition ally the noise source must be far away f 31
- English 29 31
- Installation of rectangular air pipe 31
- Level check of the indoor unit 31
- No name no name 1 hook 5 filter 31
- Installation of drainage pipeline 32
- Testing of drainage system 32
- Connection of the refrigerant pipe 33
- Selection of the refrigerant pipe 33
- Installation of protective layer of the refrigerant pipe 37
- Position and method of installing wired controller 38
- Electric installation 39
- 1 the defrosting mode after the compressor consecutively runs for t minutes it will start defrosting if the sensor detects the tem perature t1 c for consecutive 1 minute it will stop defrosting when defrosting has run for 10 minutes or the sensor detects the temperature over t2 c 41
- 2 the defrosting control there are 8 defrosting modes corresponding to different dip ways the t t1 t2 t are defi ned as below t the defrosting temp sensor starts to detect after the compressor has been operating for t minutes 41
- Accumulatively 41
- Ambient temperature over t2 c 41
- Dip and corresponding temperature 41
- English 39 41
- T outdoor ambient temperature 41
- T1 c for 1 minute continuously 41
- T1 the defrosting board starts to work when the defrosting temp sensor has been in t1 c or under 41
- T2 the defrosting will stop after it goes on for 10 minutes continuously or the temp sensor detects the 41
- The defrosting setting 41
- 1 power cord 3 4 mm² h07rn f 2 power cord 3 2 mm² h07rn f 3 communication cords 2 1 mm² h07rn f capability of breaker 25a 43
- 1 power cord 3 4 mm² h07rn f 2 power cord 3 2 mm² h07rn f 3 communication cords 4 1 mm² h07rn f capability of breaker 25a 43
- 1 power cord 3 6 mm² h07rn f 2 power cord 3 4 mm² h07rn f 3 communication cords 2 1 mm² h07rn f capability of breaker 32a 43
- 1 power cord 3 6 mm² h07rn f 2 power cord 3 4 mm² h07rn f 3 communication cords 4 1 mm² h07rn f capability of breaker 32a 43
- Cable connecting diagram 43
- English 41 43
- Indoor unit 43
- Indoor unit 1 43
- Outdoor unit 43
- Power 220v 60hz 43
- R24pevlk fdm24pevlk ry24pevlk fdym24pevlk 43
- R30pevlk fdm30pevlk ry30pevlk fdym30pevlk 43
- Schematic diagram of unit line connection 43
- The section area of cables selected by users must not be smaller than the specifi cations shown in the 1 diagram the signal wire between indoor and outdoor unit shall be installed in the shielded bushing and the unshielded twisted pair cable utp shall be used the cross sectional area of the cables must be 1 mm² 43
- 1 power cord 3 6 mm² h07rn f 2 power cord 3 1 mm² h07rn f 3 communication cords 2 1 mm² h07rn f capability of breaker 32a 44
- 1 power cord 3 6 mm² h07rn f 2 power cord 3 1 mm² h07rn f 3 communication cords 4 1 mm² h07rn f capability of breaker 32a 44
- 1 power cord 4 6 mm² h07rn f 2 power cord 3 1 mm² h07rn f 3 communication cords 2 1 mm² h07rn f capability of breaker 32a 44
- 1 power cord 4 6 mm² h07rn f 2 power cord 3 1 mm² h07rn f 3 communication cords 4 1 mm² h07rn f capability of breaker 32a 44
- English 44
- Indoor unit 44
- Outdoor unit 44
- Power 220v 3 60hz 44
- Power 220v 60hz 44
- R36pevlk fdm36pevlk ry36pevlk fdym36pevlk 44
- R42petlk fdm42pevlk r48petlk fdm48pevlk ry42petlk fdym42pevlk ry48petlk fdym48pevlk 44
- 1 power cord 5 4 mm² h07rn f 2 power cord 3 1 mm² h07rn f 3 communication cords 2 1 mm² h07rn f capability of breaker 25a 45
- 1 power cord 5 4 mm² h07rn f 2 power cord 3 1 mm² h07rn f 3 communication cords 4 1 mm² h07rn f capability of breaker 25a 45
- English 43 45
- Indoor unit 45
- Outdoor unit 45
- Power 380v 3n 60hz 45
- R42peylk fdm42pevlk r48peylk fdm48pevlk ry42peylk fdym42pevlk ry48peylk fdym48pevlk 45
- Troubleshooting and maintenance 46
- English 47 49
- Specifications x 49
- English 50
Похожие устройства
- Daikin FDYM24PEVLK Инструкция по эксплуатации
- Daikin FDYM30PEVLK Инструкция по эксплуатации
- Daikin FDYM36PEVLK Инструкция по эксплуатации
- Daikin FDYM42PEVLK Инструкция по эксплуатации
- Daikin FDYM48PEVLK Инструкция по эксплуатации
- Daikin R24PEVLK Инструкция по эксплуатации
- Daikin R30PEVLK Инструкция по эксплуатации
- Daikin R36PEVLK Инструкция по эксплуатации
- Daikin R42PETLK Инструкция по эксплуатации
- Daikin R42PEYLK Инструкция по эксплуатации
- Daikin R48PETLK Инструкция по эксплуатации
- Daikin R48PEYLK Инструкция по эксплуатации
- Daikin RY24PEVLK Инструкция по эксплуатации
- Daikin RY30PEVLK Инструкция по эксплуатации
- Daikin RY36PEVLK Инструкция по эксплуатации
- Daikin RY42PETLK Инструкция по эксплуатации
- Daikin RY42PEYLK Инструкция по эксплуатации
- Daikin RY48PETLK Инструкция по эксплуатации
- Gigabyte GA-8I925X-G Configuring SATA Hard Drive
- Gigabyte GA-8I925X-G Руководство пользователя