Daikin FDM48PEVLK [41/50] 1 the defrosting mode after the compressor consecutively runs for t minutes it will start defrosting if the sensor detects the tem perature t1 c for consecutive 1 minute it will stop defrosting when defrosting has run for 10 minutes or the sensor detects the temperature over t2 c

Daikin FDM30PEVLK [41/50] 1 the defrosting mode after the compressor consecutively runs for t minutes it will start defrosting if the sensor detects the tem perature t1 c for consecutive 1 minute it will stop defrosting when defrosting has run for 10 minutes or the sensor detects the temperature over t2 c
English 39
The defrosting setting
(1) The defrosting mode
After the compressor consecutively runs for t ” minutes, it will start defrosting if the sensor detects the tem-
perature T1 ” °C for consecutive 1 minute. It will stop defrosting when defrosting has run for 10 minutes or
the sensor detects the temperature over T2 °C
(2) The defrosting control
There are 8 defrosting modes corresponding to different DIP ways.
The “ t ”, T1 ”, T2 ”, T ” are defi ned as below:
t ............ The defrosting temp sensor starts to detect after the compressor has been operating for t minutes
accumulatively
T1 ......... The defrosting board starts to work when the defrosting temp sensor has been in T1°C or under
T1°C for 1 minute continuously
T2 ......... The defrosting will stop after it goes on for 10 minutes continuously or the temp sensor detects the
ambient temperature over T2°C
T ........... Outdoor ambient temperature
DIP and corresponding temperature
Outdoor ambient
temp. sensor
DIP 000 001 010 011 100
T
 
-
 
-
 
- - -
-3 <-3
-3 <-3
-3 <-3
t 44 44 60 90 30 30 60 44 90 90 120
T1 -2 -5 0 0 0 -2 -10 -2 -10 -2 -15
T2 15 20 20 20 20 20 15 20 15 20 15
Outdoor ambient temp. sensor
doses not work
Outdoor ambient temp. sensor works
101
110
111