Daikin EKOMB22AAV1 [44/60] Weather dependent regulation

Daikin EKOMB28AAV1 [44/60] Weather dependent regulation
Daikin Europe NV
44
7.5 Weather dependent regulation
When connecting an outdoor sensor, the leaving water temperature is automatically
regulated dependent on the outdoor temperature, in accordance with the set fuel line.
The maximum leaving water temperature (T max) is set via the display. If so desired,
the fuel line can be changed by using the service code (see par.7.3).
Fuel line graph
X. T outside in °C
Y. T leaving water in °C
A. Factory setting
(Tmax CH = 80°C, Tmin CH = 25°C, Tmin ex = -7°C, Tmax ex = 25°C)
B. Example
(Tmax CH = 60°C, Tmin CH = 25°C, Tmin ex = -7°C, Tmax ex = 25°C)