8 Configuration
Installer reference guide
65
CHYHBH05+08AA + EHYKOMB33A
Daikin hybrid for multi heat pump – heat pump module
4P471761-1A – 2017.10
Parameter Setting Range Default
settings
Description
Minimal space heating rpm 23%~50% 23% Adjustment range 23~50%
(40=propane).
It is recommended not to modify this
setting in case of natural gas.
. Minimum capacity space heating pump — 40 There is no space heating pump in the
gas boiler. Changing this setting has
no effect.
Minimal domestic hot water rpm
(not applicable for Switzerland)
23%~50% 23% Adjustment range 23~50%
(40=propane).
It is recommended not to modify this
setting in case of natural gas.
Minimal supply temperature during OT
demand. (OpenTherm thermostat)
10°C~16°C 40°C Changing this setting has no effect on
the operation of the unit.
. Reversible setting 0~1 1 This setting activates the keep hot
function of the gas boiler. It is only
used with reversible heat pump models
and should NEVER be deactivated. It
MUST be deactivated for heating only
models (set to 0).
▪ 0=disabled
▪ 1=enabled
Start rpm space heating 50%~99% 50% This is the fan rpm before heating
ignition. It is recommended not to
modify this setting.
. Start rpm domestic hot water
(not applicable for Switzerland)
50%~99% 50% This is the fan rpm before instant
domestic hot water ignition. It is
recommended not to modify this
setting.
Maximum fan rpm 45~50 48 Use this parameter to set the maximum
fan rpm. It is recommended not to
modify this setting.
Set point space heating (flow
temperature) during heating external
domestic hot water tank
60°C~90°C 85°C Do NOT modify this setting on the
boiler. Use the user interface instead.
. Comfort temperature 0°C / 40°C~65°C 0°C Temperature used for eco/comfort
function. When the value is 0°C, the
eco/comfort temperature is the same
as the domestic hot water setpoint.
Otherwise, the eco/comfort
temperature is between 40°C and
65°C.
. Waiting time after a space heating
demand from a thermostat.
0min~15min 0min Changing this setting has no effect on
the operation of the unit.
Waiting time after a domestic hot water
demand before a space heating
demand is answered.
0min~15min 0min Amount of time the boiler waits before
answering a space heating demand
after a domestic hot water demand.
. Number of eco days. 1~10 3 Number of eco days.
Anti-cycling period during space
heating operation
0min~15min 5min Minimal switch-off time in space
heating operation. It is recommended
not to modify this setting.
. Reference value for domestic hot water 24-30-36 36 ▪ 24: Not applicable.
▪ 30: Not applicable.
▪ 36: Only for EHYKOMB33AA*.
Maximum space heating power setting
The maximum space heating power setting ( ) is factory set to 70%.
If more or less power is required, you can change the fan rpm. The
table below shows the relationship between the fan rpm and the
appliance power. It is strongly recommended NOT to modify this
setting.
Desired power (kW) Setting on service display (%
of max. rpm)
26.2 83
25.3 80
22.0 70
19.0 60
15.9 50
Содержание
553- Daikin hybrid for multi heat pump heat pump
- Chyhbh05aa chyhbh08aa ehykomb33a
- Module
- Installer reference guide
- Table of contents
- Preparation 15
- Installer reference guide
- Installation 22
- General safety precautions 3
- About the units and options 10
- About the product 7
- About the documentation 8
- About the box 8
- The precautions described in this document cover very important
- Danger risk of electrocution
- The original documentation is written in english all other
- Danger
- Configuration 45
- The installation of the system and all activities described in the
- Commissioning 69
- Technical data 84
- About the documentation
- Operation 68
- Meaning of warnings and symbols
- Maintenance and service 74
- Languages are translations
- Installation manual and the installer reference guide must be performed by an authorised installer
- Indicates a situation that results in death or serious injury
- Indicates a situation that could result in electrocution
- Hand over to the user 74
- Glossary 100
- General safety precautions
- Troubleshooting 77
- Field settings table 101
- Topics follow them carefully
- Disposal 83
- Installation site
- General safety precautions
- General
- For the installer
- Refrigerant
- General safety precautions
- General safety precautions
- Electrical
- Local legislation
- Gas exhaust
- About the product
- About this document
- About the documentation
- About the box
- Overview about the box
- Installer reference guide at a glance
- Prepare the path along which you want to bring the unit inside in
- Position to prevent damage during transport
- Must be reported immediately to the carrier s claims agent
- Keep the following in mind
- Information
- Indoor unit
- Gas boiler
- Do not throw away the upper cardboard cover on the outside of the cardboard cover the installation pattern is printed
- Bring the packed unit as close as possible to its final installation
- Before unpacking move the gas boiler as close as possible to its installation position
- At delivery the unit must be checked for damage any damage
- To unpack the indoor unit
- Advance
- To unpack the gas boiler
- To remove the accessories from the indoor unit
- About the box
- The installation manual operation manual addendum book for optional equipment general safety precautions quick installation guide boiler communication cable and reducer accessory set are located in the upper part of the box the connection pieces for the gas boiler are attached to the water piping
- A b c d e
- Removing the accessories from the units
- Remove the accessories as described in 4 to unpack the indoor unit on page 9
- To remove the accessories from the gas boiler
- Overview about the units and options
- Identification label indoor unit
- Identification
- About the units and options
- Possible options for the indoor unit
- M n o p
- Identification label gas boiler
- Combining units and options
- About the units and options
- Possible options for the gas boiler
- About the units and options
- About the units and options
- About the units and options
- Preparing the installation site
- Preparation
- Possible combinations of indoor unit and outdoor unit
- Possible combinations of indoor unit and domestic hot water tank
- Overview preparation
- Installation site requirements of the indoor unit
- Special requirements for r32
- Preparation
- P471761 1a 2017 0
- Installer reference guide
- Daikin hybrid for multi heat pump heat pump module
- Chyhbh05 08aa ehykomb33a
- Use the tables in 15 table 1 maximum refrigerant charge allowed in a room indoor unit on page 90 15 table 2 minimum floor area indoor unit on page 92 15 table 3 minimum venting opening area for natural ventilation indoor unit on page 93 to calculate the needed values to make sure that your appliance is installed correctly
- Refrigerant piping requirements
- Refrigerant piping insulation
- Preparing refrigerant piping
- Preparation
- Water circuit requirements
- Preparing water piping
- Preparation
- A b d e
- To check the water volume and flow rate
- Preparation
- Formula to calculate the expansion vessel pre pressure
- C d a b
- A b d e h g
- Changing the pre pressure of the expansion vessel
- About preparing electrical wiring
- To check the water volume examples
- Preparing electrical wiring
- Preparation
- Preparation
- Overview of electrical connections for external and internal actuators
- Overview of electrical connections except external actuators
- 7 8 9 10 14 15
- To open the switch box cover of the indoor unit
- Overview installation
- Opening the units
- Installation
- About opening the units
- Precautions when mounting the indoor unit
- Mounting the indoor unit
- Installation
- About mounting the indoor unit
- To open the switch box cover of the gas boiler
- To open the gas boiler
- To install the indoor unit
- To install the gas boiler
- To install the condensate trap
- Mounting the gas boiler
- Installation
- Ø22 mm
- Internal connections
- Installation
- Condensate pump
- Condensate pipe work
- 75 mm ø22 mm
- External connections
- Connecting the refrigerant piping
- About connecting the refrigerant piping
- Ø22 mm
- Precautions when connecting the refrigerant piping
- Installation
- Using the stop valve and service port
- To handle the stop valve
- To flare the pipe end
- To braze the pipe end
- Pipe bending guidelines
- Installation
- Guidelines when connecting the refrigerant piping
- A b c d e
- To open close the stop valve
- To handle the stem cap
- To handle the service cap
- To connect the refrigerant piping to the indoor unit
- Installation
- Usage of reducers to connect the piping to the outdoor unit
- To perform vacuum drying
- To check for leaks
- Precautions when checking the refrigerant piping
- Installation
- Checking the refrigerant piping
- Charging refrigerant
- About checking the refrigerant piping
- About charging refrigerant
- To determine the complete recharge amount
- To determine the additional refrigerant amount
- To charge additional refrigerant
- Precautions when charging refrigerant
- Installation
- About the refrigerant
- About connecting the water piping
- To fix the fluorinated greenhouse gases label
- To connect the water piping for space heating
- Precautions when connecting the water piping
- Installation
- Connecting the water piping of the indoor unit
- Connecting the water piping
- To connect the water piping for space heating
- To connect the water piping for domestic hot water not applicable for switzerland
- Installation
- Connecting the water piping of the gas boiler
- To connect the water piping for domestic hot water applicable for switzerland
- Precautions when connecting the electrical wiring
- Installation
- Guidelines when connecting the electrical wiring
- Connecting the electrical wiring
- About connecting the electrical wiring
- To insulate the water piping
- To fill the space heating circuit
- To fill the domestic water circuit of the gas boiler
- To fill the domestic hot water tank
- To connect the main power supply of the indoor unit
- To connect the electrical wiring on the indoor unit
- Installation
- To connect the main power supply of the gas boiler
- To connect the communication cable between gas boiler and indoor unit
- Installation
- To connect the user interface
- Installation
- To connect the domestic hot water pump
- To connect the alarm output
- Output
- Installation
- To connect the space heating on off
- To connect the shut off valve
- To connect the safety thermostat normal
- To connect the gas pipe
- Installation
- Connecting the gas piping
- Connecting the boiler to the flue gas system
- Closed contact
- To change the gas boiler to 80 125 concentric connection
- To change the 60 100 concentric connection to a dual pipe connection
- Installation
- Calculate the total piping length
- R d 1 r d 0
- Installation
- Appliance categories and pipe lengths
- Installation
- L2 1 l1 11
- Installation
- Flue pipe position
- Applicable materials
- Plume management kit
- Insulation of the gas exhaust and air intake
- Installation
- Fitting a vertical flue system
- Fitting a horizontal flue system
- To close the indoor unit
- To close the gas boiler
- Installation
- Flues in voids
- Finishing the outdoor unit installation
- Finishing the indoor unit installation
- Finishing the gas boiler installation
- To purge the gas supply
- To finish the outdoor unit installation
- To close the outdoor unit
- To install the cover plate
- To connect the pc cable to the switch box
- Overview configuration
- Indoor unit
- Configuration
- To copy the system settings from the first to the second user interface
- To access the most used commands
- Configuration
- Cancel ok
- 06 0a 0e
- 03 07 0b 0f
- 01 05 09 0d
- 00 04 08 0c
- U5 auto address
- To copy the language set from the first to the second user interface
- Send data
- Quick wizard set the system layout after first power on
- Ok cancel
- Configuration
- Cancel ok
- 2013 jan tue
- Quick wizard standard
- Quick wizard language time and date
- Configuration
- Basic configuration
- Quick wizard options
- Configuration
- Configuration
- Configuration
- Space heating control
- Configuration
- Domestic hot water control
- Configuration
- Space heating operation advanced
- Contact helpdesk number
- Configuration
- Advanced configuration optimization
- Configuration
- Configuration
- Domestic hot water control advanced
- Configuration
- Configuration
- Heat source settings
- Configuration
- Configuration
- System settings
- Menu structure overview user settings
- Installer reference guide
- Configuration
- Chyhbh05 08aa ehykomb33a daikin hybrid for multi heat pump heat pump module 4p471761 1a 2017 0
- P471761 1a 2017 0
- Menu structure overview installer settings
- Installer reference guide
- Information
- Gas meter settings are shown but are not applicable for this unit settings shall not be used or changed
- External kwh meter settings are shown but are not applicable for this unit settings shall not be used or changed
- Depending on the selected installer settings and unit type settings will be visible invisible
- Demand pcb settings are shown but are not applicable for this unit settings shall not be used or changed
- Daikin hybrid for multi heat pump heat pump module
- Configuration
- Chyhbh05 08aa ehykomb33a
- To turn on off the gas boiler
- To set the parameters via the service code
- To reset the gas boiler
- Overview configuration
- Maximum space heating supply temperature
- Keep hot function
- Gas boiler
- Frost protection function
- Domestic hot water temperature
- Domestic hot water comfort function
- Configuration
- Basic configuration
- A b c f e d
- 2 7 5 6 3 4 8
- Configuration
- Configuration
- Maximum space heating power setting
- To change to a different type of gas
- Configuration
- About the carbon dioxide setting
- Configuration
- Overview operation
- Operation modes
- Operation
- Heating
- Flow resistance graph for appliance domestic hot water circuit
- Domestic hot water
- Precautions when commissioning
- Overview commissioning
- Commissioning
- Checklist before commissioning
- Air purge function
- To perform a wiring error check
- To check the minimum flow rate
- Commissioning
- Checklist during commissioning
- To perform an automatic air purge
- To perform a test run
- To perform a manual air purge
- To interrupt air purge
- Commissioning
- Air purge
- Underfloor heating screed dryout
- To perform an actuator test run
- Possible actuator test runs
- H 1 36h 2
- Commissioning
- C 1 35 c 2
- To readout the status of an underfloor heating screed dryout
- To program an underfloor heating screed dryout schedule
- To perform an underfloor heating screed dryout
- To perform an air purge on the gas supply
- To perform a test run on the gas boiler
- To interrupt an underfloor heating screed dryout
- Screed dryout
- Commissioning
- Overview maintenance and service
- Opening the indoor unit
- Maintenance safety precautions
- Maintenance and service
- Hand over to the user
- Checklist for yearly maintenance of the outdoor unit
- Checklist for yearly maintenance of the indoor unit
- Maintenance and service
- To disassemble the gas boiler
- To clean the inside of the gas boiler
- Maintenance and service
- Troubleshooting
- To assemble the gas boiler
- Overview troubleshooting
- Troubleshooting
- Symptom the unit is not heating or cooling as expected
- Symptom the system is making gurgling noises after commissioning
- Symptom the pump is making noise cavitation
- Symptom the compressor does not start space heating
- Solving problems based on symptoms
- Precautions when troubleshooting
- Symptom the pressure relief valve opens
- Symptom the pressure at the tapping point is temporarily unusually high
- Symptom tank disinfection function is not completed correctly ah error
- Troubleshooting
- Symptom the water pressure relief valve leaks
- Symptom the space is not sufficiently heated at low outdoor temperatures
- Troubleshooting
- Hj 11 error
- Boiler
- Abnormality ua52 error
- 5 symptom no space heating by the gas
- 4 symptom the burner resonates
- 3 symptom the burner ignites noisily
- 2 symptom the burner does not ignite
- 1 symptom boiler hydrobox combination
- 0 symptom boiler abnormality detection
- 8 symptom hot water does not reach the
- 7 symptom space heating does not reach
- 6 symptom the power is reduced
- Troubleshooting
- The temperature
- Temperature tank installed
- Temperature no tank installed
- Solving problems based on error codes
- Error codes overview
- Error codes of the indoor unit
- 9 symptom hot water does not reach the
- Troubleshooting
- Overview disposal
- Error codes of the gas boiler
- Disposal
- To start and stop forced cooling
- To pump down
- Technical data
- D082238 1b
- X5m field wiring terminal for dc
- X2m field wiring terminal for ac
- X1m indoor outdoor communication
- Wiring diagram indoor unit
- Technical data
- See the internal wiring diagram supplied with the unit on the inside of the indoor unit switch box cover the abbreviations used are listed below
- Piping diagram indoor unit
- Notes to go through before starting the unit
- English translation
- Technical data
- Technical data
- Gas boiler
- Electrical connection diagram for more details please check the unit wiring
- Domestic hot water tank
- D107996
- A1p x9a
- Technical data
- Standard parts
- Power supply
- Optional parts khwp
- Only for ksrps3 option
- Only for krtw wired room thermostat
- Only for krtr wireless room thermostat
- Only for krtets
- Only for krp1hb
- Only for krcs01 1 or ekrsca1
- Only for heat pump convector
- Wiring diagram gas boiler
- Technical data
- Installer reference guide
- Daikin hybrid for multi heat pump heat pump module
- Chyhbh05 08aa ehykomb33a
- Technical data
- Table 1 maximum refrigerant charge allowed in a room indoor unit
- P471761 1a 2017 0
- Technical data
- Not subjected to any requirements to the installation room
- Installer reference guide
- Information
- In cases where h 600 mm h is always considered to
- H the height measured from the floor to the flare nut
- H the height measured from the floor to the bottom of
- For intermediate h values i e when h is between 2 h
- For intermediate dm values i e when dm is between 2
- Dm values from the table consider the value that corresponds to the higher dm value from the table if dm 1 5 kg consider dm 1 kg
- Daikin hybrid for multi heat pump heat pump module
- Values from the table consider the value that corresponds to the lower h value from the table if h 950 mm consider the value that corresponds to h 900 mm
- Chyhbh05 08aa ehykomb33a
- The casing
- Be 600 mm as specified in iec 60335 2 40 2013 a1 2016 clause gg2
- Technical data
- Table 2 minimum floor area indoor unit
- Systems with a total refrigerant charge 1 25 kg are
- P471761 1a 2017 0
- Technical data
- Table 3 minimum venting opening area for natural ventilation indoor unit
- Installer reference guide
- Chyhbh05 08aa ehykomb33a daikin hybrid for multi heat pump heat pump module 4p471761 1a 2017 0
- Values from the table consider the value that corresponds to the lower h value from the table if h 950 mm consider the value that corresponds to h 900 mm
- Chyhbh05 08aa ehykomb33a
- Values from the table consider the lower
- Casing
- Value from the table if
- Between 2
- Technical data
- Be 600 mm as specified in iec 60335 2 40 2013 a1 2016 clause gg2
- P471761 1a 2017 0
- 1500 mm
- Mm 20 mm
- 1 kg consider
- Installer reference guide
- Information
- In cases where h 600 mm h is always considered to
- In case of a different configuration is used do not deviate from requirements mentioned in 6 preparation on page 15
- H height measured from the floor to the flare nut
- H height measured from the floor to the bottom of the
- For intermediate h values i e when h is between 2 h
- For intermediate
- Following graphics are possible examples about minimum venting opening area for natural ventilation
- Warning
- Values i e when
- Daikin hybrid for multi heat pump heat pump module
- Technical data
- Note selecting a flow outside the area of operation can cause damage or malfunction of the unit water quality must be according to en directive ec98 83ec
- Note a flow error will occur when the minimum water flow rate is not reached
- Installer reference guide
- Esp curve indoor unit
- Chyhbh05 08aa ehykomb33a daikin hybrid for multi heat pump heat pump module 4p471761 1a 2017 0
- C minimum water flow rate boiler bypassed boiler not bypassed
- B water flow rate
- B l min
- A external static pressure
- Technical specifications gas boiler
- Technical data
- General
- Gas category and supply pressure
- Technical data
- This commissioning checklist is to be completed in full by the competent person who commissioned the boiler as a means of demonstrating compliance with the appropriate building regulations and then handed to the customer to keep for future reference
- Technical data
- P471761 1a 2017 0
- Installer reference guide
- Gas boiler system commissioning checklist
- Daikin hybrid for multi heat pump heat pump module
- Control
- Condensing boilers only
- Combination boilers only
- Chyhbh05 08aa ehykomb33a
- Central heating mode
- All systems
- All installations
- Service 10
- Service 1
- Technical data
- Service record
- Service provider
- Service 9
- Service 8
- Service 7
- Service 6
- Service 5
- Service 4
- Service 3
- Service 2
- Glossary
- Field settings table
- P471775 1 2016 2 chyhbh
- Field settings table
- Chyhbh 4p471775 1 2016 2
- Field settings table
- P471775 1 2016 2 chyhbh
- Field settings table
- Field settings table
- Chyhbh 4p471775 1 2016 2
- P471775 1 2016 2 chyhbh
- Field settings table
Похожие устройства
-
Daikin EVLQ08CAV3Руководство по применению для установщика -
Daikin EVLQ08CAV3Справочное руководство для монтажника -
Daikin EVLQ08CAV3Общие правила техники безопасности -
Daikin EVLQ08CAV3Инструкция по монтажу -
Daikin EVLQ05CAV3Справочное руководство для монтажника -
Daikin EVLQ05CAV3Руководство по применению для установщика -
Daikin EVLQ05CAV3Общие правила техники безопасности -
Daikin EVLQ05CAV3Инструкция по монтажу -
Daikin EHYKOMB33AA3Справочное руководство для монтажника -
Daikin EHYKOMB33AA3Руководство по применению для установщика -
Daikin EHYKOMB33AA3Руководство по эксплуатации -
Daikin EHYKOMB33AA2Справочное руководство для монтажника
Изучите параметры настройки и рекомендации для эффективной работы тепловых насосов. Узнайте, как оптимизировать производительность и избежать ошибок.