8 | Configuration
Installer reference guide
136
EVLQ05+08CAV3 + EHYHBH05AF + EHYHBH/X08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1F – 2020.10
# Code Description
[7.7.1.1] [1‑00]
[1‑01]
[1‑02]
[1‑03]
Set weather-dependent heating:
[1-03]
[1-02]
T
a
T
t
[1-00] [1-01]
T
t
: Target leaving water temperature (main)
T
a
: Outdoor temperature
continued >>
# Code Description
[7.7.1.1] [1‑00]
[1‑01]
[1‑02]
[1‑03]
<< continuation
[1‑00]: Low outdoor ambient temperature.
40°C~+5°C (default: –10°C)
[1‑01]: High outdoor ambient temperature.
10°C~25°C (default: 15°C)
[1‑02]: Desired leaving water temperature
when the outdoor temperature equals or
drops below the low ambient temperature.
[9‑01]°C~[9‑00]°C (default: 60°C).
Note: This value should be higher than [1-03]
as for low outdoor temperatures warmer
water is required.
[1‑03]: Desired leaving water temperature
when the outdoor temperature equals or
rises above the high ambient temperature.
[9‑01]°C~min(45, [9‑00])°C (default: 35°C).
Note: This value should be lower than [1-02]
as for high outdoor temperatures less warm
water is required.
# Code Description
[7.7.1.2] [1‑06]
[1‑07]
[1‑08]
[1‑09]
Only for EHYHBX08. Set weather-
dependent cooling:
[1-09]
[1-08]
T
a
T
t
[1-06] [1-07]
T
t
: Target leaving water temperature (main)
T
a
: Outdoor temperature
continued >>