5 INSTALLATION
During installation or whenever work must be carried out on the unit, it is essential to strictly follow the instructions in
this manual, comply with the directions on the unit and in any case take all necessary precautions.
The pressures in the refrigerant circuit and the electrical components can create risky situations
during installation and maintenance work.
5.1 Dimensions and weight
Inordertocorrectlypositiontheunit,pleaserefertothedimensionaldrawingsuppliedwiththeorderconrmationfor
itssizeandweight.
5.2 Installation site
The following should be taken into account to establish the best place to install the unit and the relevant connections:
- sizeandoriginoftheaeraulicducts;
- sizeandoriginofthehydraulicpiping;
- location of the power supply;
- accessibility for maintenance or repair operations;
- load-bearing capacity of the support surface;
- ventilation of the air-cooled condenser;
- orientation and exposure to solar radiation. Keep the condensing coil out of direct sunlight as far as possible;
- direction of prevailing winds. Do not position the unit in a such way that prevailing winds can cause air recirculation
at the condensing coil;
- type of surface. Do not position the unit on dark coloured surfaces (e.g. tarred surfaces) so as to avoid
overtemperatures during use;
- possiblereections,resonancesandacousticinteractionswithelementsoutsidetheunit.
Payattentiontothepresenceofues,drains,ventsandtothestaleairofothersystems.Aircanbe
sucked from the fresh air damper and through the supply unit in the rooms to be air conditioned.
Allthemodelsintherangearedesignedandbuiltforoutdoorinstallation(terraces,gardens).Theymusttherefore
notbeinstalledundercanopiesornearplants(evenifthesewouldcoveronlypartoftheunit),inordertoavoidthe
possibility of air recirculation.
Itisobligatorytoobservetheclearancesspeciedinthedimensionaldiagramoftheunit.
If the unit is installed in particularly windy areas, windbreaks must be installed to prevent
malfunctioning of the unit.
Duringthedefrostcycle,unitsinheatpumpoperationallowwatertoowoutthatfreezeswithsub-
zerotemperatures.Althoughtheunitisinstalledperfectlyhorizontal,makeslopesinthesupport
surface to direct the defrost water into drains, wells or in any case to places where there is no danger
of accident.