Translation from original instructions
Installation manual
32
We reserve the right to make changes without any prior notice.
UATYQ*Y1
Packaged Rooftop
4P522680-1
6.3 Calibration of safety components
Anyworkontheunitmustbecarriedoutbyqualiedauthorisedpersonnel.Incorrectcalibration
values can cause serious damage to the unit and harm people.
Thecontrolandsafetyequipmentiscalibratedandtestedinthefactorybeforetheunitisshipped.
However, after the unit has been started, the safety devices must be checked (only the high and low pressure
switches).
The checks must be carried out as described in the "Periodic checks" chapter.
The calibration values are shown in the table
Control and safety
components
Unit
Activation set
point
Di󰀨erential Reset
High-pressure switch
From UATYQ20A* to
UATYQ30A*:
37,8 barg 10,8 barg
Manual
From UATYQ45A* to
UATYQ115A*:
40.5 barg 7,5 barg
Low-pressure switch All units: 1,5 barg 2,0 barg Automatic
High pressure safety
valve
From UATYQ20A* to
UATYQ30A*:
42 barg
- -
From UATYQ45A* to
UATYQ115A*:
45 barg