8 Maintenance
Table 2: Maintenance times
When
Activity
Flow meter can no
longer be read
Drain, flush and fill the system
Circulation pump
defective
Replace the circulation pump, see
below
8.1.1 Replace circulation pump
1. Close the shut-off at the flow meter and set the blue ball
valve to 90° position.
2. Replace the circulation pump.
3. Open the shut-off at the flow meter and set the blue ball
valve to 0° position.
4. In the case of pressure loss in the system, refill solar liquid
and re-commission the system.
9 Troubleshooting
Repairs may only be performed by specially trained, qualified
staff.
Observe the enclosed operating instructions in the case of
malfunctions of the circulation pump.
Table 3: Troubleshooting
Problem
Possible reason
Repair
Noise in the system
Air in the system
vent the system, see chap-
ter 7.1, page 20
Pump capacity too
high
Switch to a lower speed of
rotation