Daikin LRMEQ6AY1E [110/156] Troubleshooting

Daikin LRMEQ20AY1 [110/156] Troubleshooting
SiENBE28-901 Troubleshooting
Air Cooled Refrigeration Condensing Unit 109
Troubleshooting
*1. List of malfunction codes, description of malfunction, and electric symbols
*2. For "temperature and resistance characteristics of thermistor", refer to information on P.138.
Malfunction
code
Relevant thermistor
LRMEQ5, 6AY1
LRLEQ5, 6AY1
LRMEQ8, 10, 12AY1
LRLEQ8, 10, 12AY1
LRMEQ15, 20AY1
LRLEQ15, 20AY1
Electrical
symbol
Connector
Electrical
symbol
Connector
Electrical
symbol
Connector
H9
Outdoor air thermistor R1T X18A R1T X18A R1T X18A
J3
Discharge pipe (M1C) thermistor
R31T X29A R31T
X29A
R31T
X29A
Discharge pipe (M2C) thermistor
R32T R32T
Discharge pipe (M3C) thermistor
————R33T
J5
Suction pipe thermistor R2T
X30A
R2T
X30A
R2T
X30A
J8
Heat exchanger outlet
thermistor
R5T R5T R5T
J9
Heat exchanger inlet
thermistor
R6T R6T R6T
JA
High pressure sensor S1NPH X32A S1NPH X32A S1NPH X32A
JC
Low pressure sensor S1NPL X31A S1NPL X31A S1NPL X31A
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the malfunction
code "J3"
displayed?
NO
YES
There are multiple relevant
thermistors. Identify the
thermistor using the
monitor mode of the
outdoor unit PCB.
Check for connector
connection. (*1)
Is the resistance
normal?
YES
NO
Disconnect the thermistor
from the outdoor unit PCB,
and then make resistance
measurement using a
multiple meter.
Is the resistance
normal? (*2)
YES
NO
Properly connect it.
Replace the thermistor.
Replace the outdoor unit main PCB.