Daikin LRMEQ6AY1E [151/156] Trouble case with present machine r 407c

Daikin LRMEQ12AY1 [151/156] Trouble case with present machine r 407c
Appendix (Supplementary Information) SiENBE28-901
150 Air Cooled Refrigeration Condensing Unit
7.3 Trouble Case with Present Machine (R-407C)
Compressor damage due to the overcharge of refrigerant in the field
Cause
By mistake, a local installer added 1.3 times of the total refrigerant, not 1.3 times of the
additional charging refrigerant which is specified in the Installation Manual.
(It is already explained in the service news #MJ-08023. See the next page for more details.)
Prevention of new models
New models have improved compressor reliability by countermeasure control functions of
current models. Also, the amount of the additional charging refrigerant at the field specified
up to 0.1 times only.
Request for the indication of additional refrigerant charging amount and installation date
*Be sure to fill the blanks, which are needed for after-sale services.
Please calculate the amount of additional refrigerant charging as following method.
(1)By piping length of system
Please calculate from the total length of the liquid pipes. Calculate the total piping length of each size as follows.
(2)By connecting showcase
Please calculate from the capacity of the connected showcase as below tables.
(3)Constant
Add constant amount by outdoor unit model
Full of
liquid
A few
bubbles
flow.
Sealed state ({) Shortage of refrigerant (5)
Bubbles
come out at
all times.
(A)
(B)
Manufacture's label
value
(A)+(B)
Total additional
charging amount
kg
Charging amount
(Factory set)
kg
Total amount of
refrigerant
kg
Total length of
φ15.9 liquid pipes
+
Total length of
φ12.7 liquid pipes
Total length of
φ9.5 liquid pipes
Charging amount
by piping length
(m)×0.19 (m)×0.12 (m)×0.06 (1) kg
Capacity of showcase
(*Note.)
Amount of refrigerant
Showcase
Blower
coil
MT LT
less than 5kW 1.1kg 1.4kg 0.6kg
From 5kW to less than 10kW
2.3kg 3.2kg 1.2kg
From 10kW to less than 15kW
3.4kg 5.2kg 1.7kg
From 15kW to less than 20kW
4.6kg 2.3kg
From 20kW to less than 25kW
5.9kg 3.0kg
From 25kW to less than 30kW
7.0kg 3.5kg
From 30kW to less than 35kW
8.2kg 4.1kg
From 35kW to less than 40kW
9.7kg 4.9kg
40kW or more
11.0kg
5.5kg
Capacity of
showcase
kW
+
Capacity of
blower coil
kW
Charging amount
by connecting
showcase
Amount of
refrigerant
kg
Amount of
refrigerant
kg
(2) kg
Constant
(3) kg
Charging amount
by adjustment
(4) kg
Outdoor unit
Amount of
refrigerant
LRLEQ5, 6AY1•LRMEQ5, 6AY1
1.0kg
LRLEQ8~12AY1•LRMEQ8~12AY1
3.0kg
LRLEQ15~20AY1•LRMEQ15~20AY1
3.5kg
*Note)
1. Case of showcase the
condition of capacity
(evaporating
temperature)
MT (Medium
temperature):
–10°C
LT (Low temperature):
–35°C
2. Case of blower coil, the
condition of capacity is
10°C (Td).
(1)+(2)+
(3)+(4)
(4)By adjustment
(When the liquid eye shows shortage of
refrigerant.)
When test running, add refrigerant if the
liquid eye not be in sealing states at
cooling operation.
(4)By adjustment (2)By connecting showcase × 0.1
Do not be over 10% of (2) amount by connecting showcase.
3P251593-1A