Daikin LRMEQ6AY1E [152/156] Case example

Daikin LRMEQ8AY1E [152/156] Case example
SiENBE28-901 Appendix (Supplementary Information)
Air Cooled Refrigeration Condensing Unit 151
Secret
<Convenience-pack>
Re-precaution: Hard-and-fast additional refrigerant charge in commissioning
LRLCP14D1, 2 and all other convenience-pack models
PR
Model
This is to inform you again of the precaution (MJ06053) "For additional charge in a commissioning of
Conveni-pack, the upper limit shall be 1.3 times as much as that calculated." Because there was a
compressor failure caused by over charge that is assumed to be due to a miscalculation.
[Case example]
At the time of calculation of the upper limit of additional charge, "Initial charge in outdoor unit" was added.
After the refrigerant was charged by the calculated upper limit above, the over charge "4.29kg (30% of
14.3kg of the initial charge in the outdoor unit)" caused the compressor failure.
[Upper limit of additional refrigerant charge in commissioning]
Correct [Additional charge in the field (Calculated value depending on piping length) ] × 1.3
Wrong [Charge at factory + Additional charge in the field (Calculated value depending on piping
length) ] × 1.3
Example: Additional charge (Calculated value) :15kg The upper limit of additional charge :
19.5kg (15 × 1.3=19.5)
[Precaution for charging refrigerant]
For additional charge, please do not charge the upper limit of refrigerant at a time.
When charging refrigerant more than additional charge in the field (calculated value), please charge
refrigerant while observing through a sight glass.
A few bubbles are not problem. So please keep strictly the upper limit of additional refrigerant charge
(This
unit performs an oil return irregularly by on-off operation of a solenoid valve. Some transiently-generated
flashes during the solenoid valve operation are not problem.)
MJ–08023
When a solenoid valve is
turned onin sealed
condition Flashes
appear
Even though a solenoid
valve is turned off, flashes
sometimes appear.
Solenoid valve OFF
(Sealed condition)
Solenoid ON (Flashes appear) Solenoid valve After OFF (Just
before sealed condition)