Daikin LRMEQ6AY1E [60/156] Selection of piping material

Daikin LRLEQ15AY1 [60/156] Selection of piping material
SiENBE28-901 Test Operation
Air Cooled Refrigeration Condensing Unit 59
5.1.2 Selection of Piping Material
Make sure that the inner side and outer side of the piping used is clean and free of contaminants, such
as sulphur, oxide, dust, chips, oil and fat, and water.
It is desirable that the maximum oil adhesion in the piping is 30 mg per 10 m.
Use the following type of refrigerant piping.
Material: Seamless phosphorus deoxidized copper tube (C1220T-O for a maximum outer
diameter of 15.9 mm and C1220T-1/2H for a minimum outer diameter of 19.1 mm)
Refrigerant piping size and wall thickness: Decide the size and thickness from the following table.
(This product uses R410A. The withstand pressure of O type may be insufficient if it is
used for piping with a minimum diameter of 19.1 mm. Therefore, be sure to use 1/2 H type
with a minimum thickness of 1.0 mm.
If O type is used for piping with a minimum diameter of 19.1 mm, a minimum thickness of
1.2 mm will be required. In that case, be sure to perform the blazing of each joint.)
Be sure to perform piping work within the range specified in the following table.
¢Refrigerant piping length²
Max. permissible
one-way piping length
(equivalent length)
LRMEQ5~20AY1
a + b + c + d
130m (d is d1 or d2 or e, f whichever is longer)
LRLEQ5~20AY1
a + b + c + d
70m (d is d1 or d2 whichever is longer)
Max. branch piping length (actual length)
b + c + d
30m (d is d1 or d2 whichever is longer)
Max. difference in
height between indoor
and outdoor units
unit below outdoor unit H 35m (Note)
unit above outdoor unit H 10m
Difference in height between indoor units H1 5m
Note: A trap is required at 5 m intervals from outdoor unit.
¢Refrigerant piping size²
(MT (Medium Temperature)) LRMEQ5~20AY1 (Unit : mm)
Outdoor unit side
Piping size
Liquid pipe Gas pipe
50m or less 50~130m 50m or less 50~130m
5A · 6A type φ9.5 × 0.8 (O type) φ12.7 × 0.8 (O type) φ19.1 × 1.0 (1/2H type) φ22.2 × 1.0 (1/2H type)
8A · 10A · 12A type φ9.5 × 0.8 (O type) φ12.7 × 0.8 (O type) φ25.4 × 1.0 (1/2H type) φ28.6 × 1.0 (1/2H type)
15A · 20A type φ12.7 × 0.8 (O type) φ15.9 × 1.0 (O type) φ31.8 × 1.1 (1/2H type) φ34.9 × 1.1 (1/2H type)
Piping between branching areas
(B, b, C, c)
Select the piping from the following table in accordance with the total capacity of indoor units
connected downstream.
No size after branching can exceed the size of any upstream piping.
Piping between branching areas and each unit
Adjust the size of the piping so that it will coincide with the size of piping connecting to the indoor unit.
(LT (Low Temperature)) LRLEQ5~20AY1 (Unit : mm)
Outdoor unit side
Piping size
Liquid pipe Gas pipe
50m or less 50~70m 25m or less 25~70mm
5A · 6A type φ9.5 × 0.8 (O type) φ12.7 × 0.8 (O type) φ19.1 × 1.0 (1/2H type) φ22.2 × 1.0 (1/2H type)
8A · 10A · 12A type φ9.5 × 0.8 (O type) φ12.7 × 0.8 (O type) φ25.4 × 1.0 (1/2H type) φ28.6 × 1.0 (1/2H type)
15A · 20A type φ12.7 × 0.8 (O type) φ15.9 × 1.0 (O type) φ31.8 × 1.1 (1/2H type) φ34.9 × 1.1 (1/2H type)
Piping between branching areas
(B, b, C, c)
Select the piping from the following table in accordance with the total capacity of indoor units
connected downstream.
No size after branching can exceed the size of any upstream piping.
Piping between branching areas and each unit
Adjust the size of the piping so that it will coincide with the size of piping connecting to the indoor unit.
H
Outdoor unit
Liquid piping
Gas piping
ABC D2
FED1
Showcase
H1
Unit
cooler
fed1
abc d2
Total capacity of indoor units after branching
Gas pipe size Liquid pipe size
Less than 6.0 kW φ12.7 × 0.8 (O type) φ6.4 × 0.8 (O type)
6.0 kW or over and less than 9.9 kW φ15.9 × 1.0 (O type)
φ9.5 × 0.8 (O type)
9.9 kW or over and less than 14.5 kW φ19.1 × 1.0 (1/2H type)
14.5 kW or over and less than 18.5 kW φ22.2 × 1.0 (1/2H type)
18.5 kW or over and less than 25.0 kW φ25.4 × 1.0 (1/2H type)
25.0 kW or over and less than 31.0 kW φ28.6 × 1.0 (1/2H type)
φ12.7 × 0.8 (O type)
31.0 kW or over φ31.8 × 1.1 (1/2H type)
Total capacity of indoor units after branching
Gas pipe size Liquid pipe size
Less than 2.3 kW φ12.7 × 0.8 (O type) φ6.4 × 0.8 (O type)
2.3 kW or over and less than 4.4 kW φ15.9 × 1.0 (O type)
φ9.5 × 0.8 (O type)
4.4 kW or over and less than 6.4 kW φ19.1 × 1.0 (1/2H type)
6.4 kW or over and less than 7.8 kW φ22.2 × 1.0 (1/2H type)
7.8 kW or over and less than 10.8 kW φ25.4 × 1.0 (1/2H type)
10.8 kW or over and less than 13.4 kW φ28.6 × 1.0 (1/2H type)
φ12.7 × 0.8 (O type)
13.4 kW or over φ31.8 × 1.1 (1/2H type)