Display No. 1: Target Evaporation Temperature
Displays target evaporation temperature which is set by using the target evaporation
temperature set with DIP switch of the outdoor unit and correction value of target
evaporation temperature by pressing BS button.
{
Display No. 13: Condensation pressure equivalent saturated temperature f (HP)
The value of saturated temperature calculated from the high pressure of display No. 3
{
Display No. 14: Evaporation pressure equivalent saturated temperature f (LP)
The value of saturated temperature calculated from the low pressure of display No. 2
{
Display No. 16: Suction air SH
The difference between the suction pipe temperature Ti of display No. 9 and the saturated
temperature at the low pressure of display No. 2.
{
Display No. 17: INV. compressor discharge pipe SH
The difference between the INV. compressor discharge pipe temperature Td1 of display
No. 6 and the saturated temperature at the high pressure of display No. 3.
{
Display No. 18: STD1 compressor discharge pipe SH
The difference between the STD1 compressor discharge pipe temperature Td2 of display
No. 7 and the saturated temperature at the high pressure of display No. 3.
{
Display No. 19: STD2 compressor discharge pipe SH
The difference between the STD2 compressor discharge pipe temperature Td3 of display
No. 8 and the saturated temperature at the high pressure of display No. 3.
{
Display No. 26: Value of operating compressor total frequency
The total frequency is calculated by the equation below.
Total frequency = frequency of INV. compressor + (frequency of STD compressor
1
×
number of STD compressor)
*1 The frequency of STD compressor is fixed to 166 Hz.