Commercial Air Conditioner
5. Installation Instructions
Please reference
corresponding
Operation & Installation Manua
948
1250
25
Power wiring Terminal
184 184
55
Screw Hole
580
70
380
18
340
18
(4xM10)
Oil trap setting requirement:
Oil trap is required no mater the outdoor unit is upper or lower than indoor unit, only when
the piping length is more than 10m.
Trap dimensions:
Setting method: install one oil trap for every 10 meters at the gas pipe.
Note: the drop between the oil trops should be 10m.
L
R
R
Gas pipe diameter Min. R (mm) L (mm)
φ15.88
40 80
φ19.05
40 80
φ25.4
40 80
φ31.8
60 90
φ38.1
60 100
11
HCFU-42HK03
Model: HCFU-42CH03
HCFU-42HK03