Haier AL36LP2VHA [11/42] Section 5 explaining operation to the end user

Содержание

Section 5 Explaining Operation to the End User ENGLISH Using the OPERATING INSTRUCTIONS explain to the user howto use the air conditioner the remote controller removing the air filters placing or removing the remote controller from the remote controller holder cleaning methods precautions for operation etc Recommend that the user read the OPERATING INSTRUCTIONS carefully Section 6 Seacoast Application The outdoor unit should be installed at least a mile away from the salt water including seacoasts and inland waterways If the unit installed from 1 z mile to 5 miles away from the salt water including seacoasts and inland waterways please follow the installation instruction below Install the outdoor unit in a place such as near buildings etc where it can be protected from sea breeze which can damage the outdoor unit If you cannot avoid installing the outdoor unit by the seashore construct a protection wall around it to block the sea breeze A protection wall should be constructed with a solid material such as concrete to block the sea breeze and the height and the width of the wall should be 1 5 times larger than the size of the outdoor unit Also secure over 28 in 700mm between the protection wall and the outdoor unit for exhausted air to ventilate Install the outdoor unit in a place where water can drain smoothly If you cannot find a place satisfying above conditions please contact manufacturer Make sure to clean the sea water and the dust on the outdoor coil SECTION A INSTALLATION PAGE 11