Kentatsu KSTT280HFAN1 [12/20] Expelling air
![Kentatsu KSTT280HFAN1 [12/20] Expelling air](/views2/1829790/page12/bgc.png)
10
Installation Manual
Use refrigerant tank to expel air (see Fig.6-2 and Fig.6-3 )
Screw up the pipe nuts at A, B, C and D completely.
Loosen and remove the square-head cover and the mainte-
nance orifice nut of valves A and B.
Connect the filler hose of the refrigerant tank with the mainte-
nance orifice of valve A.
Loosen the valve of the refrigerant tank, continue filling refriger-
ant for 6 seconds to expel the air, and tighten the nut of valve B
quickly.
Loosen the valve of the refrigerant tank again, and fill the
refrigerant for 6 seconds. Detect leak for all adapters at A, B, C
and D. After making sure that no leak exists, screw off the filler
hose. After all the filled refrigerant is expelled, screw up the
maintenance orifice nut of valve A quickly.
Open the square-head spools of valves A and B completely.
Tighten the square-head cover of valves A and B.
Use a vacuum pump to expel the air (Fig.6-4 ): (For method of
using the manifold valve, see the operation manual of manifold
valve)
Loosen and remove the maintenance orifice nut of valve A, and
connect the filler hose of the manifold valve to the maintenance
orifice of valve A (tighten both valve A and valve B).
Connect the filler hose adapter to the vacuum pump.
Open the low pressure (Lo) handle of the manifold valve
completely.
Start the vacuum pump to extract air. At the beginning of
extracting air, slightly loosen the maintenance orifice nut of valve
B, check whether any air enters it (the vacuum pump noise
changes, and the multimeter indicates from negative to 0). Then
tighten this maintenance orifice nut.
Upon completion of vacuuming, tighten the low pressure (Lo)
handle of the manifold valve completely and stop the vacuum
pump. Keep extracting air for over 15 minutes. Check whether
the multimeter points at -1.0X10 Pa(-76cmHg).
Loosen and remove the square-head cover of valves A and B.
After opening valves A and B completely, tighten the square-
head cover of valves A and B.
Remove the filler hose off the maintenance orifice of valve A, and
then tighten the nut.
Fig.6-4
Manifold valve
-76cmHg
Filler hose
Filler hose
V
a c u u
m p u
m
p
Hi -handle
Lo pressure valve
Multimeter manometer
Lo-handle
From the following table, select a method of expelling air.
If the air conditioner is relocated, be sure to use a vacuum pump
or refrigerant tank to expel air.
Use the refrigerant in the outdoor unit to expel air(see Fig.6-
2and
Fig.6-3)
Screw up the pipe nuts at A, B, C and D completely.
Loosen and remove the square-head cover of valves A and B,
rotate the square-head spool of valve B counterclockwise for 45
degrees and stay for about 10 seconds, and then close the
spool of valve B tightly.
Detect leak for all adapters at A, B, C and D. After making sure
that no leak exists, open the maintenance orifice nut of valve A.
After all air is expelled, tighten the maintenance orifice nut of
valve A.
Open the spools of valves A and B completely.
Tighten the square-head cover of valves A and B completely.
6.4 Expelling Air
Fig.6-2
Fig.6-3
Length of connective pipe
(single pass)
Procedure of expelling air
Less than 5m
5~15m
Use refrigerant in the outdoor unit
Use vacuum pump or refrigerant
tank.
A
B
C
D
Outdoor unit
Intdoor unit
Stop valve
Air side
Liquid side
pipe adapter
Table.6-2
Содержание
- Split duct air conditioner 1
- Caution 3
- Precautions 3
- Warning 3
- Accessories indoor unit 4
- Install φ10 pendant bolts or ground bolts 4
- Installating indoor unit 4
- Installation space 4
- Design and connection of duct 5
- Suspending the indoor unit 5
- Caution 6
- Dimension unit mm 6
- Important construction checkpoints 6
- Install the drainpipe 6
- Installating outdoor unit 6
- Rubbish is easy to accumulate at drain stream trap make 6
- Sure to install a plug or other things which is easy to clean 6
- Convey outdoor unit 7
- Installation space 7
- Installing the outdoor unit 7
- Top view of the outdoor unit multiple units installed 7
- Refrigerant pipe 8
- Size of outdoor unit pipes and piping methods 8
- Airtight test 9
- Open all valves 9
- Refrigerant leak precautions 9
- Refrigerant replenishment quantity 9
- Remove trash and moist in the pipe 9
- Schematic diagram of connection between indoor unit and outdoor unit 9
- Table 3 9
- Use a vacuum pump to create a vacuum 9
- Caution 10
- Completing the connection system name 10
- Heat insulation of the drain pipe 10
- Heat insulation of the pipe 10
- Heat insulation of the refrigerant pipe 10
- Install the connective pipe 10
- Precautions during brazing of lines 10
- Preparation before installation 10
- And vapor service valve service ports at the outdoor unit connect iow pressure nitrogen to the liquid line service port 11
- Caution 11
- Precautions during brazing service valve 11
- Protect the vapor valve with a wet rag and braze the vapor line connection 11
- Warning 11
- Expelling air 12
- Table 2 12
- Caution 13
- Electric connection 13
- Heat insulation 13
- Install the drain pipe 13
- Leak detection 13
- 12 60 40 14
- Connective wire of indoor outside unit 14
- Cool only 14
- Heat cool 14
- Indoor unit outdoor unit 14
- Rvv 300 500 2 1 m 14
- Rvv 300 500 3 2 m 14
- Rvv 300 500 4 1 m 14
- Rvvp 300 300 5 0 m 14
- Wire controls connective wire 14
- Ycw 450 750 5 6 m 14
- Electric wire diagram 15
- Indoor unit 15
- Outdoor unit 15
- Air inlet wooden grille 16
- Air outlet wooden grille 16
- Aluminium adhesive tape 16
- Auxiliary materials 16
- Duct wrapping tape 16
- Filter 16
- Ins tall the unit at the air outlet so that th e air flo ws smo othly a nd the noise is lowe r 2 the noise value v aries w ith the length 3 the hose j oint sh ould be bent le st detac hment of the p ipe 16
- Insta ll the u nit at th e air in let so that th e air flo ws smo othly a nd the noise is lowe r 2 the noise value v aries w ith the length 3 the hose j oint sh ould be bent le st detac hment of the p ipe 16
- Install the fillter at the main body grille in case the storey height is low and at the main body of the indoor unit in case the storey height is high 16
- Installation manual 16
- It cleans conveniently at the time of installing uninstalling the fillter 3 the button structure is easy to install and uninstall 16
- Linear diffuser 16
- Methods of configuring and selecting installation 16
- Rectangular 16
- Construction and ventilation pipeline design scheme 17
- Examples of construction and ventilation pipeline design scheme flowering hidden series 17
- Installation manual 17
- Caution 18
- Trial run 18
Похожие устройства
- Kentatsu KSFU120CFDN3 Инструкция по монтажу
- Kentatsu KSFU120CFDN3 Технические данные
- Kentatsu KSFU120CFDN3 Инструкция по эксплуатации
- Kentatsu KSRU120CFDN3 Инструкция по монтажу
- Kentatsu KSRU120CFDN3 Технические данные
- Kentatsu KSRU120CFDN3 Инструкция по эксплуатации
- Kentatsu KSRU61HFDN1 Инструкция по монтажу
- Kentatsu KSRU61HFDN1 Инструкция по эксплуатации
- Kentatsu KSRU70HFDN1 Инструкция по монтажу
- Kentatsu KSRU70HFDN1 Инструкция по эксплуатации
- Kentatsu KSFU61HFDN1 Инструкция по монтажу
- Kentatsu KSFU61HFDN1 Инструкция по эксплуатации
- Kentatsu KSFU70HFDN1 Инструкция по монтажу
- Kentatsu KSFU70HFDN1 Инструкция по эксплуатации
- Kentatsu KSFU76HFDN3 Инструкция по монтажу
- Kentatsu KSFU76HFDN3 Инструкция по эксплуатации
- Kentatsu KSFU140HFDN3 Инструкция по монтажу
- Kentatsu KSFU140HFDN3 Инструкция по эксплуатации
- Kentatsu KSRU140HFDN3 Инструкция по монтажу
- Kentatsu KSRU140HFDN3 Инструкция по эксплуатации