Panasonic WH-SDF14C9E [102/125] 2 outdoor current transformer open circuit f46

Panasonic WH-SDF16C9E8 [102/125] 2 outdoor current transformer open circuit f46
102
16.5.32 Outdoor Current Transformer Open Circuit (F46)
Malfunction Decision Conditions:
A current transformer (CT) open circuit is detected by checking the compressor running frequency (
rated
frequency) and CT detected input current (< 0.65A) for continuously 20 seconds.
Malfunction Caused:
1 CT defective.
2 Faulty outdoor unit PCB.
3 Compressor defective (low compression).
Abnormality Judgment:
Continue 3 times in 20 seconds.