SNR RDC-48-540-STD Инструкция онлайн [11/15] 747430

SNR RDC-48-540-STD Инструкция онлайн [11/15] 747430
Page 11 of 15
D
efinition is as below
Name of signal Definition Remark
L Live wire of AC input
N None wire of AC input
E PGND
STATE+
Positive port of on present signal which is short-circuit
with STATE- inside module
STATE-
Negative port of on present signal which is short-circuit
with STATE+ inside module
Internal short-circuit inside power
module via a 100Ω resistor, which
is low resistance when module is
on present when power
ALM+
Positive port of alert of no output and undervoltage,
alerting coupler output to collector
ALM-
Negative port of alert of no output and undervoltage,
alerting coupler output to emission
High resistance while module alert
and low while normal.
CLISTATE+
Positive port of alert signal of overload, alerting coupler
output to collector
CLISTATE-
Negative port of alert signal of overload undervoltage,
alerting coupler output to emission
High resistance while module alert
and low while normal.
CLICON Current limit control
Externally connect constant
current controlled circuit for the
use of current limit charge of
battery management
54V- 54V negative port of DC output
54V+ 54V positive port of DC output
LS Bus line of current share
LS